Experimental Study On Bird Streamer Flashover for V-Type Insulators of DC Transmission Line in High Altitude Area

被引:0
|
作者
Wang, Shenghui [1 ]
Lei, Shengfeng [1 ]
Zhou, Jun [2 ]
Ding, Yujian [2 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewable, Beijing 102206, Peoples R China
[2] China Elect Power Res Inst, Beijing 100192, Peoples R China
关键词
Birds; Flashover; Viscosity; Insulators; Conductivity; Discharges (electric); Power transmission lines; High altitude; DC; Bird streamer flashover; Protection range; Breakdown potential gradient; PREVENTIVE MEASURES; POWER OUTAGES;
D O I
10.1109/TPWRD.2022.3199262
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In order to obtain the bird streamer flashover characteristics in high altitude areas, the discharge of DC V-type string insulators was studied in high-altitude test base at 4300 m in Tibet. The study results show that medium viscosity bird streamer is easy to form a continuous channel and cause flashover. The flashover probability of positive polarity transmission lines is slightly higher than that of negative. The conductivity of bird excrement almost has no effect on the flashover probability in the range of 1.9 similar to 20.9 mS/cm. To increase the vertical air gap distance can reduce bird streamer flashover probability. Based on the experiment results, the recommended vertical air gap distance values of +/- 400 kV DC transmission line were proposed. Considering the influence of wind and bird streamer falling angle, the protection radius was set 3.5 m at 3500 similar to 5000 m altitude area. Bird streamer flashover is a mixed discharge of air gap breakdown and the surface discharge along the bird streamer channel, at the altitude of 4300 m area, the minimum breakdown potential gradient is about 2.1 kV/cm, and the discharge between bird streamer and shielding ring can be approximately equivalent to rod-rod gap discharge.
引用
收藏
页码:812 / 820
页数:9
相关论文
共 5 条
  • [1] Simulated Experimental Research on the Bird Streamer Flashover of DC Transmission Line in High Altitude Area
    Zhou J.
    Wang S.
    Ding Y.
    Wang X.
    Yao X.
    Gaodianya Jishu/High Voltage Engineering, 2020, 46 (04): : 1345 - 1352
  • [2] Study on pollution flashover characteristic of insulators on 500kV AC transmission lines in high-altitude area
    Huang, Ruiping
    Zhou, Jun
    Xu, Yueneng
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 3306 - 3309
  • [3] Study of DC Flashover Performance of Ice-covered Insulators at High Altitude
    Jiang, Xingliang
    Zhao, Shihua
    Hu, Jianlin
    Zhang, Zhijin
    Shu, Lichun
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (02) : 391 - 400
  • [4] Analysis and Protection Studies of Bird Droppings Falling on the Electric Field Distribution Near the 330-kV Transmission Line V-Type Composite Insulators
    Wang, Wenzhuo
    Ma, Zhenxiang
    Fan, Yudi
    Ma, Jianqiao
    Liu, Kang
    Wang, Yihu
    Xu, Hao
    IEEE ACCESS, 2024, 12 : 97938 - 97950
  • [5] Experimental Research and Conductor Selection on Electromagnetic Environment of ±500kV DC Transmission Line at High Altitude
    Zhao L.
    Xiao B.
    Wang B.
    Yue S.
    Gao L.
    Dianwang Jishu/Power System Technology, 2021, 45 (02): : 794 - 801