Investigation of Discharge Propagation in Localized High-Temperature SF6 Gas With Breakdown Voltage Measurement

被引:6
作者
Kotsuji, Hideyuki [1 ,2 ]
Kuroda, Mami [1 ]
Terada, Masanao [1 ]
Shiraishi, Katsuhiko [1 ]
Urai, Hajime [3 ]
Yokomizu, Yasunobu [2 ]
机构
[1] Hitachi Ltd, Ibaraki 3191292, Japan
[2] Nagoya Univ, Dept Elect & Elect Engn, Nagoya 4578530, Japan
[3] Daido Univ, Dept Elect Engn, Nagoya 4648603, Japan
关键词
Arc; circuit breaker; critical electric field; dielectric breakdown; discharge progress; gas flow; hot gas; nozzle; SF6; HOT SF6;
D O I
10.1109/TPS.2023.3238472
中图分类号
O35 [流体力学]; O53 [等离子体物理学];
学科分类号
070204 ; 080103 ; 080704 ;
摘要
In high-voltage gas circuit breakers (HVCBs), high-pressure gas is blown between the electrodes to cool the arc. The temperature distribution between the electrodes at the current zero point has a large gas temperature difference. This study aims to experimentally clarify the effect of the cold gas region on the breakdown voltage of gases with large temperature differences. In an experiment, a hot gas generator using arc heat was used to create a gas space with a large temperature difference between electrodes, and the breakdown voltage was evaluated. The breakdown voltage in the gas space with a cold gas region was twice that of the case, where the space between the electrodes was filled with hot gas. It was found that the discharge initiated in the hot gas region was suppressed in the cold gas region and that the breakdown voltage in a gas space with the hot and cold region was influenced by the existence of the cold gas.
引用
收藏
页码:429 / 436
页数:8
相关论文
共 15 条
[1]  
Dhotre MT, 2017, 2017 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), P201, DOI 10.1109/EIC.2017.8004627
[2]   PTFE Vapor Contribution to Pressure Changes in High-Voltage Circuit Breakers [J].
Gonzalez, Jean-Jacques ;
Freton, Pierre ;
Reichert, Frank ;
Petchanka, Arkadz .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2015, 43 (08) :2703-2714
[3]   Analysis of the Dielectric Breakdown Characteristics for a 252-kV Gas Circuit Breaker [J].
Jiang, Xu ;
Li, Xingwen ;
Zhao, Hu ;
Jia, Shenli ;
Yan, Jiu Dun ;
Zhu, Kai .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (03) :1592-1599
[4]   Analysis of Dielectric Breakdown of Hot SF6 Gas in a Gas Circuit Breaker [J].
Kim, Hong-Kyu ;
Chong, Jin-Kyo ;
Song, Ki-Dong .
JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2010, 5 (02) :264-269
[5]   Investigation on Pressure Build-Up and Blowing Processes by Multipoint Pressure Measurement and Fluid Analysis for Self-Blast-Type High-Voltage Circuit Breaker [J].
Kotsuji, Hideyuki ;
Sakuyama, Toshiaki ;
Terada, Masanao ;
Urai, Hajime .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2021, 49 (02) :854-861
[6]   Analytical Study on Electron Avalanche in Two Different Temperature and Pressure Regions for High-temperature SF6 Gas [J].
Kuroda, Mami ;
Yokomizu, Yasunobu ;
Terada, Masanao ;
Kotsuji, Hideyuki ;
Shiraishi, Katsuhiko ;
Urai, Hajime .
2022 6TH INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT - SWITCHING TECHNOLOGY (ICEPE-ST), 2022, :108-111
[7]  
Seeger M., 2019, PLASMA PHYS TECHNOL, V6, P39, DOI DOI 10.14311/PPT.2019.1.39
[8]  
Shinkai T., 2000, Transactions of the Institute of Electrical Engineers of Japan, Part B, V120-B, P81
[9]   Method of Evaluating Dielectric Interruption Capability of High-Voltage Circuit Breaker [J].
Terada, Masanao ;
Urai, Hajime ;
Ishikawa, Masanori ;
Shiraishi, Katsuhiko ;
Sakuyama, Toshiaki ;
Kotsuji, Hideyuki ;
Kuroda, Mami ;
Ishii, Tatsuya ;
Yokomizu, Yasunobu .
IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (05) :3885-3892
[10]   Method of Evaluating Exhaust Characteristics of High-Voltage Circuit Breaker [J].
Terada, Masanao ;
Urai, Hajime ;
Yokomizu, Yasunobu .
IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (02) :707-714