On the effect of the transversal aspect ratio on the double-glazed solar air heater performance

被引:8
作者
Mzad, Hocine [1 ]
Bennour, Fethi [1 ,2 ]
机构
[1] Badji Mokhtar Univ Annaba, Mech Engn Dept, POB 12, DZ-23005 Annaba, Algeria
[2] Badji Mokhtar Univ Annaba, Lab Res Ind Risks Control & Safety, Annaba, Algeria
关键词
aspect ratio optimization; DG-SAH; efficiency; exergy; heat transfer; simulation; the Eismann correlation; OPTIMUM CHANNEL GEOMETRY; COLLECTOR ASPECT RATIO; EXERGY ANALYSIS; PLATE; ABSORBER; DESIGN; OPTIMIZATION; TEMPERATURE; EFFICIENCY; ENERGY;
D O I
10.1002/htj.22804
中图分类号
O414.1 [热力学];
学科分类号
摘要
The transversal aspect ratio of solar air heaters (SAHs) is a critical geometric parameter that influences the heat transfer from the absorber plate to the working fluid and, accordingly, the overall heat loss level. The present work addresses the effect of the aspect ratio on the performance of a solar air heating system and the behavior of heat transfer coefficients (HTCs) within it and along the flow channel. A mathematical model of energy-balance equations was formulated to examine and analyze the double-glazed solar air heater thermal behavior. The Eismann correlation, which is more accurate than Holland's correlation, was employed to determine the HTC between the two glass covers. The useful energy, Nusselt number (Nu), efficiency, overall loss, and HTCs as a function of the aspect ratio were evaluated across the collector length. On the basis of the findings, the higher the ratio, the better the efficiency of the SAH. Indeed, increasing the collector's cross-sectional aspect ratio (r) up to 19 increases useful energy efficiency by more than 87%, Nu by 84%, thermohydraulic efficiency from 0.4 to 0.76, and overall heat loss by 1.15 W/(m(2) K). Furthermore, reducing r from 19 to 2 will improve the collector power from 1.855 to 3.473 kW.
引用
收藏
页码:2771 / 2795
页数:25
相关论文
共 52 条
[1]   Experimental study of compound parabolic concentrator with flat plate receiver [J].
Abd, Hareth Maher ;
Alomar, Omar Rafae ;
Ali, Firas Aziz ;
Salih, Mothana M. Mohamed .
APPLIED THERMAL ENGINEERING, 2020, 166
[2]   Energy and exergy analysis of solar air heater having new design absorber plate with conical surface [J].
Abuska, Mesut .
APPLIED THERMAL ENGINEERING, 2018, 131 :115-124
[3]   Energetic and exegetic performance analysis of flat plate solar collector under variables heat transfer coefficient and inlet water temperature [J].
Ali, Sabhan Hamid ;
Alomar, Omar Rafae ;
Ali, Omar Mohammed .
CASE STUDIES IN THERMAL ENGINEERING, 2021, 28
[4]   Energy and exergy analysis of hybrid photovoltaic thermal solar system under climatic condition of North Iraq [J].
Alomar, Omar Rafae ;
Ali, Omar Mohammed .
CASE STUDIES IN THERMAL ENGINEERING, 2021, 28
[5]  
[Anonymous], 2017, ASHRAE FUNDAMENTALS
[6]   Energy and exergy analysis of different solar air collector systems with forced convection [J].
Bahrehmand, D. ;
Ameri, M. ;
Gholampour, M. .
RENEWABLE ENERGY, 2015, 83 :1119-1130
[7]   A dimensionless model for the outlet temperature of a nonisothermal flat plate solar collector for air heating [J].
Baritto, Miguel ;
Bracamonte, Johane .
SOLAR ENERGY, 2012, 86 (01) :647-653
[8]  
Bennour F., 2022, ENERGY HARVESTING SY, DOI [10.1515/ehs-2021-0089, DOI 10.1515/EHS-2021-0089]
[9]   A numerical study of the double-glazed solar air heater (DG-SAH) performance using optimized gas-filled interspaces [J].
Bennour, Fethi ;
Mzad, Hocine .
CASE STUDIES IN THERMAL ENGINEERING, 2022, 40
[10]   Review and performance evaluation of roughened solar air heaters [J].
Bisht, Vijay Singh ;
Patil, Anil Kumar ;
Gupta, Anirudh .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2018, 81 :954-977