Finite Element Method Assisted Audible Noise Detection for Overhead Line Conductors Using the Cage Experiment

被引:0
|
作者
Li, Yigui [1 ]
Li, Qi [1 ,2 ]
Meng, Wei [3 ]
Tang, Qi [4 ]
Li, Li [3 ]
Hu, Jianlin [1 ]
Jiang, Xingliang [1 ]
机构
[1] Chongqing Univ, Xuefeng Mt Energy Equipment Safety Natl Observat &, Chongqing 400044, Peoples R China
[2] Univ Manchester, Dept Elect & Elect Engn, Manchester M13 9PL, England
[3] Guangdong Power Grid Co Ltd, Elect Power Res Inst, Guangzhou 510080, Peoples R China
[4] Ningbo Orient Wires & Cables Co Ltd, Ningbo 315801, Peoples R China
关键词
audible noise; corona cage; HVDC transmission lines; time-domain measurement; sound field simulation; finite element method; CORONA CURRENT;
D O I
10.3390/en16124564
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Audible noise (AN) has been the main concern in recent years when considering electromagnetic environmental impact in designing overhead lines (OHLs). Driven by the increased demand of high voltage direct current (HVDC) transmission lines, a novel corona cage experiment is built in association with an acoustic simulation using the finite element method (FEM). The characteristics of the acoustic wave propagation within the testing hall are analyzed using FEM, and the optimized locations for AN detection are determined. On the basis of complying with measurement standards, the location of the measurement is selected to be closer to the sound source and further away from the reflecting surface, to generate more accurate measurement results. In the designated test hall for this paper, the influence of refraction and reflection of sound waves is not obvious. The attenuation of sound waves below 4 kHz is negligible, while for higher frequencies such as 4 kHz and 8 kHz it is significant. Finally, FEM simulation is used to optimize the location for measurement microphones, and further experiments are carried out to verify its accuracy.
引用
收藏
页数:15
相关论文
共 50 条
  • [1] Evaluation of audible noise from surface processing conductors for AC overhead transmission line
    Miyajima, Kiyotomi
    Tanabe, Kazuo
    ELECTRICAL ENGINEERING IN JAPAN, 2007, 159 (03) : 19 - 25
  • [2] Evaluation of audible noise from surface processing conductors for AC overhead transmission line
    Miyajima, Kiyotomi
    Tanabe, Kazuo
    IEEJ Transactions on Power and Energy, 2006, 126 (04) : 415 - 420
  • [3] Experimental verification of the potential of superhydrophobic surfaces in reducing audible noise on HVAC overhead line conductors
    Zhang, Xu
    Cotton, Ian
    Li, Qi
    Rowland, Simon M.
    Emersic, Christopher
    Lian, Chengxing
    Li, Wenyuan
    HIGH VOLTAGE, 2022, 7 (04) : 692 - 704
  • [4] Audible noise spectrum characteristics of UHVDC positive line using corona cage
    Liu, Yuanqing
    Guo, Jian
    Lu, Jiayu
    Gaodianya Jishu/High Voltage Engineering, 2013, 39 (06): : 1324 - 1330
  • [5] Acoustic Noise Evaluation for Overhead Line Conductors Using an Anechoic Chamber
    Li, Qi
    Rowland, Simon M.
    Dupere, Iain
    Shuttleworth, Roger
    IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (04) : 1835 - 1843
  • [6] A Finite-Element Approach for Electric Field Computation at the Surface of Overhead Transmission Line Conductors
    Farah, Arthur A. M.
    Afonso, Marcio M.
    Vasconcelos, Joao A.
    Schroeder, Marco A. O.
    IEEE TRANSACTIONS ON MAGNETICS, 2018, 54 (03)
  • [7] Application of electric field calculation to measurement of audible noise from overhead transmission lines using corona cage
    Tatematsu, Akiyoshi
    Tanabe, Kazuo
    IEEJ Transactions on Fundamentals and Materials, 2012, 132 (02) : 156 - 165
  • [8] Possible Applications of the Method of Finite Elements to the Design of Overhead-line Conductors.
    Papailiou, Konstantin O.
    Mueller, Guenther
    Roll, Karl
    Elektrizitatswirtschaft, 1982, 81 (03): : 71 - 74
  • [9] Investigating tension in overhead high voltage power transmission line using finite element method
    Ahmad, Ashfaq
    Jin, Yi
    Zhu, Changan
    Javed, Iqra
    Akram, M. Waqar
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 114
  • [10] Evaluation of superconductor assisted machining (SUAM) with superconducting coated conductors using the finite element method
    Kinoshita, Y.
    Zhang, R.
    Otabe, E. S.
    Suzuki, K.
    Tanaka, Y.
    Nakashima, H.
    Nakasaki, T.
    32ND INTERNATIONAL SYMPOSIUM ON SUPERCONDUCTIVITY (ISS2019), 2020, 1590