A Fault-Tolerant Control Strategy for Three-Level Grid-Connected NPC Inverters after Single-Arm Failure with Optimized SVPWM

被引:0
|
作者
Huang, Jingtao [1 ]
Bai, Feng [1 ]
Yang, Qing [1 ]
Ren, Shiyi [1 ]
Abu-Siada, Ahmed
机构
[1] Henan Univ Sci & Technol, Sch Informat Engn, Luoyang 471023, Peoples R China
基金
中国国家自然科学基金;
关键词
NPC inverter; fault-tolerant control; neutral point potential (NPP) fluctuation; SVPWM optimisation compensation; low pass filter; hysteresis comparator;
D O I
10.3390/en16237863
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Three-level NPC inverters have been widely used in grid-connected systems due to their superior performance compared with two-level inverters, but more switches lead to high fault probability. Meanwhile, the neutral point potential (NPP) fluctuation of the DC link is an inherent problem of three-level NPC inverters. To keep the three-level NPC inverter running stably after single-arm failure, a fault-tolerant control strategy based on an optimised space vector pulse width modulation (SVPWM) is proposed in this paper. Firstly, the common-mode voltage (CMV) of the postfault three-level NPC inverter is analysed and then the preliminary synthesis principles of the reference voltage vector are determined. Then, in order to ensure the NPP balance and the quality of the grid-connected currents, the reference voltage vector synthesis rules are optimised, a low-pass filter (LPF) and a hysteresis comparator are designed, respectively, to ensure the quality of grid-connected currents and effectively decrease the DC link NPP deviation. Finally, the simulation results show that the proposed fault-tolerant control strategy can realize the stable and reliable operation of the grid-connected three-level NPC inverter after single-arm failure, and the CMV can be reduced significantly, the quality of grid-connected currents is also improved. The proposed fault-tolerant strategy also shows good performance when the grid-connected currents change.
引用
收藏
页数:16
相关论文
共 19 条
  • [1] Open-Circuit Fault Diagnosis and Fault-Tolerant Control for a Grid-Connected NPC Inverter
    Choi, Ui-Min
    Lee, June-Seok
    Blaabjerg, Frede
    Lee, Kyo-Beum
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2016, 31 (10) : 7234 - 7247
  • [2] A Model Predictive Control based Fault-Tolerant Control Strategy for T-Type Three-Level Inverters
    Chen, Jie
    Chen, Alian
    Zhang, Chenghui
    Li, Ke
    2017 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2017, : 2839 - 2845
  • [3] Research on Unbalance Fault-Tolerant Control Strategy of Modular Multilevel Photovoltaic Grid-Connected Inverter
    Liu, Yiqi
    Li, Danhua
    Jin, Yu
    Wang, Qingbo
    Song, Wenlong
    ENERGIES, 2018, 11 (06):
  • [4] Fault-tolerant control for three-phase three-level T-type inverters with a redundant leg
    Chen, Danjiang
    Zheng, Liyuan
    ARCHIVES OF ELECTRICAL ENGINEERING, 2022, 71 (04) : 931 - 948
  • [5] Fault-Tolerant Three-Vector Model-Predictive-Control-Based Grid-Connected Control Strategy for Offshore Wind Farms
    Wu, Jiahui
    Li, Jiangyong
    Wang, Haiyun
    Li, Guodong
    Ru, Yalun
    ELECTRONICS, 2024, 13 (12)
  • [6] Fault Diagnosis and Fault-Tolerant Control of DC-link Voltage Sensor for Two-stage Three-Phase Grid-Connected PV Inverters
    Kim, Gwang-Seob
    Lee, Kyo-Beum
    Lee, Dong-Choon
    Kim, Jang-Mok
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2013, 8 (04) : 752 - 759
  • [7] Fault-Tolerant Control and Its Transit Process for Three-Level NPC Inverter Fed Induction Motor System
    Deng, Qingli
    Ge, Xingli
    PROCEEDINGS OF THE 15TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA 2020), 2020, : 921 - 926
  • [8] Fault-Tolerant Control of NPC Three-Level Inverters-Fed Double-Stator-Winding PMSM Drives Based on Vector Space Decomposition
    Wang, Zheng
    Wang, Yibo
    Chen, Jian
    Cheng, Ming
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2017, 64 (11) : 8446 - 8458
  • [9] Fault-Tolerant Control of Dual Three-phase PMSM Drives Fed by T-type Three-level Inverters
    Wang, Xueqing
    Wang, Zheng
    Xu, Zhixian
    Cheng, Ming
    2019 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2019, : 3178 - 3184
  • [10] Nonlinear control of grid-connected PV systems using active power filter with three-phase three-level NPC inverter
    Elallali, A.
    Abouloifa, A.
    Lachkar, I
    Taghzaoui, C.
    Giri, Fouad
    Mchaouar, Y.
    IFAC PAPERSONLINE, 2022, 55 (12): : 61 - 66