The Influence of Heat Transfer Coefficient α of Insulating Liquids on Power Transformer Cooling Systems

被引:8
作者
Goscinski, Przemyslaw [1 ]
Nadolny, Zbigniew [1 ]
Tomczewski, Andrzej [2 ]
Nawrowski, Ryszard [2 ]
Boczar, Tomasz [3 ]
机构
[1] Poznan Univ Tech, Inst Elect Power Engn, Fac Environm Engn & Energy, PL-60965 Poznan, Poland
[2] Poznan Univ Tech, Inst Elect Engn & Elect, Fac Control Robot & Elect Engn, PL-60965 Poznan, Poland
[3] Opole Univ Technol, Inst Elect Power Engn & Renewable Energy, Fac Elect Engn Automat Control & Informat, PL-45758 Opole, Poland
关键词
power transformers; insulating liquid; temperature distribution; heat transfer;
D O I
10.3390/en16062627
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The power transformer plays an important role in electric power systems. One of the conditions for the proper operation of the transformer is to ensure a sufficiently low temperature. This condition can be met if the heat exchange is effective. Heat transfer depends, among other things, on the electrically insulating liquid. The thermal property describing the ability of a liquid to transfer heat is the heat transfer coefficient alpha. At the design stage of the transformers, it is most often assumed that the value of the alpha coefficient is constant and equal to 100 W center dot m(-2)center dot K-1. Such simplifications can lead to the improper design of the transformer since this factor depends on many factors. The article presents the results of research on the dependence of the heat transfer coefficient alpha on the type of electrical insulation liquid, the thermal load of the cooled surface, and the length of the heating element. Four types of electrical insulating liquids were considered: mineral oil, synthetic ester, natural ester, and natural ester with reduced viscosity. The obtained results prove that the type of electrical insulating liquid and the thermal surface load value affect the alpha coefficient. The length of the heating element did not affect the alpha factor.
引用
收藏
页数:15
相关论文
共 28 条
[21]   Proposal of Physical-Statistical Model of Thermal Aging Respecting Threshold Value [J].
Soucek, Jakub ;
Trnka, Pavel ;
Hornak, Jaroslav .
ENERGIES, 2017, 10 (08)
[22]   A New Multi-Conductor Transmission Line Model of Transformer Winding for Frequency Response Analysis Considering the Frequency-Dependent Property of the Lamination Core [J].
Wang, Song ;
Guo, Ze ;
Zhu, Ting ;
Feng, Hanke ;
Wang, Shuhong .
ENERGIES, 2018, 11 (04)
[23]   Reliability Evaluation Method for Oil-Paper Insulation in Power Transformers [J].
Wang, Youyuan ;
Gong, Senlian ;
Grzybowski, Stanislaw .
ENERGIES, 2011, 4 (09) :1362-1375
[24]   Temperature Rise Calculation of Magnetic Core Considering the Temperature Effect of Magnetic Properties in an Electrical Steel Sheet [J].
Wang, Zhen ;
Xu, Kai ;
Du, Yufeng .
SYMMETRY-BASEL, 2022, 14 (11)
[25]  
Wisniewski S., 2009, HEAT TRANSFER BOOK
[27]   Streaming Electrification of C60 Fullerene Doped Insulating Liquids for Power Transformers Applications [J].
Zdanowski, Maciej .
ENERGIES, 2022, 15 (07)
[28]   Dual-Temperature Evaluation of a High-Temperature Insulation System for Liquid-Immersed Transformer [J].
Zhang, Xiaojing ;
Ren, Lu ;
Yu, Haichuan ;
Xu, Yang ;
Lei, Qingquan ;
Li, Xin ;
Han, Baojia .
ENERGIES, 2018, 11 (08)