Data window selection for removal of decaying DC component in current phasor estimation for distance protection

被引:0
|
作者
Hajimahani, Mohammad Kazem [1 ]
Zamani, Hamid [1 ]
Jamali, Sadegh [1 ]
机构
[1] Iran Univ Sci & Technol, Sch Elect Engn, Ctr Excellence Power Syst Automat & Operat, Tehran, Iran
关键词
Distance protection; Decaying DC current; Transmission line; Data window; OFFSET; ALGORITHM; ACCURATE; SIGNAL;
D O I
10.1016/j.epsr.2023.109546
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In distance protection, the fault current signal is usually distorted by the decaying direct current (DC) and harmonics preventing accurate and fast estimation of the fault current phasor. This paper presents a method based on the carefully selected data windows and least square (LSQ) method to improve the performance of the current phasor estimation. The method comprises a short and variable data window for fast operation of distance relay for close faults and a fixed data window for the accurate operation of the relay for faults close to the boundary of Zone 1. The short and variable data window can achieve high speed in the phasor estimation in a quarter of cycle, whereas the second algorithm uses a fixed data window with an excellent frequency response to increase the accuracy of the phasor estimation. The proposed method is first tested using mathematical formulation under different conditions such as different characteristics of the DC component, noise, harmonics and frequency deviation. Then the method is tested by more realistic samples taken from a simulated transmission system under different fault conditions for flexibility, speed and accuracy. All the test results validate the aforementioned features of the proposed algorithms.
引用
收藏
页数:12
相关论文
共 28 条
  • [21] Modified Notch Filter-based Instantaneous Phasor Estimation for High-speed Distance Protection
    Soon-Ryul Nam
    Sang-Hee Kang
    Jin-Man Sohn
    Jong-Keun Park
    Electrical Engineering, 2007, 89 : 311 - 317
  • [22] Modified notch filter-based instantaneous phasor estimation for high-speed distance protection
    Nam, Soon-Ryul
    Sohn, Jin-Man
    Kang, Sang-Hee
    Park, Jong-Keun
    ELECTRICAL ENGINEERING, 2007, 89 (04) : 311 - 317
  • [23] Application of a Recursive Phasor Estimation Method for Adaptive Fault Component Based Differential Protection of Power Transformers
    Ashrafian, Abdolaziz
    Mirsalim, Mojtaba
    Masoum, Mohammad A. S.
    IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2017, 13 (03) : 1381 - 1392
  • [24] High-Frequency Fault Component Distance Protection for Flexible DC Distribution System
    Jia K.
    Zhao Q.
    Feng T.
    Zhao G.
    Bi T.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2020, 35 (02): : 383 - 394
  • [25] An effective method for impedance estimation in distance relay based on DC offset removal
    Vazquez M, Ernesto
    Ramirez, Juan M.
    Zamora, A.
    Paternina, M. R. A.
    2015 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, 2015,
  • [26] A Protection Scheme for Series Capacitor Compensated Transmission Lines that Uses DC Component of Line Current
    Razavi, Abbas Ali
    Samet, Haidar
    2013 21ST IRANIAN CONFERENCE ON ELECTRICAL ENGINEERING (ICEE), 2013,
  • [27] A novel AC line distance protection scheme for AC/DC hybrid system based on fault component energy equation
    Ma, Jing
    Liu, Chen
    Cheng, Peng
    Phadke, A. G.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 134
  • [28] IMPROVING THE PERFORMANCE OF DISTANCE RELAYS IN THE PROTECTION OF SHORT TRANSMISSION LINES BASED ON THE CURRENT ESTIMATION OF THE LINE END
    Hosseinimoghadam, Seyed Mohammad Sadegh
    Dashtdar, Masoud
    Dashtdar, Majid
    UNIVERSITY POLITEHNICA OF BUCHAREST SCIENTIFIC BULLETIN SERIES C-ELECTRICAL ENGINEERING AND COMPUTER SCIENCE, 2021, 83 (01): : 215 - 232