Assessing the Impact of Stochastic Demands and Fixture Purging on Free Chlorine Residuals in Premise Plumbing Systems

被引:1
作者
Clements, Emily [1 ,2 ]
Bibby, Kyle [1 ]
Nerenberg, Robert [1 ]
机构
[1] Univ Notre Dame, Dept Civil & Environm Engn & Earth Sci, Notre Dame, IN 46556 USA
[2] Southern Nevada Water Author, Henderson, NV 89015 USA
来源
ACS ES&T WATER | 2024年 / 4卷 / 04期
关键词
chlorine residuals; premiseplumbing; stochasticdemands; purging; flushing; EPANET; SIMDEUM; DRINKING-WATER; CHLORAMINE DECAY; BACTERIA; BULK; PIPE; AGE;
D O I
10.1021/acsestwater.3c00727
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In this study, we used modeling with stochastic demands to assess free chlorine concentrations in premise plumbing systems. Different occupancy scenarios and the use of automated purging devices at the fixtures were assessed. Chlorine concentrations were highly variable, so three novel metrics were proposed to assess the temporal distribution of chlorine residuals: the initial chlorine concentrations at fixtures for each use, the percentage of time a fixture was exposed to low chlorine concentrations (below 0.1 mg/L), and the durations of the low chlorine events. Showers, particularly those with lower occupancy, often had near-zero chlorine residuals. The chlorine residuals were below a 0.1 mg/L threshold 75% of the time for the one-person household but only 55% in a two-person household. 12-h scheduled purging reduced the percentage of time with low chlorine to 29% for the one-person household. Lower chlorine residuals in the water supply, smaller pipes, and longer service pipes resulted in substantially lower median chlorine concentrations at the fixtures. The choice of decay coefficients also had a large impact on the percentage of time with low chlorine. Overall, this research provides a new methodology to quantify and assess the highly variable chlorine concentrations in premise plumbing systems and the impacts of purging devices.
引用
收藏
页码:1668 / 1679
页数:12
相关论文
共 50 条
  • [1] Water quality modeling in the dead end sections of drinking water distribution networks
    Abokifa, Ahmed A.
    Yang, Y. Jeffrey
    Lo, Cynthia S.
    Biswas, Pratim
    [J]. WATER RESEARCH, 2016, 89 : 107 - 117
  • [2] Chlorine decay in drinking-water transmission and distribution systems: Pipe service age effect
    Al-Jasser, A. O.
    [J]. WATER RESEARCH, 2007, 41 (02) : 387 - 396
  • [3] Chlorine dioxide bulk decay prediction in desalinated drinking water
    Ammar, T. A.
    Abid, K. Y.
    El-Bindary, A. A.
    El-Sonbati, A. Z.
    [J]. DESALINATION, 2014, 352 : 45 - 51
  • [4] [Anonymous], 2017, Principles and Practices of Drinking-water Chlorination: A guide to strengthening chlorination practices in small-to medium-sized water supplies
  • [5] Comparison of Techniques for Maintaining Adequate Disinfectant Residuals in a Full-Scale Water Distribution Network
    Avvedimento, Stefania
    Todeschini, Sara
    Manenti, Sauro
    Creaco, Enrico
    [J]. WATER, 2022, 14 (07)
  • [6] Dead-end flushing of a distribution system: Short and long-term effects on water quality
    Barbeau, B
    Gauthier, V
    Julienne, K
    Carriere, A
    [J]. JOURNAL OF WATER SUPPLY RESEARCH AND TECHNOLOGY-AQUA, 2005, 54 (06): : 371 - 383
  • [7] Simulating Residential Water Demand with a Stochastic End-Use Model
    Blokker, E. J. M.
    Vreeburg, J. H. G.
    van Dijk, J. C.
    [J]. JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT-ASCE, 2010, 136 (01): : 19 - 26
  • [8] Blokker M., 2017, Drinking Water Engineering and Science, V10, P1
  • [9] Carrière A, 2005, J AM WATER WORKS ASS, V97, P82
  • [10] Optimizing DMAs' formation in a water pipe network: the water aging and the operating pressure factors
    Chondronasios, Apostolos
    Gonelas, Konstantinos
    Kanakoudis, Vasilis
    Patelis, Menelaos
    Korkana, Panagiota
    [J]. JOURNAL OF HYDROINFORMATICS, 2017, 19 (06) : 890 - 899