Study of the operating characteristics of a pump-driven thermosyphon loop with gas-liquid separation

被引:4
|
作者
Wang, Leixin [1 ]
Cheng, Hao [1 ]
Yang, Tongzhi [1 ]
Zhao, Yifan [1 ]
Yuan, Weixing [1 ,3 ]
Ren, Kexian [2 ,3 ]
机构
[1] Beihang Univ, Sch Aeronaut Sci & Engn, Lab Ergon & Environm Control, 37 Xueyuan Rd, Beijing 100191, Peoples R China
[2] Tsinghua Univ, Sch Architecture, Dept Bldg Sci, Beijing 100084, Peoples R China
[3] Xiang Yang Solergy Technol Co Ltd, Xiangyang 441000, Peoples R China
关键词
Pump-driven; Thermosyphon loop; Gas-liquid separation; Data center; High efficiency; HEAT-PIPE SYSTEM; DATA CENTERS; THERMAL MANAGEMENT; COOLING SYSTEM; PERFORMANCE; FLOW; RECOVERY; UNIT;
D O I
10.1016/j.applthermaleng.2023.121265
中图分类号
O414.1 [热力学];
学科分类号
摘要
Pump-driven thermosyphon loop (PDTL) is a highly efficient cooling method for air-conditioning systems in data centers. Typically, the refrigerant in gas-liquid two-phase state leads to significant pressure drop in pipes following evaporator, which results in more energy consumption for data centers cooling. This study proposes a novel PDTL with gas-liquid separation (PDTLGLS), aiming to separate the gas-liquid phase refrigerant into liquid phase and gas phase, to reduce pressure drop following evaporator and improve the PDTL performance using a gas-liquid separator. Driven by the pressure difference between the gas-liquid separator and the reservoir, the gas-phase refrigerant is condensed into liquid-phase refrigerant back to the reservoir and the liquid-phase refrigerant returns to a reservoir directly without heat exchanging. This paper firstly conducted a theoretical analysis of PDTLGLS. Then the experiments were conducted using R134a to investigate the influence of refrig-erant flow rate and heating power on the performance of PDTLGLS. Furthermore, transient characteristics of the PDTLGLS were experimentally analyzed by varying the heating power. The experimental results show that the PDTLGLS achieves 36.8%-53.3% less heat dissipation temperature difference (from evaporator to condenser) and 28.3%-33.3% higher EER than traditional PDTL, and lower dryness could enlarge the PDTLGLS advantages. Furthermore, both analysis results and experimental results show that the PDTLGLS can adjust to diverse refrigerant mass flow and heating power via the self-regulation of the liquid height in the gas-liquid separator, which implies that the PDTLGLS is an effective way to enhance the traditional PDTL performance and could sustain stable operation across a broad spectrum of operating conditions.
引用
收藏
页数:11
相关论文
共 50 条
  • [31] Thermal performance of a multi-loop pump-driven heat pipe as an energy recovery ventilator for buildings
    Zhou, Feng
    Duan, Wei
    Ma, Guoyuan
    APPLIED THERMAL ENGINEERING, 2018, 138 : 648 - 656
  • [32] Evaluation of gas-liquid separation performance of natural gas filters
    Li Baisong
    Petroleum Science, 2009, (04) : 438 - 444
  • [33] Experimental Study of a Pump-Driven Microchannel-Separated Heat Pipe System
    Chen, Shengpeng
    Xu, Peng
    Shi, Juan
    Sheng, Lisha
    Han, Chaoling
    Chen, Zhenqian
    SUSTAINABILITY, 2023, 15 (24)
  • [34] Evaluation of gas-liquid separation performance of natural gas filters
    Li Baisong
    Ji Zhongli
    Yang Xue
    PETROLEUM SCIENCE, 2009, 6 (04) : 438 - 444
  • [35] Experimental investigation on a novel integrated system of vapor compression and pump-driven two phase loop for energy saving in data centers cooling
    Ma, Yuezheng
    Ma, Guoyuan
    Zhang, Shuang
    Xu, Shuxue
    ENERGY CONVERSION AND MANAGEMENT, 2015, 106 : 194 - 200
  • [36] The Software Design of a Gas-liquid Separation and Metering System
    Shen Huadong
    Xiao Xinhua
    MANUFACTURING SCIENCE AND TECHNOLOGY, PTS 1-8, 2012, 383-390 : 5286 - 5291
  • [37] The Structure Design of a Gas-Liquid Separation and Metering System
    Jiang Jinyu
    PROCEEDINGS OF THE 2011 INTERNATIONAL CONFERENCE ON INFORMATICS, CYBERNETICS, AND COMPUTER ENGINEERING (ICCE2011), VOL 2: INFORMATION SYSTEMS AND COMPUTER ENGINEERING, 2011, 111 : 41 - 48
  • [38] Experimental assessment of a new device for gas-liquid separation
    Noor, S.
    Soliman, H. M.
    CHEMICAL ENGINEERING RESEARCH & DESIGN, 2019, 149 : 45 - 51
  • [39] the Structure Design of a Gas-liquid Separation and Metering System
    Jiang Jinyu
    2010 INTERNATIONAL COLLOQUIUM ON COMPUTING, COMMUNICATION, CONTROL, AND MANAGEMENT (CCCM2010), VOL I, 2010, : 662 - 665
  • [40] A novel arterial Wick for gas-liquid phase separation
    Pour, Negar Beheshti
    Thiessen, David B.
    AICHE JOURNAL, 2019, 65 (04) : 1340 - 1354