Experimental study of pump-driven chip-level two-phase cooling system for data centres

被引:1
|
作者
Wang, Leixin [1 ]
Cheng, Hao [1 ]
Yang, Tongzhi [1 ]
Yuan, Weixing [1 ,3 ]
Ren, Kexian [1 ,2 ]
机构
[1] Beihang Univ, Sch Aeronaut Sci & Engn, Lab Ergon & Environm Control, Beijing, Peoples R China
[2] Tsinghua Univ, Sch Architecture, Dept Bldg Sci, Beijing, Peoples R China
[3] Beihang Univ, Sch Aeronaut Sci & Engn, Lab Ergon & Environm Control, 37 Xueyuan Rd, Beijing 100191, Peoples R China
关键词
Pump-driven; two-phase cooling; chip-level; energy saving; data centre; central processing units; internal refrigerant cycle; external water cycle; HEAT-PIPE SYSTEM; THERMAL MANAGEMENT; THERMOSIPHON LOOP; ENERGY; PERFORMANCE; AIR;
D O I
10.1177/1420326X231183300
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this study, we proposed and designed a pump-driven chip-level two-phase cooling system (PCTCS) and experimentally demonstrated that it can directly cool central processing units in data centres (DCs). The operation of the PCTCS involves an internal refrigerant cycle (IRC) and an external water cycle (EWC). Within the IRC, multiple mini-channel evaporators enable the dissipation of heat from the CPUs in the servers through a plate heat exchanger to initiate the EWC, which is followed by the dissipation of the heat to the environment. We performed experiments to systematically analyze the effects of key operation parameters on PCTCS performance of the IRC. The results indicated that the average and the highest core temperature of the CPUs were 76.3 degrees C and 79.0 degrees C, respectively, under extremely harsh heat dissipation conditions. The key driving component of the PCTCS is a refrigerant pump with high energy efficiency ratio (EERp) defined as ratio of heat dissipated by the power of the refrigerant pump. The EERp was 17-18 when the CPUs were at 0% load and 38-42 and 68-76 when the CPUs were at 50% and 100% loads, respectively. Moreover, optimizing the flow resistance of the IRC can improve the performance of the PCTCS.
引用
收藏
页码:57 / 73
页数:17
相关论文
共 45 条
  • [41] EXPERIMENTAL STUDY OF TWO-PHASE AIR/WATER FLOW IN A CENTRIFUGAL PUMP WORKING WITH A CLOSED OR A SEMI-OPEN IMPELLER
    Mansour, Michael
    Wunderlich, Bernd
    Thevenin, Dominique
    PROCEEDINGS OF THE ASME TURBO EXPO: TURBOMACHINERY TECHNICAL CONFERENCE AND EXPOSITION, 2018, VOL 9, 2018,
  • [42] EXPERIMENTAL CHARACTERIZATION OF CONFINED, PACKAGE-LEVEL DIRECT TWO-PHASE JET IMPINGEMENT COOLING WITH MICRO-PIN FIN SURFACE ENHANCEMENT
    Wu, Qianying
    Gong, Zheng
    Chan, Chih-Yao
    Kwon, Heungdong
    Goodson, Ken
    Wei, Tiwei
    PROCEEDINGS OF ASME 2023 INTERNATIONAL TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC MICROSYSTEMS, INTERPACK2023, 2023,
  • [43] DETAILED EXPERIMENTAL AND ANALYTICAL STUDY ON LONG TWO-PHASE CLOSED THERMOSIPHONS RELATED TO PASSIVE SPENT-FUEL POOL COOLING
    Grass, Claudia
    Kruessenberg, Anne
    Kulenovic, Rudi
    Weyermann, Fabian
    Starflinger, Joerg
    Schaffrath, Andreas
    PROCEEDINGS OF THE 26TH INTERNATIONAL CONFERENCE ON NUCLEAR ENGINEERING, 2018, VOL 6A, 2018,
  • [44] Experimental Investigation on Heat Transfer Mechanism of Air-Blast-Spray-Cooling System with a Two-Phase Ejector Loop for Aeronautical Application
    Li, Jia-Xin
    Li, Yun-Ze
    Cai, Ben-Yuan
    Li, En-Hui
    ENERGIES, 2019, 12 (20)
  • [45] Experimental study of gas-liquid two-phase operating characteristics and bubble evolution law of a semi-open mixed-flow pump
    Luo, Xingqi
    Yan, Sina
    Sun, Shuaihui
    Feng, Jianjun
    Xie, Hang
    Zhang, Lefu
    He, Denghui
    OCEAN ENGINEERING, 2023, 272