Comprehensive Study on Transformer Fault Detection via Frequency Response Analysis

被引:7
|
作者
Kakolaki, Seyed Ebrahim Hosseini [1 ]
Hakimian, Vahid [1 ]
Sadeh, Javad [1 ]
Rakhshani, Elyas [2 ]
机构
[1] Ferdowsi Univ Mashhad, Fac Engn, Mashhad 91779, Iran
[2] Delft Univ Technol, Dept Elect Sustainable Energy, NL-2628 CD Delft, Netherlands
关键词
INDEX TERMS Transformer fault detection; frequency response analysis; hybrid model; ladder model; configuration-transfer function pair; artificial intelligence; online frequency response analysis; SHORT-CIRCUIT FAULTS; POWER TRANSFORMERS; RADIAL DEFORMATION; AXIAL DISPLACEMENT; PART I; WINDING DISPLACEMENTS; TRANSIENT SIMULATION; DIAGNOSTIC-TECHNIQUE; MECHANICAL DEFECTS; FRA INTERPRETATION;
D O I
10.1109/ACCESS.2023.3300378
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The sudden outage of a transformer due to a fault can cause irreparable damage to the electricity industry. Hence, by conducting momentarily inspections of the transformer's condition, faults can be promptly detected, and the transformer can be disconnected from the power grid to prevent subsequent failures in this equipment. Detecting faults at an early stage can also result in reduced repair costs. One recent promising technique for fault detection is Frequency Response Analysis (FRA), which compares the transformer's response in healthy and faulty conditions for understanding the occurrence of transformer faults. This paper presents a comprehensive and accurate modeling approach for the behavior of the transformer at different frequencies, followed by an exposition of the requirements for implementing this method in order to find the fault type, severity, and location. Additionally, various methods for analyzing the results of frequency response are introduced and discussed. In this regard, attempts have been made to introduce advanced complementary methods to address the weaknesses and limitations of the frequency response method. Finally, the concepts are summarized, and suggestions for further research with applications in this field are presented and compared.
引用
收藏
页码:81852 / 81881
页数:30
相关论文
共 50 条
  • [21] Interpretation of Frequency Response Analysis for Fault Detection in Power Transformers
    Al-Ameri, Salem Mgammal
    Kamarudin, Muhammad Saufi
    Yousof, Mohd Fairouz Mohd
    Salem, Ali A.
    Siada, A. Abu
    Mosaad, Mohamed I.
    APPLIED SCIENCES-BASEL, 2021, 11 (07):
  • [22] Application of Frequency Response Analysis in Shunt Reactor Fault Detection
    Wang, Zaihua
    Ying, Guangyao
    Ma, Sicong
    Cai, Wenfang
    Li, Weijun
    2019 5TH INTERNATIONAL CONFERENCE ON GREEN POWER, MATERIALS AND MANUFACTURING TECHNOLOGY AND APPLICATIONS (GPMMTA 2019), 2019, 2185
  • [23] Time-frequency Analysis for Power Transformer Fault Detection Using Vibration Method
    Hong Kaixing
    Huang Hai
    Zheng Jing
    Zhou Jianping
    Zhou Yangyang
    Liu Jiangming
    PROCEEDINGS OF THE 2014 9TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA), 2014, : 2110 - +
  • [24] Transformer fault type discrimination based on window calculation method and frequency response analysis
    Vosoughi, Ahmad
    Samimi, Mohammad Hamed
    MEASUREMENT, 2022, 202
  • [25] Frequency Response and Vibration Analysis in Transformer Winding Turn-to-Turn Fault Recognition
    Bagheri, M.
    Phung, B. T.
    2016 INTERNATIONAL CONFERENCE ON SMART GREEN TECHNOLOGY IN ELECTRICAL AND INFORMATION SYSTEMS (ICSGTEIS), 2016, : 10 - 15
  • [26] TRANSFORMER FAULT DETECTION BY DISSOLVED GAS ANALYSIS
    WADDINGT.FB
    ALLAN, DJ
    ELECTRICAL REVIEW, 1969, 184 (21): : 751 - &
  • [27] Comparison of time and frequency method in fault detection for transformer windings
    Korenciak, Daniel
    Gutten, Miroslav
    Karman, Martin
    2022 INTERNATIONAL CONFERENCE ON DIAGNOSTICS IN ELECTRICAL ENGINEERING (DIAGNOSTIKA), 2022, : 162 - 165
  • [28] Modeling of a power transformer winding for deformation detection based on frequency response analysis
    Almas, Shintemirov
    Tang, Wenhu
    Wu, Q. H.
    PROCEEDINGS OF THE 26TH CHINESE CONTROL CONFERENCE, VOL 5, 2007, : 506 - +
  • [29] Detection and quantitative diagnosis of axial displacement of transformer winding by frequency response analysis
    Miyazaki, Satoru
    Tahir, Mehran
    Tenbohlen, Stefan
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2019, 13 (15) : 3493 - 3500
  • [30] A novel scheme for fault detection in PVmodules based on frequency response analysis
    Yokwana, X. P.
    Mosetlhe, T. C.
    Yusuff, A. A.
    2021 IEEE PES/IAS POWERAFRICA CONFERENCE, 2021, : 161 - 165