Climatic applicability of indirect evaporative cooling strategies for data centers in China

被引:10
|
作者
Cui, Xin [1 ]
Yang, Chuanjun [1 ]
Yan, Weichao [1 ]
Wang, Xinyu [1 ]
Liu, Yahui [1 ]
Jin, Liwen [1 ]
机构
[1] Xi An Jiao Tong Univ, Inst Bldg Environm & Sustainable Technol, Sch Human Settlements & Civil Engn, Xian 710049, Shaanxi, Peoples R China
来源
基金
中国国家自然科学基金;
关键词
Indirect evaporative cooling; Free cooling; Data center; Climate zone; Energy efficiency; ENERGY PERFORMANCE; AIR; COOLER; SIMULATION; SYSTEM; TEMPERATE; REGIONS;
D O I
10.1016/j.jobe.2023.108431
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Modern digital developments have propelled data center (DC) to prominence, with the cooling requirement being an important driver of its energy consumption. This study explores the climate application potential of indirect evaporative cooling (IEC) technology, which utilizes water evaporation for cooling. The IEC technology is considered as a promising avenue for energyefficient DC cooling system. This study reveals essential insights for optimizing DC cooling performance by analyzing different IEC operation modes, including dry mode, wet mode, and cascading hybrid mode. The selection of operation mode is closely related to climatic conditions, DC working conditions, and IEC cooling efficiency. Higher DC supply air temperatures extend dry mode cooling hours and decrease cascading hybrid mode hours. It enhances energy savings through better utilization of natural free cooling resources. Elevating IEC cooling efficiency expands dry mode cooling hours while reducing reliance on mechanical cooling, contributing to improved power usage effectiveness (PUE) and energy conservation. The analysis is based on a typical data center and considers representative cities in different climate zones of China, emphasizing the importance of reducing the PUE and energy consumption of the DC by adjusting the DC supply air temperature and improving the IEC cooling efficiency. This work provides a useful reference for customizing DC cooling strategies according to various climate differences, optimizing energy efficiency and promoting sustainable development.
引用
收藏
页数:17
相关论文
共 50 条
  • [21] Dynamic performance evaluation of porous indirect evaporative cooling system with intermittent spraying strategies
    Shi, Wenchao
    Min, Yunran
    Ma, Xiaochen
    Chen, Yi
    Yang, Hongxing
    Applied Energy, 2022, 311
  • [22] Experimental investigation of two-stage indirect/direct evaporative cooling system in various climatic conditions
    Heidarinejad, Ghassem
    Bozorgmehr, Mojtaba
    Delfani, Shahram
    Esmaeelian, Jafar
    BUILDING AND ENVIRONMENT, 2009, 44 (10) : 2073 - 2079
  • [23] Application of indirect evaporative cooling to variable domestic cooling load
    Joudi, KA
    Mehdi, SM
    ENERGY CONVERSION AND MANAGEMENT, 2000, 41 (17) : 1931 - 1951
  • [24] Indirect evaporative cooling of energy efficient building
    Arkar, C
    Novak, P
    STROJNISKI VESTNIK-JOURNAL OF MECHANICAL ENGINEERING, 1996, 42 (5-6): : 187 - 193
  • [25] ENERGY EFFICIENT DATA CENTERS USING EVAPORATIVE COOLING AND AIR SIDE ECONOMIZERS
    Iyengar, Madhusudan
    Schmidt, Roger
    PROCEEDINGS OF THE ASME PACIFIC RIM TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC SYSTEMS, MEMS AND NEMS 2011, VOL 2, 2012, : 623 - 627
  • [26] Experimental investigation on a loop thermosyphon with evaporative condenser for free cooling of data centers
    Shao, Shuangquan
    Liu, Haichao
    Zhang, Hainan
    Tian, Changqing
    ENERGY, 2019, 185 : 829 - 836
  • [27] Modeling of Indirect Evaporative Cooling Systems: A Review
    Caruana, Roberta
    De Antonellis, Stefano
    Marocco, Luca
    Guilizzoni, Manfredo
    FLUIDS, 2023, 8 (11)
  • [28] INDIRECT-DIRECT EVAPORATIVE COOLING SYSTEMS
    ESKRA, N
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1980, 22 (05): : 21 - 25
  • [29] Investigation of Sensible Cooling Performance in the Case of an Air Handling Unit System with Indirect Evaporative Cooling: Indirect Evaporative Cooling Effects for the Additional Cooling System of Buildings
    Kostyak, Attila
    Szekeres, Szabolcs
    Csaky, Imre
    BUILDINGS, 2023, 13 (07)
  • [30] Applicability of Solar Evaporative Cooling in Greenhouses productivity Improvement
    Merabti, Leila
    Abbas, Mohamed
    Taane, Walid
    PROCEEDINGS OF 2019 7TH INTERNATIONAL RENEWABLE AND SUSTAINABLE ENERGY CONFERENCE (IRSEC), 2019, : 223 - 226