Theoretical and experimental studies for a transcritical CO2 heat pump with spirally fluted tube gas cooler

被引:5
|
作者
Wang, Wenyi [1 ]
Ye, Zuliang [2 ]
Yin, Xiang [1 ]
Song, Yulong [1 ]
Cui, Ce [1 ]
Cao, Feng [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Energy & Power Engn, Xian 710049, Peoples R China
[2] Zhongxing Telecommun Equipment Corp, Shenzhen 518057, Peoples R China
关键词
Transcritical CO 2 system; Spirally fluted gas cooler; Numerical simulation and experimental; research; Heat exchanger efficiency; number of transfer; units analysis; Exergy loss analysis; PRESSURE-DROP CHARACTERISTICS; CARBON-DIOXIDE; SUPERCRITICAL CO2; OPTIMIZATION; SYSTEMS; PERFORMANCE; EXCHANGER; ENERGY; MODEL; CYCLE;
D O I
10.1016/j.applthermaleng.2023.121414
中图分类号
O414.1 [热力学];
学科分类号
摘要
Transcritical CO2 system has been widely used in many fields to provide heating and cooling capabilities, and optimizing the structure of the gas cooler is an effective way to improve its performance. This paper presents a theoretical and experimental study of a spirally fluted tube-in-tube heat exchanger used as a gas cooler in a transcritical CO2 heat pump. The theoretical research uses numerical simulations to investigate the flow and heat transfer characteristics. The effect of the different CO2 mass flow rates, inlet pressure, and temperature on the performance of the spirally fluted gas cooler is evaluated and analyzed. The simulation results show that the spirally fluted structure can significantly improve the heat transfer performance of the CO2 side compared to the flat tube, which indicates that the spirally fluted gas cooler could be an effective way to enhance the operating performance of the transcritical CO2 system. Then experimental research is conducted in a transcritical CO2 heat pump prototype to validate the functional performance of the spirally fluted gas cooler. The effect of the different CO2 mass flow rates, inlet pressure and temperature, and the different water inlet and outlet temperatures on the performance of the spirally fluted gas cooler in the prototype are tested. The heat exchanger efficiency - number of transfer units (epsilon-NTU) method is employed to analyze the operating performance based on the experimental data. In addition, the exergy loss method is used to quantitatively evaluate the side-effect of the large pressure drop by the spirally fluted structure. Both the theoretical and experimental results show that the spirally fluted tube gas cooler can significantly improve the performance of the transcritical CO2 system. Besides, a heat transfer and friction coefficient correlation are established based on the experimental data for future research guidance.
引用
收藏
页数:13
相关论文
共 50 条
  • [31] Numerical investigation on cooling heat transfer and flow characteristics of supercritical CO2 in spirally fluted tube at various inclination angles
    Yu, Zhongyang
    Tao, Leren
    Huang, Lihao
    Wang, Dong
    Zhang, Suhan
    Yu, Qing
    Li, Meng
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2021, 166
  • [32] Experimental evaluation of transcritical CO2 refrigeration with mechanical subcooling
    Bush, John
    Beshr, Mohamed
    Aute, Vikrant
    Radermacher, Reinhard
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2017, 23 (06) : 1013 - 1025
  • [33] Experimental and numerical investigation of a CO2 heat pump system for electrical vehicle with series gas cooler configuration
    Wang, Yufeng
    Wang, Dandong
    Yu, Binbin
    Shi, Junye
    Chen, Jiangping
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 100 : 156 - 166
  • [34] Experimental investigation on the hot gas bypass defrosting in air source transcritical CO2 heat pump water heater
    Wang, Yikai
    Ye, Zuliang
    Song, Yulong
    Yin, Xiang
    Cao, Feng
    APPLIED THERMAL ENGINEERING, 2020, 178
  • [35] Comparative study of upgraded CO2 transcritical air source heat pump systems with different heat sinks
    Yao, Liang
    Li, Minxia
    Hu, Yusheng
    Wang, Qifan
    Liu, Xuetao
    APPLIED THERMAL ENGINEERING, 2021, 184 (184)
  • [36] An optimisation study on a real-world transcritical CO2 heat pump system with a flash gas bypass
    Wang, Ji
    Belusko, Martin
    Semsarilar, Hesam
    Evans, Michael
    Liu, Ming
    Bruno, Frank
    ENERGY CONVERSION AND MANAGEMENT, 2022, 251
  • [37] Exergy assessment of an optimized capillary tube-based transcritical CO2 heat pump system
    Agrawal, Neeraj
    Bhattacharyya, Souvik
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2009, 33 (14) : 1278 - 1289
  • [38] Experimental analysis of a tri-partite brazed plate gas cooler for CO2 heat pump water heaters
    Zendehboudi, Alireza
    APPLIED THERMAL ENGINEERING, 2024, 241
  • [39] Experimental and numerical study on transcritical CO2 air source heat pump water heater
    Li, Yifan
    Li, Mengxi
    Yang, Junlan
    APPLIED THERMAL ENGINEERING, 2025, 258
  • [40] Subcooling effect on the optimal performance for a transcritical CO2 heat pump with cold thermal energy storage
    Wang, Ji
    Evans, Michael
    Belusko, Martin
    Zhao, Chunrong
    Liu, Ming
    Bruno, Frank
    HEAT AND MASS TRANSFER, 2023, 59 (07) : 1257 - 1275