Exergy, carbon footprint and cost lifecycle evaluation of cascade mechanical subcooling CO2 commercial refrigeration system in China

被引:25
作者
Dai, Baomin [1 ]
Cao, Yu [1 ]
Zhou, Xuan [1 ]
Liu, Shengchun [1 ]
Fu, Rao [1 ]
Li, Cenxi [1 ]
Wang, Dabiao [2 ]
机构
[1] Tianjin Univ Commerce, Tianjin Key Lab Refrigerat Technol, Tianjin 300134, Peoples R China
[2] Fuzhou Univ, Sch Chem Engn, Natl Engn Res Ctr Chem Fertilizer Catalyst NERC CF, Fuzhou 350002, Fujian, Peoples R China
基金
中国博士后科学基金; 中国国家自然科学基金;
关键词
CO2 booster refrigeration system; Multi-stage dedicated mechanical subcooling; Exergy analysis; Environment analysis; Economic analysis; HEAT-PUMP SYSTEM; FIELD-MEASUREMENTS; ENERGY; DIOXIDE;
D O I
10.1016/j.jclepro.2023.140186
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The concept of cascade mechanical subcooling is recommended to widen the application of natural working fluid CO2, improve the efficiency and reduce the carbon footprint of CO2 refrigeration system applied in commercial supermarket. Three potential configurations for CO2 system with integrated multi-stage dedicated mechanical subcooling (MS-DMS) are proposed as prospect solutions. Life cycle assessment is conducted from the viewpoint of exergy, carbon footprint and cost performance for the proposed refrigeration systems, and compared with baseline CO2 booster refrigeration system (BASE) and traditional R404A system. 8 representative cities located in diverse climatic zones across China are chosen as scenarios and discussed in detail. The results indicate the irreversible loss is efficiently reduced with the utilization of MS-DMS. The annual exergy efficiency of CO2 system integrated with triple-stage DMS (TS-DMS) is 11.92-18.48% higher than BASE. Life cycle climate performance (LCCP) is reduced by 6.87% when the TS-DMS is employed in Haikou in contrast to BASE from the perspective of carbon emissions. Additionally, the life cycle cost (LCC) is remarkably reduced by 6.8% compared with BASE. Consequently, MS-DMS CO2 systems are more suitable for the application in warm or hot regions in contrast to BASE due to its better emission reduction performance as well as lower life cycle cost.
引用
收藏
页数:19
相关论文
共 56 条
[31]   An experimental study on the use of variable capacity two-stage compressors in transcritical carbon dioxide light commercial refrigerating systems [J].
Kimura de Carvalho, Bruno Yuji ;
Melo, Claudio ;
Pereira, Roberto Horn .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 106 :604-615
[32]  
Li K, 2021, 13 NAT PEOPL C
[33]   Energetic, economic and environmental analysis of air source transcritical CO2 heat pump system for residential heating in China [J].
Liu, Shengchun ;
Li, Zheng ;
Dai, Baomin ;
Zhong, Zhifeng ;
Li, Hailong ;
Song, Mengjie ;
Sun, Zhili .
APPLIED THERMAL ENGINEERING, 2019, 148 :1425-1439
[34]   Energy improvements of CO2 transcritical refrigeration cycles using dedicated mechanical subcooling [J].
Llopis, Rodrigo ;
Cabello, Ramon ;
Sanchez, Daniel ;
Torrella, Enrique .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 55 :129-141
[35]   Performance of a new two-stage transcritical CO2 refrigeration cycle with two ejectors [J].
Manjili, F. Eskandari ;
Cheraghi, M. .
APPLIED THERMAL ENGINEERING, 2019, 156 :402-409
[36]   CO2 refrigeration system heat recovery and thermal storage modelling for space heating provision in supermarkets: An integrated approach [J].
Maouris, Georgios ;
Sarabia Escriva, Emilio Jose ;
Acha, Salvador ;
Shah, Nilay ;
Markides, Christos N. .
APPLIED ENERGY, 2020, 264
[37]   Performance analysis and exergoeconomic evaluation of a TRC system enhanced by a dedicated mechanical subcooling [J].
Miran, Ali Zahedi ;
Nemati, Arash ;
Yari, Mortaza .
ENERGY CONVERSION AND MANAGEMENT, 2019, 197
[38]   Annual performance of a supermarket refrigeration system using different configurations with CO2 refrigerant [J].
Mitsopoulos, Georgios ;
Syngounas, Evangelos ;
Tsimpoukis, Dimitrios ;
Bellos, Evangelos ;
Tzivanidis, Christos ;
Anagnostatos, Stavros .
ENERGY CONVERSION AND MANAGEMENT-X, 2019, 1
[39]   Assessment of the utilization of equivalent warming impact metrics in refrigeration, air conditioning and heat pump systems [J].
Mota-Babiloni, Adrian ;
Barbosa, Jader R., Jr. ;
Makhnatch, Pavel ;
Lozano, Jaime A. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2020, 129
[40]   Experimental assessment of dedicated and integrated mechanical subcooling systems vs parallel compression in transcritical CO2 refrigeration plants [J].
Nebot-Andres, Laura ;
Calleja-Anta, Daniel ;
Sanchez, Daniel ;
Cabello, Ramon ;
Llopis, Rodrigo .
ENERGY CONVERSION AND MANAGEMENT, 2022, 252