Thermal and experimental analysis of cross-flow closed cooling tower

被引:9
作者
Hassab, M. A. [1 ]
Mansour, M. Khamis [1 ]
Sadek, L. A. [2 ]
Qassem, M. A. [1 ]
机构
[1] Alexandria Univ, Fac Engn, Dept Mech Engn, Alexandria, Egypt
[2] Beirut Arab Univ, Fac Engn, Dept Mech Engn, Beirut, Lebanon
关键词
Cross-flow closed cooling; Experimental analysis; Effectiveness; Number of transfer units; (NTU); Enthalpy potential; WET; PERFORMANCE;
D O I
10.1016/j.aej.2023.02.012
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Background: Cross-flow closed cooling towers (CCCT) are an indirect-contact evapora-tive cooler in which ambient air, spray water, and process fluid work together. The thermal perfor-mance of this cooling tower has significant impact on the thermal performance of the system in which it is implemented. CCCT introduces considerable difficulty in its thermal analysis particularly because it has two-dimensional analysis in its heat characteristics. Methods: In this work, a novel correlation between the tower effectiveness (e) and its number of transfer units (NTU) was developed to simulate analytically the thermal performance/design of CCCT. This relationship is featured by its simplicity in use and has non-iterative procedure to be employed as the traditional one in the literature. Results: The new relationship was verified through comparison with experimental work. The simulated results from the new model show a satisfactory agreement with those obtained from the our experimental work of less than +/- 5%, less than +/- 2% difference from experimental work done by Jiang et al. [8], and with deviation of-3.89% from those obtained by Kroger [9]. On the other hand, there is a good agreement between the present model and those obtained from the traditional epsilon-NTU method with maximum deviation of-4.56%. Conclusions: These new correlations are handy to be used by the process engineer or CCCT designer and they are featured by direct input parameters and no need for iterative process.(c) 2023 THE AUTHORS. Published by Elsevier BV on behalf of Faculty of Engineering, Alexandria University. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/ licenses/by-nc-nd/4.0/).
引用
收藏
页码:739 / 746
页数:8
相关论文
共 12 条
[1]  
Baker D.R., 1961, J HEAT TRANSF, V83, P339, DOI DOI 10.1115/1.3682276
[2]   Thermal performance of cross flow cooling towers in variable wet bulb temperature [J].
Hajidavalloo, Ebrahim ;
Shakeri, Reza ;
Mehrabian, Mozaffar A. .
ENERGY CONVERSION AND MANAGEMENT, 2010, 51 (06) :1298-1303
[3]   Design of Cooling Towers by the Effectiveness-NTU Method [J].
Jaber, H. ;
Webb, R. L. .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1989, 111 (1-4) :837-843
[4]   Experimental and numerical analysis of a cross-flow closed wet cooling tower [J].
Jiang, Jing-Jing ;
Liu, Xiao-Hua ;
Jiang, Yi .
APPLIED THERMAL ENGINEERING, 2013, 61 (02) :678-689
[5]   Cooling tower performance evaluation:: Merkel, poppe, and e-NTU methods of analysis [J].
Kloppers, JC ;
Kröger, DG .
JOURNAL OF ENGINEERING FOR GAS TURBINES AND POWER-TRANSACTIONS OF THE ASME, 2005, 127 (01) :1-7
[6]   A critical investigation into the heat and mass transfer analysis of crossflow wet-cooling towers [J].
Kloppers, JC ;
Kröger, DG .
NUMERICAL HEAT TRANSFER PART A-APPLICATIONS, 2004, 46 (08) :785-806
[7]  
Kro ger D.G., 2004, AIR COOLED HEAT EXCH, V1, P236
[8]   Novel lumped modeling for determining thermal performance of DX evaporator under partially-wet and fully-wet conditions [J].
Mansour, M. Khamis ;
Hassab, M. A. .
APPLIED THERMAL ENGINEERING, 2016, 98 :1025-1035
[9]  
Merkel F, 1926, Z VER DTSCH ING, V70, P123
[10]  
Poppe M., 1991, VDI-Warmeatlas, V111, P1