Study of the operating characteristics of a pump-driven thermosyphon loop with gas-liquid separation

被引:6
作者
Wang, Leixin [1 ]
Cheng, Hao [1 ]
Yang, Tongzhi [1 ]
Zhao, Yifan [1 ]
Yuan, Weixing [1 ,3 ]
Ren, Kexian [2 ,3 ]
机构
[1] Beihang Univ, Sch Aeronaut Sci & Engn, Lab Ergon & Environm Control, 37 Xueyuan Rd, Beijing 100191, Peoples R China
[2] Tsinghua Univ, Sch Architecture, Dept Bldg Sci, Beijing 100084, Peoples R China
[3] Xiang Yang Solergy Technol Co Ltd, Xiangyang 441000, Peoples R China
关键词
Pump-driven; Thermosyphon loop; Gas-liquid separation; Data center; High efficiency; HEAT-PIPE SYSTEM; DATA CENTERS; THERMAL MANAGEMENT; COOLING SYSTEM; PERFORMANCE; FLOW; RECOVERY; UNIT;
D O I
10.1016/j.applthermaleng.2023.121265
中图分类号
O414.1 [热力学];
学科分类号
摘要
Pump-driven thermosyphon loop (PDTL) is a highly efficient cooling method for air-conditioning systems in data centers. Typically, the refrigerant in gas-liquid two-phase state leads to significant pressure drop in pipes following evaporator, which results in more energy consumption for data centers cooling. This study proposes a novel PDTL with gas-liquid separation (PDTLGLS), aiming to separate the gas-liquid phase refrigerant into liquid phase and gas phase, to reduce pressure drop following evaporator and improve the PDTL performance using a gas-liquid separator. Driven by the pressure difference between the gas-liquid separator and the reservoir, the gas-phase refrigerant is condensed into liquid-phase refrigerant back to the reservoir and the liquid-phase refrigerant returns to a reservoir directly without heat exchanging. This paper firstly conducted a theoretical analysis of PDTLGLS. Then the experiments were conducted using R134a to investigate the influence of refrig-erant flow rate and heating power on the performance of PDTLGLS. Furthermore, transient characteristics of the PDTLGLS were experimentally analyzed by varying the heating power. The experimental results show that the PDTLGLS achieves 36.8%-53.3% less heat dissipation temperature difference (from evaporator to condenser) and 28.3%-33.3% higher EER than traditional PDTL, and lower dryness could enlarge the PDTLGLS advantages. Furthermore, both analysis results and experimental results show that the PDTLGLS can adjust to diverse refrigerant mass flow and heating power via the self-regulation of the liquid height in the gas-liquid separator, which implies that the PDTLGLS is an effective way to enhance the traditional PDTL performance and could sustain stable operation across a broad spectrum of operating conditions.
引用
收藏
页数:11
相关论文
共 45 条
[1]   Experimental investigations of pump-driven closed-loop thermosyphon system [J].
Birajdar, Mahasidha R. ;
Sewatkar, Chandrasekhar M. .
HEAT TRANSFER, 2022, 51 (08) :7387-7410
[2]  
Brown G. O., 2003, Environmental and water resources history, P34, DOI [10.1061/40650%282003%294, DOI 10.1061/40650(2003)4, 10.1061/40650(2003)4]
[3]   Cooling systems in data centers: state of art and emerging technologies [J].
Capozzoli, Alfonso ;
Primiceri, Giulio .
SUSTAINABILITY IN ENERGY AND BUILDINGS: PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE SEB-15, 2015, 83 :484-493
[4]   Evaluation of air management system's thermal performance for superior cooling efficiency in high-density data centers [J].
Cho, Jinkyun ;
Kim, Byungseon Sean .
ENERGY AND BUILDINGS, 2011, 43 (09) :2145-2155
[5]   A review on airflow management in data centers [J].
Chu, Wen-Xiao ;
Wang, Chi-Chuan .
APPLIED ENERGY, 2019, 240 :84-119
[6]   A review of current status of free cooling in datacenters [J].
Daraghmeh, Hafiz M. ;
Wang, Chi-Chuan .
APPLIED THERMAL ENGINEERING, 2017, 114 :1224-1239
[7]   An Overview of Numerical Simulations on Gas-Solid Cyclone Separators with Tangential Inlet [J].
Dehdarinejad, Ehsan ;
Bayareh, Morteza .
CHEMBIOENG REVIEWS, 2021, 8 (04) :375-391
[8]   Principles of loop thermosyphon and its application in data center cooling systems: A review [J].
Ding, Tao ;
Chen, Xiaoxuan ;
Cao, Hanwen ;
He, Zhiguang ;
Wang, Jianmin ;
Li, Zhen .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2021, 150
[9]   Experimental study on a loop thermosyphon cooling system in data centers using CO2 as a working Fluid, especially thermal environment and energy-saving effect [J].
Ding, Tao ;
Cao, Han Wen ;
He, Zhi Guang ;
Wu, Jun Da ;
Li, Zhen .
APPLIED THERMAL ENGINEERING, 2020, 175
[10]   Experiment research on influence factors of the separated heat pipe system, especially the filling ratio and Freon types [J].
Ding, Tao ;
Cao, Han Wen ;
He, Zhi Guang ;
Li, Zhen .
APPLIED THERMAL ENGINEERING, 2017, 118 :357-364