Optimal negative sequence current suppression strategy without phase-locked loop based on the control of clustered new energy power stations

被引:2
作者
Li, Zhenxing [1 ,2 ,3 ]
Zhu, Yi [2 ]
Hu, Cong [2 ]
Tan, Hong [2 ]
Weng, Hanli
Li, Zhenhua [1 ]
机构
[1] China Three Gorges Univ, Hubei Prov Key Lab Operat & Control, Cascaded Hydropower Stn, Yichang, Peoples R China
[2] China Three Gorges Univ, Coll Elect Engn & New Energy, Yichang, Peoples R China
[3] Three Gorges Univ, 8 Univ Rd, Xiling St, Yichang 443002, Hubei, Peoples R China
基金
中国国家自然科学基金;
关键词
capacity constraint; grid-connected inverter; negative sequence current suppression; none phase-locked loop (PLL); DESIGN; DFIG;
D O I
10.1049/gtd2.12870
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In the context of extremely uneven sources and loads in China, several large-scale power transmission systems have been established. Affected by the small equivalent impedance of the system, the increase of negative sequence currents during open-phase operation has seriously threatened the stable operation of synchronous generators. The necessity of negative sequence current suppression is particularly prominent. To address the above issues, this paper analyzes the feasible negative sequence suppression capacity of the grid-connected inverter under the principle of positive sequence priority. Using the geometric analysis method to determine the optimal suppression capacity. The none-phase-locked loop (PLL) control method is used to improve the response speed and form the negative sequence current suppression strategy adapted to the open-phase operation period. A simulation model was built in PSCAD to verify the effectiveness of the proposed strategy. The result shows that the suppression strategy has a faster response than the conventional PLL control. In scenarios with large negative sequence currents to be suppressed, a maximum suppression effect of approximately 63% can be achieved. Compared with the traditional suppression capacity selection, the strategy in this paper can reduce the residual of negative sequence current by about 10% at most. The negative sequence currents intruding into the generator can be effectively suppressed without additional devices. An optimal negative sequence suppression strategy without phase-locked loop (PLL) based on the control of clustered new energy power station is proposed. This strategy achieves effective suppression of negative sequence current during open-phase operation without additional devices. image
引用
收藏
页码:4248 / 4257
页数:10
相关论文
共 20 条
  • [1] Control Scheme for Negative-Sequence Voltage Compensation and Current Sharing in Inverter-Based Grid-Connected Microgrids
    Castilla, Miguel
    Velasco, Manel
    Miret, Jaume
    Borrell, Angel
    Guzman, Ramon
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2022, 37 (06) : 6556 - 6567
  • [2] Design and experimental investigation of digital model predictive current controller for single phase grid integrated photovoltaic systems
    Chatterjee, Aditi
    Mohanty, Kanungobarada
    Kommukuri, Vinaya Sagar
    Thakre, Kishor
    [J]. RENEWABLE ENERGY, 2017, 108 : 438 - 448
  • [3] A comprehensive review of virtual synchronous generator
    Cheema, Khalid Mehmood
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 120
  • [4] DSCC-MMC STATCOM Main Circuit Parameters Design Considering Positive and Negative Sequence Compensation
    Cupertino A.F.
    Farias J.V.M.
    Pereira H.A.
    Seleme S.I., Jr.
    Teodorescu R.
    [J]. Journal of Control, Automation and Electrical Systems, 2018, 29 (1) : 62 - 74
  • [5] Direct power control of voltage source inverters with unbalanced grid voltages
    Eloy-Garcia, J.
    Arnaltes, S.
    Rodriguez-Amenedo, J. L.
    [J]. IET POWER ELECTRONICS, 2008, 1 (03) : 395 - 407
  • [6] Single-Phase Enhanced Phase-Locked Loops Based on Multiple Delayed Signal Cancellation Filters for Micro-Grid Applications
    Gude, Srinivas
    Chu, Chia-Chi
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2019, 55 (06) : 7122 - 7133
  • [7] Control Scheme of Cascaded H-Bridge STATCOM Using Zero-Sequence Voltage and Negative-Sequence Current
    Hatano, Nobuhiko
    Ise, Toshifumi
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (02) : 543 - 550
  • [8] Modeling and enhanced control of DFIG under unbalanced grid voltage conditions
    Hu, Jiabing
    He, Yikang
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2009, 79 (02) : 273 - 281
  • [9] A Coordination Control With Extra Active Power Exchange Way to Extend Negative Sequence Current Compensation Range for STATCOM Based on Hybrid Cascaded Converter
    Lu, Daorong
    Wei, Miaoyu
    Shen, Shibin
    Hu, Haibing
    Xing, Yan
    Li, Xiang
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2022, 37 (12) : 15442 - 15456
  • [10] [孟建辉 Meng Jianhui], 2014, [电工技术学报, Transactions of China Electrotechnical Society], V29, P1