Parametric analysis and optimization of a novel cascade compression-absorption refrigeration system integrated with a flash tank and a reheater

被引:32
作者
Faruque, Md Walid [1 ]
Khan, Yasin [1 ]
Nabil, Mahdi Hafiz [1 ]
Ehsan, M. Monjurul [1 ]
机构
[1] Islamic Univ Technol IUT, Dept Mech & Prod Engn, Gazipur 1704, Bangladesh
关键词
Absorption cycle; Cascade refrigeration; Flash tank; Exergy analysis; Comparative study; Optimization; VAPOR INJECTION CYCLE; EXERGY ANALYSIS; PERFORMANCE IMPROVEMENT; LITHIUM BROMIDE; ENERGY; LIQUID; WATER; MIXTURE;
D O I
10.1016/j.rineng.2023.101008
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This article presents a novel cascade configuration for a compression absorption refrigeration system by combing a single effect absorption cycle with a reheater at the higher temperature circuit (HTC) and a modified vapor compression cycle with the flash tank at the lower temperature circuit (LTC). The proposed refrigeration system is investigated by the energy and exergy method, parametric analysis, and optimization by genetic algorithm for two different refrigerant pairs. At the LTC, the R41 refrigerant pair is employed whereas, lithium bromide so-lution (LiBr/H2O) and ammonia solution (NH3/H2O) are employed at the HTC. A detailed energy and exergy analysis is performed between the conventional and novel systems to illustrate the improvement achieved by the proposed system. Results suggest that at an evaporator temperature of-35 degrees C, using the combination of R41 and LiBr/H2O, the proposed system is capable to achieve 15.39% higher COP and exergetic efficiency than the conventional cascade absorption cycle. Furthermore, by employing R41-NH3/H2O combination under identical working conditions, the proposed system has achieved 18.49% higher COP and exergy efficiency than the conventional system. Additionally, a comparative parametric analysis between the two refrigerant pairs in the proposed system is conducted. The analysis suggests that R41-LiBr/H2O refrigerant pair has a significant advantage over the R41-NH3/H2O refrigerant pair. Lastly, the optimization of the proposed system is conducted by implementing the genetic algorithm to determine the optimal operating conditions for maximum COP and exergy efficiency.
引用
收藏
页数:16
相关论文
共 50 条
  • [21] Multi-objective optimization and thermo-economic analysis of an enhanced compression-absorption cascade refrigeration system and ORC integrated system for cooling and power cogeneration
    Sun, Xiaojing
    Liu, Linlin
    Dong, Yachao
    Zhuang, Yu
    Li, Jiao
    Du, Jian
    Yin, HongChao
    ENERGY CONVERSION AND MANAGEMENT, 2021, 236
  • [22] Performance assessment of a solar based novel combined cycle using vapor compression-absorption refrigeration system for trigeneration application
    Khan, Yunis
    Singh, Pawan Kumar
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART C-JOURNAL OF MECHANICAL ENGINEERING SCIENCE, 2025,
  • [23] Thermodynamic analysis of hybrid heat source driven organic Rankine cycle integrated flash tank vapor-compression refrigeration system
    Ashwni
    Sherwani, Ahmad Faizan
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 129 : 267 - 277
  • [24] Thermodynamic analysis of a compression-absorption refrigeration air-conditioning system coupled with liquid desiccant dehumidification
    Su, Wei
    Zhang, Xiaosong
    APPLIED THERMAL ENGINEERING, 2017, 115 : 575 - 585
  • [25] Superstructure-Based Simultaneous Optimization of a Heat Exchanger Network and a Compression-Absorption Cascade Refrigeration System for Heat Recovery
    Sun, Xiaojing
    Liu, Linlin
    Dong, Yachao
    Zhuang, Yu
    Zhang, Lei
    Du, Jian
    INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2020, 59 (36) : 16017 - 16028
  • [26] OPTIMUM PARAMETRIC ANALYSIS BASED ON THERMODYNAMIC MODELING OF A COMPRESSION ABSORPTION CASCADE REFRIGERATION SYSTEM
    Ansari, Naushad Ahmad
    Arora, Akhilesh
    Samsher
    Manjunath, K.
    JOURNAL OF THERMAL ENGINEERING, 2020, 6 (04): : 559 - 576
  • [27] Thermodynamic and thermo-economic analysis of compression-absorption cascade refrigeration system using low-GWP HFO refrigerant powered by geothermal energy
    Salhi, Khelifa
    Korichi, Mourad
    Ramadan, Khaled M.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 94 : 214 - 229
  • [28] Thermodynamic performance study on a novel absorption- compression cascade refrigeration activated by an internal combustion engine
    Han, Xiaolong
    Li, Jianbo
    Kong, Xiangqiang
    Sun, Tao
    Zhang, Chen
    Yin, Li
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2021, 45 (06) : 9595 - 9612
  • [29] Thermodynamic analysis and optimization of double effect absorption refrigeration system using genetic algorithm
    Arshad, Muhammad Umer
    Ghani, Muhammad Usman
    Ullah, Atta
    Gungor, Afsin
    Zaman, Muhammad
    ENERGY CONVERSION AND MANAGEMENT, 2019, 192 : 292 - 307
  • [30] Thermo-Economic Assessment of Advanced Triple Cascade Refrigeration System Incorporating a Flash Tank and Suction Line Heat Exchanger
    Nabil, Mahdi Hafiz
    Khan, Yasin
    Faruque, Md Walid
    Ehsan, M. Monjurul
    ENERGY CONVERSION AND MANAGEMENT, 2023, 295