Reliability Assessment of Fixed Foam Systems of Storage Tank Based on Fuzzy Fault Tree Analysis

被引:0
作者
Ramezanifar, Ehsan [1 ]
Gholamizadeh, Kamran [1 ]
Mohammadfam, Iraj [2 ]
Aliabadi, Mostafa Mirzaei [2 ]
机构
[1] Hamadan Univ Med Sci, Occupat Hlth & Safety Res Ctr, Sch Publ Hlth, Dept Occupat Hlth Engn, Hamadan, Iran
[2] Hamadan Univ Med Sci, Occupat Hlth & Safety Res Ctr, Sch Publ Hlth, Dept Hlth, Hamadan, Iran
关键词
Fixed foam system; Reliability; Fuzzy Fault Tree Analysis; Storage tank; Safety barrierORIGINAL; RISK-ASSESSMENT; OIL; FIRE; GAS;
D O I
暂无
中图分类号
R1 [预防医学、卫生学];
学科分类号
1004 ; 120402 ;
摘要
Introduction: Risk assessment is a scale for predicting reliability and can manage interactions between components and process variables. Moreover, the reliability of one component or barrier affects the overall risk of the system. Being one of the most critical safety barriers of the storage tank, the failures of Fixed Foam Systems (FFS) on demand can result in severe consequences. FFS, is of grave importance in decreasing the risks associated with fires and damages.Material and Methods: This study aims to determine the probability of root causes related to FFS failure through Fuzzy Fault Tree Analysis (FFTA) to estimate system reliability. In conventional fault tree analysis, accurate data is usually used to assess the failure probability of basic events. Therefore, the introduced approaches were employed to quantify failure probabilities and uncertainty handling. Finally, system reliability was estimated according to the failure probability of the top event.Results: The findings showed that 13 baseline events involved FFS performance. According to the results, failures of cable path and detection system (or resistance temperature detectors), set the activation switch (multi-position) incorrectly, and foam makers not continuously running are the three most critical basic events influencing the reliability of fixed foam systems. In addition, this paper estimated the system reliability at 0.8470Conclusion: The results showed that the FFTA could be used in matters such as reliability evaluation failure and risk assessment using experts' judgment. This paper can also show the adaptation of the fuzzy approach to assess the failure probability of the basic event in the fault tree analysis (FTA).
引用
收藏
页码:1 / 17
页数:17
相关论文
共 50 条
[1]   Risk Assessment of Water Resources Development Plans Using Fuzzy Fault Tree Analysis [J].
Abedzadeh, Saeedeh ;
Roozbahani, Abbas ;
Heidari, Ali .
WATER RESOURCES MANAGEMENT, 2020, 34 (08) :2549-2569
[2]   Human reliability analysis in de-energization of power line using HEART in the context of Z-numbers [J].
Aghaei, Hamed ;
Mirzaei Aliabadi, Mostafa ;
Mollabahrami, Farzaneh ;
Najafi, Kamran .
PLOS ONE, 2021, 16 (07)
[3]   An Application of Fuzzy Fault Tree Analysis for Reliability Evaluation of Wind Energy System [J].
Akhtar, Iram ;
Kirmani, Sheeraz .
IETE JOURNAL OF RESEARCH, 2022, 68 (06) :4265-4278
[4]   Application of the bow-tie analysis technique in quantitative risk assessment of gas condensate storage considering domino effects [J].
Aliabadi, M. M. ;
Ramezani, H. ;
Kalatpour, O. .
INTERNATIONAL JOURNAL OF ENVIRONMENTAL SCIENCE AND TECHNOLOGY, 2022, 19 (06) :5373-5386
[5]  
Aliabadi MM, 2021, Saf Reliabil, V40, P48, DOI [10.1080/09617353.2020.1858242, DOI 10.1080/09617353.2020.1858242]
[6]   Human error analysis in furnace start-up operation using HEART under intuitionistic fuzzy environment [J].
Aliabadi, Mostafa Mirzaei .
JOURNAL OF LOSS PREVENTION IN THE PROCESS INDUSTRIES, 2021, 69
[7]  
American Petroleum Institute, 2007, API 650-2013 Welded tanks for oil storageS
[8]  
Association NFPA, 2012, FLAMM COMB LIQ COD H
[9]  
Bahrami S, 2021, J HEALTH SAF WORK, V11, P577
[10]  
Bakbaki A, 2017, J OCCUPATIONAL HYGIE, V4, P41