Experimental evaluation of individual effects of water mist spray characteristics on thermal radiation attenuation using twin-fluid nozzles with full-cone spray pattern

被引:2
作者
Jo, Jae Geun [1 ]
Lee, Chi Young [1 ,2 ]
机构
[1] Pukyong Natl Univ, Div Architectural & Fire Protect Engn, Busan, South Korea
[2] Pukyong Natl Univ, Dept Fire Protect Engn, Busan, South Korea
基金
新加坡国家研究基金会;
关键词
separate effect; spray characteristics; thermal radiation attenuation; twin-fluid nozzle; water mist; HEPTANE POOL FIRE; SUPPRESSION; PERFORMANCE; SYSTEM;
D O I
10.1002/prs.12421
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
In this study, the effects of water mist spray characteristics on thermal radiation attenuation were experimentally investigated using five types of external and internal mixing twin-fluid nozzles with a full-cone spray pattern. To the best of our knowledge, this may be the first attempt to experimentally examine the separate effects of water mist spray characteristics on thermal radiation attenuation. Water and air supply pressures were measured, and their values were 1.3-55.5 and 29.8-316 kPa, respectively. The Sauter mean diameter and volume median diameter of the water mist were measured to be 20-99 mu m and 21-108 mu m, respectively. The spray angle and width of the water mist were approximately 20 degrees and 110 mm, respectively. The thermal radiation attenuation afforded by the water mist discharged from the twin-fluid nozzle increased with increasing water and air flow rates and decreasing droplet sizes. Within the experimental range, the thermal radiation attenuation was approximately 6.9%-28.4%. Based on experimental data, the effects of the water flow rate and droplet size on thermal radiation attenuation were examined independently. The dependence of the thermal radiation attenuation on the droplet size was greater than that on the water flow rate.
引用
收藏
页码:141 / 154
页数:14
相关论文
共 28 条
  • [21] Murrell JV., 1995, HAL OPT TECHN WORK C
  • [22] Usui K., 2014, FIRE SAF SCI, P1196, DOI DOI 10.3801/IAFSS.FSS.11-1196
  • [23] Impact of scattered radiation on thermal radiation shielding by water curtains
    Voytkov, I. S.
    Volkov, R. S.
    Kopylov, N. P.
    Syshkina, E. Yu
    Tomilin, A., V
    Strizhak, P. A.
    [J]. PROCESS SAFETY AND ENVIRONMENTAL PROTECTION, 2021, 154 : 278 - 290
  • [24] A review on research status and key technologies of battery thermal management and its enhanced safety
    Wang, Yan
    Gao, Qing
    Wang, Guohua
    Lu, Pengyu
    Zhao, Mengdi
    Bao, Wendi
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2018, 42 (13) : 4008 - 4033
  • [25] Experimental study on the synergistic effect of gas extinguishing agents and water mist on suppressing lithium-ion battery fires
    Zhang, Lin
    Li, Yongqi
    Duan, Qiangling
    Chen, Man
    Xu, Jiajia
    Zhao, Chunpeng
    Sun, Jinhua
    Wang, Qingsong
    [J]. JOURNAL OF ENERGY STORAGE, 2020, 32
  • [26] Zhigang Liu Z., 1999, J. Fire Protect. Eng, V10, P32, DOI DOI 10.1177/104239159901000303
  • [27] Zhu N., 2003, INT J ENG PERFORM BA, V5, P170
  • [28] Experimental and numerical study on attenuation of thermal radiation from large-scale pool fires by water mist curtain
    Zhu, Pei
    Wang, Xishi
    Wang, Zhigang
    Cong, Haiyong
    Ni, Xiaomin
    [J]. JOURNAL OF FIRE SCIENCES, 2015, 33 (04) : 269 - 289