Impact of displacement ventilation and underfloor air distribution systems on concentrations of indoor particle in different seasons

被引:6
作者
Li, Linlin [1 ]
Yao, Cheng [1 ]
Liu, Wencheng [1 ]
Yin, Zuohong [1 ]
Huang, Weifang [1 ]
Yao, Yifeng [1 ]
Luo, Yang [1 ]
Huang, Yuandong [1 ]
机构
[1] Univ Shanghai Sci & Technol, Coll Environm & Architecture, Shanghai 200093, Peoples R China
来源
JOURNAL OF BUILDING ENGINEERING | 2024年 / 84卷
关键词
Indoor particles; Ventilation systems; CRE; DR; Thermal comfort; THERMAL COMFORT; PARTICULATE; ENERGY; DEPOSITION; DISPERSION; ROOM; CONTAMINANT; POLLUTANTS; TRANSPORT; POLLUTION;
D O I
10.1016/j.jobe.2024.108466
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The particle motion in a room is affected by the thermal environment and the air supply conditions caused by seasonal changes. In the study, a Lagrangian discrete trajectory model combined with the Eulerian fluid method was adopted to simulate the characteristics of indoor airflow and the diffusion of two typical indoor particles with considering different air supply conditions in different seasons. Specifically, the thermal comfort perception, draught rating (DR) of the indoor personnel, and the contaminant removal effectiveness (CRE, epsilon) of indoor particles under the influences of displacement ventilation (DV) and underfloor air distribution (UFAD) systems were investigated. The results revealed that when considering the indoor thermal comfort under summer and winter air supply conditions, UFAD was found be more effective than the DV system in protecting the temperature difference of indoor personnel. Additionally, the removal effect of PM1 in the breathing area was superior compared to that of the DV system. Regarding the removal effectiveness of PM2.5, the removal performance of both ventilation systems decreased, but the removal effect of the DV system on PM2.5 in the breathing area (with the largest epsilon l of 1.55) was significantly better than that of the UFAD system under winter operating conditions. It is essential for the selection of the ventilation system to consider the thermal comfort of indoor occupants, as different ventilation systems have varying capabilities to remove particles of different sizes. Therefore, choosing an appropriate ventilation system is crucial for enhancing indoor air quality, and the findings of this study provide a basis for improving indoor air quality.
引用
收藏
页数:24
相关论文
共 53 条
[1]   Saving energy by using underfloor-air-distribution (UFAD) system in commercial buildings [J].
Alajmi, Ali ;
El-Amer, Wid .
ENERGY CONVERSION AND MANAGEMENT, 2010, 51 (08) :1637-1642
[2]   Experimental evaluation of thermal comfort, ventilation performance indices and exposure to airborne contaminant in an airborne infection isolation room equipped with a displacement air distribution system [J].
Berlanga, F. A. ;
Ruiz de Adana, M. ;
Olmedo, I. ;
Villafruela, J. M. ;
San Jose, J. F. ;
Castro, F. .
ENERGY AND BUILDINGS, 2018, 158 :209-221
[3]   Airborne particulate matter and gaseous air pollutants in residential structures in Lodi province, Italy [J].
Cattaneo, A. ;
Peruzzo, C. ;
Garramone, G. ;
Urso, P. ;
Ruggeri, R. ;
Carrer, P. ;
Cavallo, D. M. .
INDOOR AIR, 2011, 21 (06) :489-500
[4]   Analysis on the impact of mean radiant temperature for the thermal comfort of underfloor air distribution systems [J].
Chung, Jae Dong ;
Hong, Hiki ;
Yoo, Hoseon .
ENERGY AND BUILDINGS, 2010, 42 (12) :2353-2359
[5]   Comparison study on air flow and particle dispersion in a typical room with floor, skirt boarding, and radiator heating systems [J].
Dehghan, Mohammad Hadi ;
Abdolzadeh, Morteza .
BUILDING AND ENVIRONMENT, 2018, 133 :161-177
[6]   A review of different ventilation modes on thermal comfort, air quality and virus spread control [J].
Fan, Man ;
Fu, Zheng ;
Wang, Jia ;
Wang, Zhaoying ;
Suo, Hanxiao ;
Kong, Xiangfei ;
Li, Han .
BUILDING AND ENVIRONMENT, 2022, 212
[7]   CFD MODELING OF THE AIR AND CONTAMINANT DISTRIBUTION IN ROOMS [J].
FAN, YC .
ENERGY AND BUILDINGS, 1995, 23 (01) :33-39
[8]   Modeling particle dispersion and deposition in indoor environments [J].
Gao, N. P. ;
Niu, J. L. .
ATMOSPHERIC ENVIRONMENT, 2007, 41 (18) :3862-3876
[9]  
Hesarakia Arefeh., 2015, SUSTAIN CITIES SOC, V19, P165
[10]   Validity of Orifice equation and impact of building parameters on wind-induced natural ventilation rates with minute mean wind pressure difference [J].
Jiang, Zitao ;
Kobayashi, Tomohiro ;
Yamanaka, Toshio ;
Sandberg, Mats ;
Kobayashi, Noriaki ;
Choi, Narae ;
Sano, Kayuki .
BUILDING AND ENVIRONMENT, 2022, 219