A novel noniterative single-ended fault location method with distributed parameter model for AC transmission lines

被引:2
作者
Duan, Mengzhao [1 ]
Liu, Yu [1 ,2 ]
Lu, Dian [1 ]
Pan, Ruiyu [1 ]
机构
[1] ShanghaiTech Univ, Sch Informat Sci & Technol, Shanghai 201210, Peoples R China
[2] Minist Educ, Key Lab Control Power Transmiss & Convers SJTU, Shanghai 200240, Peoples R China
基金
中国国家自然科学基金;
关键词
Fault location; Noniterative method; Single-ended measurements; Distributed parameter model; DYNAMIC STATE ESTIMATION; VOLTAGE;
D O I
10.1016/j.ijepes.2023.109358
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Fast and accurate fault location methods can save costs and ensure power supply reliability. This paper proposes a novel noniterative single-ended phasor domain fault location method with distributed parameter model for AC transmission lines. Due to the limitation of information, the legacy impedance-based single-ended fault location methods usually are based on assumptions on the line or system to obtain more information. The method proposed in this paper takes advantage of the additional information brought by the operation mode of circuit breakers. The proposed method only needs the local measurements and does not need the measurements and the equivalent source parameters of the remote system. The proposed method only uses single-ended data and is not affected by communication and synchronization. The proposed method is noniterative and there is no risk of nonconvergence. In addition, the method proposed in this paper does not rely on the assumptions of legacy methods and considers the distributed parameters, avoiding the disadvantages of the legacy methods. The effectiveness of the proposed method is verified through a lot of case studies in PSCAD/EMTDC, with different fault types, fault locations and resistances. & COPY; 2017 Elsevier Inc. All rights reserved.
引用
收藏
页数:14
相关论文
共 27 条
[1]  
[Anonymous], 2003, IEC Standard 61850
[2]  
[Anonymous], 2015, IEEE Standard C37.114-2014
[3]   A fast and accurate Bi-level fault location method for transmission system using single ended phasor measurements [J].
Arpanahi, Moossa Khodadadi ;
Fini, Masoud Hajiakbari ;
Khoshnama, Majid ;
Ghorbani, Amir .
ELECTRIC POWER SYSTEMS RESEARCH, 2022, 210
[4]   Asynchronous Fault Location Scheme Based on Voltage Distribution for Three-Terminal Transmission Lines [J].
Cao, Pulin ;
Shu, Hongchun ;
Yang, Bo ;
Fang, Yi ;
Han, Yiming ;
Dong, Jun ;
Yu, Tao .
IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (05) :2530-2540
[5]   A Single-Ended Fault Location Method for Grid-Connected Converter System Based on Control and Protection Coordination [J].
Chang, Peng ;
Song, Guobing ;
Hou, Junjie ;
Xu, Ruidong .
IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (04) :3071-3081
[6]   A Single-Terminal Fault Location Method for Transmission Lines Integrated by Inverter-Type Source [J].
Chang, Peng ;
Song, Guobing ;
Hou, Junjie ;
Xu, Ruidong .
IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (03) :1704-1713
[7]   AN ACCURATE FAULT LOCATOR WITH COMPENSATION FOR APPARENT REACTANCE IN THE FAULT RESISTANCE RESULTING FROM REMOTE-END INFEED [J].
ERIKSSON, L ;
SAHA, MM ;
ROCKEFELLER, GD .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1985, 104 (02) :424-436
[8]   Fault location on transmission lines based on travelling waves using correlation and MODWT [J].
Gonzalez-Sanchez, V. H. ;
Torres-Garcia, V. ;
Guillen, D. .
ELECTRIC POWER SYSTEMS RESEARCH, 2021, 197
[9]   A Generalized Closed-From Solution for Wide-Area Fault Location by Characterizing the Distributions of Superimposed Errors [J].
Jegarluei, Mohammad Rezaei ;
El-Gorashi, Taisir E. H. ;
Elmirghani, Jaafar M. H. ;
Azizi, Sadegh .
IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (06) :5484-5487
[10]   A New Single Ended Fault Location Method for Transmission Line Based on Positive Sequence Superimposed Network During Auto-Reclosing [J].
Ji, Liang ;
Tao, Xiaojie ;
Fu, Yang ;
Fu, Yong ;
Mi, Yang ;
Li, Zhenkun .
IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (03) :1019-1029