Impact of superconducting fault current limiters on Delayed Current Zeros in industrial power systems

被引:8
|
作者
Silva, R. F. [1 ]
Mafra, G. R. F. Q. [2 ]
Sotelo, G. G. [1 ]
Fortes, M. Z. [1 ]
Trillaud, F. [3 ]
Guillen, D. [4 ]
机构
[1] Fluminense Fed Univ UFF, Engn Sch, Passo Patria Str, 156, Room E347, BR-21240210 Niteroi, RJ, Brazil
[2] Petrobras SA, Republ Chile Str, 65, BR-20031912 Rio De Janeiro, RJ, Brazil
[3] Univ Nacl Autonoma Mexico, Inst Engn, Mexico City 04510, Mexico
[4] Tecnol Monterrey, Sch Engn & Sci, Monterrey 64849, Mexico
关键词
Superconductor fault current limiter; Delayed Current Zero; Vacuum circuit-breaker; Industrial power system; CIRCUIT-BREAKER; SIMULATIONS; PERFORMANCE;
D O I
10.1016/j.ijepes.2022.108594
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Electric power systems may exhibit fault currents with high asymmetry when generators are close to large motors and loads. In this condition and depending on the fault inception instants, the fault current waveforms may present Delayed Current Zeros (DCZ). During transient studies, in some cases, breakers do not see the current zero-crossing for several cycles. Indeed, if the breaker opens just after a transient when the current has not reached steady-state and may be offset by a slow exponentially decaying DC component, then, the breaker will fail to open as the current will not cross zero within the interruption time. Here, the main concern associated with DCZ is however related to the interruption of the circuit breakers on a current wave crossing zero. At this moment, the interruption is accompanied of an electrical arc having the potential to damage equipment. Resistive superconducting fault current limiters (r-SFCL) are a known solution to reduce the magnitude of short-circuit current in electrical systems. It is a versatile technology that can tackle both fault and stability issues in aging and modern power grids alike. As a side benefit, it may also address the DCZ problem. The present work aims at investigating the impact that an r-SFCL may have on DCZ and, in particular, its ability to eliminate this issue altogether. To that end, a r-SFCL based on an existing design was modeled using the consolidated thermal-electrical analogy. This approach has proven to be fairly accurate to model the transient behavior of the superconducting device. Here, the case study simulates a solid short-circuit at the terminal of a generator in a specific bus, simulating an industrial power system, that includes a circuit breaker, a motor load, and a r-SFCL. The electromagnetic transient computations were carried out considering load and no-load conditions with and without the r-SFCL. Eight scenarios were considered, showing that r-SFCLs can actually address DCZ in addition to limit the fault level.
引用
收藏
页数:9
相关论文
共 50 条
  • [21] Behaviors and Application Prospects of Superconducting Fault Current Limiters in Power Grids
    Shu, Bin
    Li, Xue N.
    Zhang, Kai
    Sun, Xin
    Li, Wei
    Liu, Zhao Y.
    Lou, Q. H.
    Liu, Yu
    Yao, Bao Q.
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2014, 24 (05)
  • [22] Prospective of Applications of Superconducting Fault Current Limiters in Chinese Power Grids
    Chen, Z. L.
    Gong, W. Z.
    Ren, A. L.
    Zi, M. R.
    Xiong, Z. Q.
    Si, D. J.
    Ye, F.
    SUPERCONDUCTIVITY CENTENNIAL CONFERENCE 2011, 2012, 36 : 894 - 901
  • [23] Non-superconducting fault current limiters
    Hagh, M. Tarafdar
    Abapour, M.
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2009, 19 (05): : 669 - 682
  • [24] Superconducting Fault Current Limiters Saving Rate
    Manusov, V. Z.
    Mikheyev, P. A.
    IFOST 2008: PROCEEDING OF THE THIRD INTERNATIONAL FORUM ON STRATEGIC TECHNOLOGIES, 2008, : 538 - 539
  • [25] Analysis of 3-Phase Superconducting Fault Current Limiters in Power Systems With Inhomogeneous Quenching
    Mansour, Diaa-Eldin A.
    Yehia, Doaa M.
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2013, 23 (03)
  • [26] Optimal location assignment and design of superconducting fault current limiters applied to loop power systems
    Hongesombut, K
    Mitani, Y
    Tsuji, K
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2003, 13 (02) : 1828 - 1831
  • [27] Utility Perspective on Fault Current Limiters and Expected Synergies from Integrating Fault Current Limiters with Superconducting Cables
    Duggan, P. M.
    2008 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, VOLS 1-11, 2008, : 2636 - 2637
  • [28] Integration of Fault Current Limiters in Electric Power Systems: A Review
    Ouali, Saad
    Cherkaoui, Abdeljabbar
    IEEE SYSTEMS JOURNAL, 2021, 15 (03): : 4470 - 4479
  • [29] Current-Time Characteristics of Resistive Superconducting Fault Current Limiters
    Blair, Steven M.
    Booth, Campbell D.
    Burt, Graeme M.
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2012, 22 (02)
  • [30] Safe Operation Improvement of an Electrical Power System by Superconducting Fault Current Limiters
    Chai, Yi
    Jiang, Congmei
    Zhang, Ke
    Xu, Shuiqing
    PROCEEDINGS OF THE 28TH CHINESE CONTROL AND DECISION CONFERENCE (2016 CCDC), 2016, : 1310 - 1314