Experimental analysis of horizontal grounding wires buried in high-resistivity soils subjected to impulse currents

被引:7
作者
Alipio, Rafael [1 ]
Coelho, Vilson L. [2 ]
Canever, Gennaro L. [2 ]
机构
[1] CEFET MG Fed Ctr Technol Educ Minas Gerais, DEE Dept Elect Engn, Ave Amazonas 7675, BR-30510000 Belo Horizonte, MG, Brazil
[2] UNISATC, Univ Ctr SATC, Ave Pascoal Meller 73, BR-88805380 Criciuma, SC, Brazil
关键词
Grounding; Experimental response; Impulse response; Lightning; Frequency-dependent soil parameters; SIMULATION; ELECTRODES; EFFICIENCY; MODEL;
D O I
10.1016/j.epsr.2022.108761
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents experimental results of the ground potential rise (GPR) developed by grounding wires buried in high-resistivity soils and subjected to impulse currents. A large experimental dataset is presented, comprising grounding wire lengths ranging from 10 m to 50 m, buried in soils of resistivities between around 1100 Omega m to 1600 Om, and subjected to impulse currents with front-time ranging from around 1.2 mu s to 7 mu s. The experimental results further confirmed some important aspects regarding the lightning response of grounding electrodes buried in high-resistivity soils, namely the influence of the frequency dependence of soil parameters and the value of impulse impedance lower than the grounding resistance for electrodes shorter than effective length. Comparison between experimental and simulated results reinforces the need to consider the frequency-dependence of soil parameters for obtaining accurate results of the lightning response of grounding systems buried in poor conducting soils.
引用
收藏
页数:8
相关论文
共 21 条
[1]   The Effect of Frequency Dependence of Soil Electrical Parameters on the Lightning Performance of Grounding Systems [J].
Akbari, Majed ;
Sheshyekani, Keyhan ;
Alemi, Mohamad Reza .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2013, 55 (04) :739-746
[2]  
Alipio R., 2021, GROUND202021 9 LPE I, P93
[3]   A comprehensive analysis of the effect of frequency-dependent soil electrical parameters on the lightning response of wind-turbine grounding systems [J].
Alipio, Rafael ;
Conceicao, Daiane ;
De Conti, Alberto ;
Yamamoto, Kazuo ;
Dias, Rosilene N. ;
Visacro, Silverio .
ELECTRIC POWER SYSTEMS RESEARCH, 2019, 175
[4]   Modeling the Frequency Dependence of Electrical Parameters of Soil [J].
Alipio, Rafael ;
Visacro, Silverio .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2014, 56 (05) :1163-1171
[5]   Impulse Efficiency of Grounding Electrodes: Effect of Frequency-Dependent Soil Parameters [J].
Alipio, Rafael ;
Visacro, Silverio .
IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (02) :716-723
[6]   Frequency Dependence of Soil Parameters: Effect on the Lightning Response of Grounding Electrodes [J].
Alipio, Rafael ;
Visacro, Silverio .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2013, 55 (01) :132-139
[7]   MODELING ANTENNAS NEAR TO AND PENETRATING A LOSSY INTERFACE [J].
BURKE, GJ ;
MILLER, EK .
IEEE TRANSACTIONS ON ANTENNAS AND PROPAGATION, 1984, 32 (10) :1040-1049
[8]  
Caetano C.E.F., 2018, 2018 34th International Conference on Lightning Protection (ICLP), P1, DOI 10.1109/ICLP.2018.8503460
[9]   AN ELECTROMAGNETIC MODEL FOR TRANSIENTS IN GROUNDING SYSTEMS [J].
GRCEV, L ;
DAWALIBI, F .
IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (04) :1773-1779
[10]   Impulse Efficiency of Ground Electrodes [J].
Grcev, Leonid .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (01) :441-451