Electromagnetic Time Reversal Fault Location Method Based on Characteristic Frequency of Traveling Waves

被引:4
|
作者
Cui, Haonan [1 ]
Yang, Qing [1 ]
Sun, Jian [1 ]
Zhou, Tong [1 ]
He, Yanxiao [2 ]
机构
[1] Chongqing Univ, Dept Elect Engn, State Key Lab Power Transmiss Equipment & Secur &, Chongqing 400044, Peoples R China
[2] Chongqing Univ Technol, Liangjiang Int Coll, Chongqing 400044, Peoples R China
基金
中国国家自然科学基金;
关键词
Electromagnetic time reversal (EMTR); fault current signal energy (FCSE); fault location; 3-PHASE TRANSMISSION-LINES; NETWORKS;
D O I
10.1109/TPWRD.2023.3268201
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In its application to locate ground faults, the electromagnetic time reversal (EMTR) method uses voltage from only a single point. However, when a high-impedance fault (HIF) occurs, the reflected signal from the fault point is weak, leading to an error between the simulated and actual fault location results. This paper proposes a new EMTR method based on the characteristic frequency of the traveling wave reflecting from the fault point. First, the transient signal spectrum under different fault resistances was analyzed, and the reasons for the inapplicability of the existing EMTR method under HIF conditions were discussed. Subsequently, a single-end signal expression with fault resistance was deduced, and the applicability of the EMTR method, which involves calculating only the energy of the fault current at the characteristic frequency, was verified. A reduced-scale experiment and a simulation in PSCAD were performed, and the EMTR method and proposed method were compared. The results showed that the proposed method can be applied to different complex lines, and it outperforms the conventional EMTR method in the event of HIFs.
引用
收藏
页码:3033 / 3044
页数:12
相关论文
共 50 条
  • [21] Fault Location in Multi-Terminal HVDC Networks Based on Electromagnetic Time Reversal with Limited Time Reversal Window
    Razzaghi, Reza
    Paolone, Mario
    Rachidi, Farhad
    Descloux, Justine
    Raison, Bertrand
    Retiere, Nicolas
    2014 POWER SYSTEMS COMPUTATION CONFERENCE (PSCC), 2014,
  • [22] Fault Location Estimation based on Wavelet Analysis of Traveling Waves
    Kale, Vijay
    Bhide, Sudhir
    Bedekar, Prashant
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [23] High-impedance fault location method of three-phase distribution lines based on electromagnetic time reversal
    Sun, Jian
    Zhang, Xindong
    Wei, Siyu
    Luo, Qingliang
    Hu, Yi
    Yang, Qing
    ELECTRIC POWER SYSTEMS RESEARCH, 2022, 212
  • [24] Fault location of a DC distribution network based on a direct time reversal method
    Yang H.
    Zhu Z.
    Huang W.
    Yu W.
    Zhou S.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2022, 50 (16): : 66 - 75
  • [25] A Method Based on High Frequency Electromagnetic Transients for Fault Location on Grounding Grids
    Rodrigues, Nilton R. N. M.
    de Oliveira, Rodrigo M. S.
    Carvalho, Lorena F. P.
    de Almeida, Jose Felipe S.
    2013 SBMO/IEEE MTT-S INTERNATIONAL MICROWAVE & OPTOELECTRONICS CONFERENCE (IMOC), 2013,
  • [26] Study on fault location of distribution mixed feeders based on double terminal method of traveling waves
    Ji, Tao
    Sun, Tong-Jing
    Xu, Bing-Yin
    Chen, Ping
    Xue, Yong-Duan
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2006, 26 (12): : 89 - 94
  • [27] A Distribution Line Fault Location Estimation Algorithm Based on Electromagnetic Time-Reversal Method Calculated in the Finite Difference Time Domain
    Sun, Jian
    Yang, Qing
    Xu, Wenhua
    He, Wenlong
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2022, 64 (03) : 865 - 873
  • [28] A Data-Driven Fault Location Algorithm Based on the Electromagnetic Time Reversal in Mismatched Media
    Wang, Zhaoyang
    Chen, Zhe
    Paolone, Mario
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (05) : 3709 - 3721
  • [29] Distribution network fault location based on an electromagnetic time reversal P-parametric criterion
    Liu Q.
    Huang Y.
    Wang Y.
    Fu Y.
    Wang L.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2024, 52 (03): : 74 - 82
  • [30] Resolution of Misjudgment in Fault location of Transmission Line with Series Compensator Based on Electromagnetic Time Reversal
    Shang Liqun
    Hu Yanhai
    Huang Ruoxuan
    Yang Chenguang
    2019 IEEE 2ND INTERNATIONAL CONFERENCE ON ELECTRONICS AND COMMUNICATION ENGINEERING (ICECE 2019), 2019, : 310 - 314