Three-Dimensional FDTD-Based Simulation of Lightning-Induced Surges in Secondary Circuits With Shielded Control Cables Over Grounding Grids in Substations

被引:10
作者
Tatematsu, Akiyoshi [1 ]
Yamanaka, Akifumi [1 ]
机构
[1] Cent Res Inst Elect Power Ind, Yokosuka, Kanagawa 2400196, Japan
关键词
Cable shielding; Transient analysis; Surface impedance; Finite difference methods; Voltage measurement; Lightning; Substations; FDTD method; lightning; secondary circuits; shielded control cables; substations; transients; MULTIPHASE NETWORK EQUIVALENT; AIR-INSULATED SUBSTATION; INDUCED VOLTAGES; THIN WIRES; CURRENT TRANSFORMERS; COAXIAL CABLES; POWER-STATIONS; FREQUENCY; TRANSIENTS; MODEL;
D O I
10.1109/TEMC.2023.3245206
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Nowadays, plenty of sensitive electronic devices are installed in secondary circuits in substations. When lightning strikes a substation and transmission line, lightning currents flow into the grounding structure of the substation through shield wires and lightning surge arresters in the primary circuit, and lightning overvoltages are induced on control cables in the secondary circuit owing to the effect of transient ground potential rises of the grounding structure and electromagnetic coupling. Shielded control cables are one of the countermeasures against lightning overvoltage induced on control cables; thus, it is useful to evaluate the effectiveness of shielded control cables for designing protection measures properly. Recently, the finite-difference time-domain (FDTD) method, which is one of the full-wave numerical approaches, has been commonly used for simulating electromagnetic transient phenomena in grounding structures, such as the grounding grids of substations. In this work, first, we studied the modeling of tape-type shielded control cables used in substations for FDTD-based electromagnetic transient analyses. Then, using the control cable model, we simulated a test platform of primary and secondary circuits in a substation and calculated the transient response of a grounding grid and voltages induced on the control cable when a lightning impulse current was injected into the grounding grid. We then compared the calculated results with the measured waveforms for validation.
引用
收藏
页码:528 / 538
页数:11
相关论文
共 70 条
[1]   TRANSIENT-RESPONSE OF MULTI-CONDUCTOR TRANSMISSION-LINES EXCITED BY A NONUNIFORM ELECTROMAGNETIC-FIELD [J].
AGRAWAL, AK ;
PRICE, HJ ;
GURBAXANI, SH .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 1980, 22 (02) :119-129
[2]   Electromagnetic disturbances of control circuits in power stations and substations experienced in Japan [J].
Ametani, A. ;
Motoyama, H. ;
Ohkawara, K. ;
Yamakawa, H. ;
Suga, N. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2009, 3 (09) :801-815
[3]  
[Anonymous], 2014, CUDA Zone
[4]  
[Anonymous], 2013, GUID NUM EL AN METH
[5]  
[Anonymous], 2013, EMC POW PLANTS SUBST
[6]   Modeling of thin wires in a lossy medium for FDTD simulations [J].
Baba, Y ;
Nagaoka, N ;
Ametani, A .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2005, 47 (01) :54-60
[7]   Applications of the FDTD Method to Lightning Electromagnetic Pulse and Surge Simulations [J].
Baba, Y. ;
Rakov, Vladimir A. .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2014, 56 (06) :1506-1521
[8]   EMP COUPLING THROUGH CABLE SHIELDS [J].
CASEY, KF ;
VANCE, EF .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 1978, 20 (01) :100-106
[9]  
Celozzi S., 1993, P 10 EL COMP ZUR SWI, P493
[10]  
CIGRE Working Group C4.37, 2019, EL COMP METH LIGHTN