Comparative study on the thermal characteristics of natural draft wet cooling tower with internal and external auxiliary fans

被引:6
作者
Chen, Xuehong [1 ]
Sun, Fengzhong [2 ]
Xia, Lijiang [1 ]
Song, Xu [1 ]
Zhang, Xiaoyu [2 ]
机构
[1] Ludong Univ, Low Carbon Energy Inst, Yantai 264000, Peoples R China
[2] Shandong Univ, Sch Energy & Power Engn, Jinan 250061, Peoples R China
关键词
Natural draft wet cooling tower; Internal auxiliary fan; External auxiliary fan; Thermal performance; Environmental crosswind; Air deflector; Numerical calculation; NUMERICAL-SIMULATION; PERFORMANCE; VENTILATION; WALLS;
D O I
10.1016/j.ijheatmasstransfer.2022.123648
中图分类号
O414.1 [热力学];
学科分类号
摘要
Auxiliary ventilation is an innovative approach for strengthening the thermal performance of natural draft wet cooling towers, which can be implemented with internal and external fans. In this study, a threedimensional numerical model for cooling tower with these fans is established, with consideration of the existence or absence of air deflectors. To comparatively study the thermal performance of the above cooling towers, some critical parameters such as the air mass flow rate and circulating water temperature drop are computed, and the airflow and water temperature field are also investigated. Results manifest that external fans can enhance the air mass flow rate greater than internal fans under various crosswind velocities, while they are more effective in increasing the water temperature drop under a lower and a higher crosswind velocity, with a maximum increment of 8.5% and 10.0%, respectively. The addition of air deflectors narrows the high-velocity area, thus improving the uniformity of air distribution. The positive effect of air deflectors enhances with the increase of crosswind velocity, which decreases the water temperature drop of cooling tower with internal fans and that with external fans by 10.3% and 5.6% at most, respectively. This study can promote the engineering applications of auxiliary fans.(c) 2022 Elsevier Ltd. All rights reserved.
引用
收藏
页数:12
相关论文
共 37 条
  • [1] Novel model predictive control by hypothetical stages to improve energy efficiency of industrial cooling tower
    Agarwal, Neha Kumari
    Biswas, Pinakpani
    Shirke, Anand
    [J]. APPLIED THERMAL ENGINEERING, 2022, 215
  • [2] The effect of windbreak walls on the thermal performance of natural draft dry cooling towers
    Al-Waked, R
    Behnia, M
    [J]. HEAT TRANSFER ENGINEERING, 2005, 26 (08) : 50 - 62
  • [3] Enhancing performance of wet cooling towers
    Al-Waked, Rafat
    Behnia, Masud
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (10) : 2638 - 2648
  • [4] Critical guidelines to cope with the adverse impacts of the inner peripheral vortex in the high-level water collecting natural draft wet cooling tower
    Chen, Guangan
    Zhao, Yuanbin
    Ge, Wenjing
    Li, Wendong
    [J]. APPLIED THERMAL ENGINEERING, 2020, 168
  • [5] The efficiency of high-level water collecting cooling tower with the installation of cross wall affect by the evolution of aerodynamic field
    Chen, Guangan
    Zhao, Yuanbin
    Li, Wendong
    Ge, Wenjing
    [J]. APPLIED THERMAL ENGINEERING, 2019, 161
  • [6] Hot air extraction to improve aerodynamic and heat transfer performances of natural draft dry cooling system
    Chen, Lei
    Wang, Weijia
    Kong, Yanqiang
    Yang, Lijun
    Du, Xiaoze
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2020, 163
  • [7] Numerical study regarding cooling capacity for non-equidistant fillings in large-scale wet cooling towers
    Chen, Rui
    Zhang, Deying
    Zhang, Zhengqing
    Han, Qiang
    He, Suoying
    Gao, Ming
    [J]. CASE STUDIES IN THERMAL ENGINEERING, 2021, 26 (26)
  • [8] Field test study on water droplet diameter distribution in the rain zone of a natural draft wet cooling tower
    Chen, Xuehong
    Sun, Fengzhong
    Lyu, Dongqiang
    [J]. APPLIED THERMAL ENGINEERING, 2019, 162
  • [9] New retrofit method to improve the thermal performance of natural draft wet cooling towers based on the reconstruction of the aerodynamic field
    Chen, Xuehong
    Sun, Fengzhong
    Chen, Youliang
    Gao, Ming
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 132 : 671 - 680
  • [10] Novel method for improving the cooling performance of natural draft wet cooling towers
    Chen, Xuehong
    Sun, Fengzhong
    Chen, Youliang
    Gao, Ming
    [J]. APPLIED THERMAL ENGINEERING, 2019, 147 : 562 - 570