Development and experimental study of a compact silica gel-water adsorption chiller for waste heat driven cooling in data centers

被引:18
作者
Du, Shuai [1 ]
Cui, Zhaopeng [1 ]
Wang, R. Z. [1 ]
Wang, Hongbin [1 ]
Pan, Quanwen [2 ]
机构
[1] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, 800 Dongchuan Rd, Shanghai 200240, Peoples R China
[2] Hangzhou City Univ, Cryogen Ctr, Hangzhou 310015, Peoples R China
基金
中国国家自然科学基金;
关键词
Compact adsorption chiller; Extra-low driving temperature; Silica gel-water; Data center; Waste heat recovery; COOLED DATA CENTERS; THERMAL MANAGEMENT; RECOVERY; AIR; PERFORMANCE; ART;
D O I
10.1016/j.enconman.2023.117985
中图分类号
O414.1 [热力学];
学科分类号
摘要
In recent years, data centers have experienced rapid construction, leading to a significant surge in energy consumption, and cooling systems have emerged as prominent energy consumers of data centers. Among the cooling technologies, liquid cooling allows higher cooling circuit temperatures and provides potential for heat recovery. As a thermally driven cooling technology, adsorption refrigeration systems offer an alternative way to compression refrigeration systems by utilizing low-grade waste heat from liquid-cooled circuits to produce chilled water for air-cooled components. In this study, a compact silica gel-water adsorption chiller is developed for a small modular data center and experimentally investigated under extremely low driving temperatures. Under the typical summer conditions with the hot/cooling/chilled water inlet temperatures of 50 degrees C/30 degrees C/ 23 degrees C, the adsorption chiller achieves the cooling power of 4.9 kW and the COP of 0.50. When the cooling water inlet temperature changes from 32 degrees C to 24 degrees C, both the cooling power and COP show significant improvements, from 3.04 kW to 10.50 kW and from 0.44 to 0.66, respectively. Moreover, the increase of the hot water inlet temperature from 48 degrees C to 56 degrees C can enhance the cooling power to some extent, while the chilled water inlet temperature has little influence on the performance. The experimental results demonstrate the feasibility and performance of the developed adsorption chiller in data center waste heat driven cooling. Besides, potential adsorbents and possible optimization strategies are presented for performance improvement based on adsorption potential method.
引用
收藏
页数:10
相关论文
共 33 条
[1]  
Andrae A, 2015, Challenges, V6, P117, DOI [10.3390/challe6010117, 10.3390/challe6010117, DOI 10.3390/CHALLE6010117]
[2]  
Araya Sebastian, 2018, 2018 17th IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm). Proceedings, P850, DOI 10.1109/ITHERM.2018.8419530
[3]   Cooling systems in data centers: state of art and emerging technologies [J].
Capozzoli, Alfonso ;
Primiceri, Giulio .
SUSTAINABILITY IN ENERGY AND BUILDINGS: PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE SEB-15, 2015, 83 :484-493
[4]   Experimental and numerical analysis for potential heat reuse in liquid cooled data centres [J].
Carbo, Andreu ;
Oro, Eduard ;
Salom, Jaume ;
Canuto, Mauro ;
Macias, Mario ;
Guitart, Jordi .
ENERGY CONVERSION AND MANAGEMENT, 2016, 112 :135-145
[5]   Thermodynamic analysis of hybrid cooling system integrated with waste heat reusing and peak load shifting for data center [J].
Chen, Hua ;
Peng, Yu-hang ;
Wang, Yan-ling .
ENERGY CONVERSION AND MANAGEMENT, 2019, 183 :427-439
[6]   Thermal management of air and liquid cooled data centres: A review [J].
Chethana, G. D. ;
Gowda, B. Sadashive .
MATERIALS TODAY-PROCEEDINGS, 2021, 45 :145-149
[7]   Adsorption-Driven Heat Pumps: The Potential of Metal-Organic Frameworks [J].
de Lange, Martijn F. ;
Verouden, Karlijn J. F. M. ;
Vlugt, Thijs J. H. ;
Gascon, Jorge ;
Kapteijn, Freek .
CHEMICAL REVIEWS, 2015, 115 (22) :12205-12250
[8]   The viability of ultra low temperature waste heat recovery using organic Rankine cycle in dual loop data center applications [J].
Ebrahimi, Khosrow ;
Jones, Gerard F. ;
Fleischer, Amy S. .
APPLIED THERMAL ENGINEERING, 2017, 126 :393-406
[9]   Thermo-economic analysis of steady state waste heat recovery in data centers using absorption refrigeration [J].
Ebrahimi, Khosrow ;
Jones, Gerard F. ;
Fleischer, S. .
APPLIED ENERGY, 2015, 139 :384-397
[10]   A review of data center cooling technology, operating conditions and the corresponding low-grade waste heat recovery opportunities [J].
Ebrahimi, Khosrow ;
Jones, Gerard F. ;
Fleischer, Amy S. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2014, 31 :622-638