Study of the operating characteristics of a pump-driven thermosyphon loop with gas-liquid separation

被引:4
|
作者
Wang, Leixin [1 ]
Cheng, Hao [1 ]
Yang, Tongzhi [1 ]
Zhao, Yifan [1 ]
Yuan, Weixing [1 ,3 ]
Ren, Kexian [2 ,3 ]
机构
[1] Beihang Univ, Sch Aeronaut Sci & Engn, Lab Ergon & Environm Control, 37 Xueyuan Rd, Beijing 100191, Peoples R China
[2] Tsinghua Univ, Sch Architecture, Dept Bldg Sci, Beijing 100084, Peoples R China
[3] Xiang Yang Solergy Technol Co Ltd, Xiangyang 441000, Peoples R China
关键词
Pump-driven; Thermosyphon loop; Gas-liquid separation; Data center; High efficiency; HEAT-PIPE SYSTEM; DATA CENTERS; THERMAL MANAGEMENT; COOLING SYSTEM; PERFORMANCE; FLOW; RECOVERY; UNIT;
D O I
10.1016/j.applthermaleng.2023.121265
中图分类号
O414.1 [热力学];
学科分类号
摘要
Pump-driven thermosyphon loop (PDTL) is a highly efficient cooling method for air-conditioning systems in data centers. Typically, the refrigerant in gas-liquid two-phase state leads to significant pressure drop in pipes following evaporator, which results in more energy consumption for data centers cooling. This study proposes a novel PDTL with gas-liquid separation (PDTLGLS), aiming to separate the gas-liquid phase refrigerant into liquid phase and gas phase, to reduce pressure drop following evaporator and improve the PDTL performance using a gas-liquid separator. Driven by the pressure difference between the gas-liquid separator and the reservoir, the gas-phase refrigerant is condensed into liquid-phase refrigerant back to the reservoir and the liquid-phase refrigerant returns to a reservoir directly without heat exchanging. This paper firstly conducted a theoretical analysis of PDTLGLS. Then the experiments were conducted using R134a to investigate the influence of refrig-erant flow rate and heating power on the performance of PDTLGLS. Furthermore, transient characteristics of the PDTLGLS were experimentally analyzed by varying the heating power. The experimental results show that the PDTLGLS achieves 36.8%-53.3% less heat dissipation temperature difference (from evaporator to condenser) and 28.3%-33.3% higher EER than traditional PDTL, and lower dryness could enlarge the PDTLGLS advantages. Furthermore, both analysis results and experimental results show that the PDTLGLS can adjust to diverse refrigerant mass flow and heating power via the self-regulation of the liquid height in the gas-liquid separator, which implies that the PDTLGLS is an effective way to enhance the traditional PDTL performance and could sustain stable operation across a broad spectrum of operating conditions.
引用
收藏
页数:11
相关论文
共 50 条
  • [1] Experimental investigations of pump-driven closed-loop thermosyphon system
    Birajdar, Mahasidha R.
    Sewatkar, Chandrasekhar M.
    HEAT TRANSFER, 2022, 51 (08) : 7387 - 7410
  • [2] Experimentally comparative study on two-phase natural and pump-driven loop used in HVAC systems
    Zhang, Penglei
    Li, Xianting
    Shi, Wenxing
    Wang, Baolong
    Rong, Xingyue
    APPLIED THERMAL ENGINEERING, 2018, 142 : 321 - 333
  • [3] Experimental research on dynamic characteristics and control strategy of the pump-driven two-phase loop with dual evaporators
    Zhang, Penglei
    Liu, Kehan
    Li, Yue
    Yang, Xiaorui
    Li, Xiaolin
    CASE STUDIES IN THERMAL ENGINEERING, 2022, 38
  • [4] Research on gas-liquid separation characteristics in the helico-axial multiphase pump
    Quan, Hui
    Sun, Jun
    Li, Yanan
    Liu, Xiaoyi
    Li, Jiayi
    Su, Houde
    PHYSICS OF FLUIDS, 2023, 35 (11)
  • [5] A heat pump-driven mechanical vapor compression desalination system and its operating characteristics
    Yang, Han
    Yang, Chunxin
    Geng, Leiming
    WATER RESOURCES AND INDUSTRY, 2024, 32
  • [6] Experimental research on the separation characteristics of a gas-liquid cyclone separator in WGS
    Zhou, Wen
    Chenglin, E.
    Fan, Yiping
    Wang, Kangsong
    Lu, Chunxi
    POWDER TECHNOLOGY, 2020, 372 (372) : 438 - 447
  • [7] Separation Characteristics in a Novel Gas-Liquid Vortex Separator
    Zhou, Wen
    Chenglin, E.
    Li, Zixuan
    Lu, Chunxi
    INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2020, 59 (40) : 18115 - 18125
  • [8] Experimental study of ventilation system with heat recovery integrated by pump-driven loop heat pipe and heat pump
    Liu, Shuailing
    Ma, Guoyuan
    Xu, Shuxue
    Jia, Xiaoya
    Wu, Guoqiang
    JOURNAL OF BUILDING ENGINEERING, 2022, 52
  • [9] Experimental study of pump-driven chip-level two-phase cooling system for data centres
    Wang, Leixin
    Cheng, Hao
    Yang, Tongzhi
    Yuan, Weixing
    Ren, Kexian
    INDOOR AND BUILT ENVIRONMENT, 2024, 33 (01) : 57 - 73
  • [10] Numerical study on a new separator for downhole gas-liquid separation
    Zeng, Xiaobo
    Zheng, Chunfeng
    Li, Ang
    Fan, Guangming
    Xiao, Youhong
    Yan, Changqi
    CHEMICAL ENGINEERING RESEARCH & DESIGN, 2025, 214 : 317 - 326