SF6 decomposition behaviour under partial discharge of typical insulation defects in gas-solid insulated valve-side bushing of converter transformer

被引:11
|
作者
Cheng, Hongtu [1 ]
Zeng, Fuping [1 ,2 ,4 ]
Tang, Bowen [3 ,5 ]
Li, Haotian [1 ]
Tang, Ju [1 ,2 ]
Huang, Zujian [1 ]
Chao, Xianzong [1 ]
机构
[1] Wuhan Univ, Sch Elect Engn & Automat, Wuhan, Peoples R China
[2] Hubei Key Lab Power Equipment & Syst Secur Integra, Wuhan, Peoples R China
[3] Hubei Univ Technol, Sch Elect & Elect Engn, Wuhan, Peoples R China
[4] Wuhan Univ, Sch Elect Engn & Automat, Wuhan 430072, Peoples R China
[5] Hubei Univ Technol, Sch Elect & Elect Engn, Wuhan 430068, Peoples R China
关键词
RECOGNITION;
D O I
10.1049/hve2.12303
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper we investigated SF6 decomposition behaviour of typical insulation defects in gas-solid insulated converter transformer valve-side bushing under partial discharge (PD). Additionally, we compared the results with that of gas insulated switchgear (GIS). The results indicated that SF6 decomposition behaviour varies with the insulation defects type. For metal protrusion defects, the proportion ranking of CO2 and SO2 can be related to whether the needle tip is wrapped with epoxy resin-impregnated paper (ERIP). The proportion of carbon-containing products is much higher under contamination defect than under other defects. Moreover, the proportion of carbon-containing components is higher under flashover condition than under PD condition and is accompanied by the appearance of H2S and CS2. However, the yield of SO2F2 is always low. Compared to negative DC voltages, positive DC voltages have a higher proportion of carbon-containing components, mainly in the form of more CO2 and less SOF2. Compared to the PD decomposition behaviour of typical insulation defects in GIS, when PD involves ERIP, the proportion of carbon-containing products, especially CO2, is significant higher, while the proportion of sulphur containing products, especially SO2F2, is lower.
引用
收藏
页码:690 / 697
页数:8
相关论文
共 25 条
  • [21] Simultaneous and Dynamic Detection of SF6 Decomposition Products Under Partial Discharge Defect of Gas-Insulated Power Equipment by Fiber-Enhanced Raman Spectroscopy
    Kong, Weiping
    Liu, Qiang
    Li, Qiuchi
    Yao, Xinrong
    Wan, Fu
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2024, 31 (01) : 376 - 384
  • [22] Partial Discharge Characteristics of Epoxy Insulation Surface Under AC/LI Superimposed Voltages in SF6/N2 Gas Mixtures
    Zhou, Yang
    Han, Xutao
    Wang, Yanxin
    Niu, Lin
    Zhang, Xuanrui
    Qin, Yan
    Li, Junhao
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2024, 31 (06) : 3074 - 3082
  • [23] A Case Analysis of Particle Defects Found in 220kV GIS by Ultrasonic Partial Discharge and SF6 Gas Decomposition Products Joint Detection
    He, Jin
    Li, Songyuan
    Zhang, Chi
    Cao, Meng
    Chen, Rong
    Zhu, Xuliang
    INTERNATIONAL CONFERENCE ON PHYSICS, PHOTONICS AND OPTICAL ENGINEERING, ICPPOE 2022, 2023, 2440
  • [24] Influence of creeping distance and gas pressure on negative creeping discharge for composite insulation consisting of N2/SF6 and solid dielectric under pulse voltage
    Ueno, Hideki
    Ohnishi, Hiroshi
    Tada, Kazuya
    Onoda, Mitsuyoshi
    Nakayama, Hiroshi
    Japanese Journal of Applied Physics, Part 1: Regular Papers and Short Notes and Review Papers, 1999, 38 (7 A): : 4182 - 4186
  • [25] Influence of creeping distance and gas pressure on negative creeping discharge for composite insulation consisting of N2/SF6 and solid dielectric under pulse voltage
    Ueno, H
    Ohnishi, H
    Tada, K
    Onoda, M
    Nakayama, H
    JAPANESE JOURNAL OF APPLIED PHYSICS PART 1-REGULAR PAPERS SHORT NOTES & REVIEW PAPERS, 1999, 38 (7A): : 4182 - 4186