Energy efficiency evaluation for building air-conditioning systems determined by coincident design weather data

被引:4
|
作者
Xiao, Rui [1 ,2 ]
Chen, Youming [1 ,2 ]
Zhang, Xinchao [1 ,2 ]
Cao, Minghao [1 ,2 ]
Fang, Zhengcheng [1 ,2 ]
机构
[1] Hunan Univ, Coll Civil Engn, Changsha 410082, Hunan, Peoples R China
[2] Hunan Univ, Key Lab Bldg Safety & Energy Efficiency, Minist Educ, Changsha 410082, Hunan, Peoples R China
来源
基金
中国国家自然科学基金;
关键词
Coincident design day; Design weather data; Air-conditioning system design; Energy efficiency; Energy simulation; CONSUMPTION; LOAD;
D O I
10.1016/j.jobe.2024.108581
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Accurate design weather data are important for the energy efficiency of building air conditioning systems. Design cooling load of air conditioning system can be calculated accurately by coincident design day (CDD). It is important to evaluate the effect of coincident design day on the energy consumption and thermal comfort of air conditioning systems for promoting its application in engineering design. In this study, the coincident design days were determined and applied to the building's air-conditioning systems design. Using DesignBuilder simulations, cooling electricity consumption and thermal comfort performance of the proposed system have been investigated in three climate zones. A comparative assessment of the systems using coincident design days has been made against the systems using traditional design days. Results show that for the rooms with single external walls using the packaged terminal air conditioner (PTAC), the energy saved by coincident design days is 3.27%-7.19%, 1.43%-5.46%, and 2.25%-5.18% in Beijing, Changsha, and Hong Kong. For the whole buildings using fan coil with dedicated outdoor air (FCU + DOA), constant air volume (CAV), and variable air volume (VAV) systems, the energy saved by coincident design days is 11.38%-12.67%, 17.89%-17.9%, and 14.99%-16.06%, respectively in Beijing. In Changsha, these systems determined by coincident design days save energy are 11.19%-11.47%, 14.7%-17.82%, and 13.42%-16.05%. In Hong Kong, these systems determined by coincident design days save energy are 11.73%-12.48%, 17.97%-18.8%, and 14.99%-15.35%. The application of coincident design days to the CAV systems has the highest efficiency. These results demonstrate that the air conditioning systems determined by coincident design days can significantly reduce cooling energy consumption without affecting indoor thermal comfort, and fulfill the requirements of indoor thermal risk levels in the three climate zones of China.
引用
收藏
页数:21
相关论文
共 50 条
  • [41] Evaluation of normal-epidemic dual-purpose air conditioning systems in post-pandemic era based on conventional design weather data and coincident design days
    Fang, Zhengcheng
    Chen, Youming
    BUILDING AND ENVIRONMENT, 2024, 264
  • [42] Online Optimal Ventilation Control of Building Air-conditioning Systems
    Wang, Shengwei
    Sun, Zhongwei
    Sun, Yongjun
    Zhu, Na
    INDOOR AND BUILT ENVIRONMENT, 2011, 20 (01) : 129 - 136
  • [43] A Simplified Air-conditioning Systems Model with Energy Management
    Dejvises, Jackravut
    Tanthanuch, Nutthaphong
    2016 INTERNATIONAL ELECTRICAL ENGINEERING CONGRESS, IEECON2016, 2016, : 361 - 364
  • [44] AIR-CONDITIONING AND PARTICLE FILTRATION SYSTEMS FOR ENERGY SAVING
    TAKENAMI, T
    OHMI, T
    FUKUDA, S
    SOLID STATE TECHNOLOGY, 1989, 32 (04) : 161 - 168
  • [45] Energy simulation approach to air-conditioning system evaluation
    Sekhar, SC
    Yat, CJ
    BUILDING AND ENVIRONMENT, 1998, 33 (06) : 397 - 408
  • [46] Energy Efficient Demand Control for Air-Conditioning Systems
    Tomita, Yasushi
    Kuwabara, Kenichi
    Kobayashi, Nobuhisa
    Murata, Junichi
    Goda, Tadahiro
    2013 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PES), 2013,
  • [47] ENERGY CONSERVATION IN HEATING AND AIR-CONDITIONING PUMPING SYSTEMS
    RISHEL, JB
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1974, 16 (06): : 37 - 40
  • [48] Analysis of energy efficiency of displacement ventilation air-conditioning system
    Wang, Yueren
    Liu, Yuchuan
    Shenyang Jianzhu Daxue Xuebao (Ziran Kexue Ban)/Journal of Shenyang Jianzhu University (Natural Science), 2007, 23 (03): : 457 - 460
  • [49] Solid desiccant air-conditioning systems - Design parameters
    Panaras, G.
    Mathioulakis, E.
    Belessiotis, V.
    ENERGY, 2011, 36 (05) : 2399 - 2406
  • [50] Design of Efficient Air-Conditioning Systems for Electric Vehicles
    Torregrosa-Jaime, Barbara
    Paya, Jorge
    Corberan, Jose
    SAE INTERNATIONAL JOURNAL OF ALTERNATIVE POWERTRAINS, 2013, 2 (02) : 291 - 303