Distribution networks reliability assessment considering distributed automation system with penetration of DG units and SOP devices

被引:9
作者
Shafik, M. B. [1 ,2 ]
Elbarbary, Zakaria M. S. [3 ]
Bu, Siqi [2 ]
Azmy, Ahmed M. [4 ]
Hussien, Mohamed G. [4 ,5 ]
机构
[1] Kafrelsheikh Univ, Fac Engn, Dept Elect Engn, Kafrelsheikh 33516, Egypt
[2] Hong Kong Polytech Univ, Dept Elect & Elect Engn, Hong Kong 999077, Peoples R China
[3] King Khalid Univ, Coll Engn, Dept Elect Engn, Abha, Saudi Arabia
[4] Tanta Univ, Fac Engn, Dept Elect Power & Machines Engn, Tanta 31527, Egypt
[5] Harbin Inst Technol Shenzhen, Sch Mech Engn & Automat, Shenzhen, Peoples R China
关键词
Distribution networks; Reliability; Distributed automation system; Cost; benefit study; DG units; Soft Open Points; ENERGY-RESOURCES;
D O I
10.1016/j.egyr.2023.05.224
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The electric utility industry is moving towards a deregulated and competitive market to meet customer expectations. So, system performance and reliability assessments are getting targeted more than before. Several performance measures of reliability are developed in the literature. In this research, the NEPLAN Simulator reliability analysis module is used to determine all the reliability indices in different cases of study considering the effect of the Advanced Distributed Automation System (ADAS). The analysis also benefits from the presence of Penetration of Distributed Generation (DG) units and Soft Open Points (SOP) to enhance system reliability alongside power quality. Therefore, this paper provides a methodology based on a cost/benefit study for distribution networks to define the best location of DG units and SOP devices that leads to better reliability indices. The objectives of the study are demonstrated and investigated through Bus 4 of the standard reliability Roy Bollington Test System (RBTS). NEPLAN uses a tool to apply the Reliability Centered Maintenance (RCM) strategy, which leads to a substantial reduction of maintenance expenses. Simulation results indicate a significant reduction in system reliability cost by 65.8% with significant enhancement in the average of all reliability indices and at each load point too such as Customer Average Interruption Duration Index (CAIDI) which is improved from 40.899 to 29.883, Energy not supplied also is declined by 52.34%. It is also worth saying that, even using DG units or SOP devices separately leads to positive results but the best outcomes are obtained with an appropriate combination of both. & COPY; 2023 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
引用
收藏
页码:6199 / 6210
页数:12
相关论文
共 34 条
[1]  
Abdullah A.M., 2012, IEEE PES INNOVATIVE, P1, DOI [10.1109/ISGT-Asia.2012.6303331, DOI 10.1109/ISGT-ASIA.2012.6303331]
[2]   Optimized Sectionalizing Switch Placement Strategy in Distribution Systems [J].
Abiri-Jahromi, Amir ;
Fotuhi-Firuzabad, Mahmud ;
Parvania, Masood ;
Mosleh, Mohsen .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (01) :362-370
[3]  
Ahmad S, 2017, INT J ADV COMPUT SC, V8, P375
[4]   A distributed automation architecture for distribution networks, from design to implementation [J].
Angioni, Andrea ;
Lu, Shengye ;
Hooshyar, Hossein ;
Cairo, Ignasi ;
Repo, Sami ;
Ponci, Ferdinanda ;
Della Giustina, Davide ;
Kulmala, Anna ;
Dede, Alessio ;
Monti, Antonello ;
Del Rosario, Gerard ;
Vanfretti, Luigi ;
Corchero Garcia, Cristina .
SUSTAINABLE ENERGY GRIDS & NETWORKS, 2018, 15 :3-13
[5]  
[Anonymous], 2012, IEEE P1366/D7, January 2012, P1
[6]  
Deng Feng, 2012, 2012 CHIN INT C EL D, P1
[7]  
Ding M, 2010, IEEE PEDG 2010: THE 2ND INTERNATIONAL SYMPOSIUM ON POWER ELECTRONICS FOR DISTRIBUTED GENERATION SYSTEMS, P958, DOI 10.1109/PEDG.2010.5545855
[8]  
Du JW, 2014, ASIA-PAC POWER ENERG
[9]   Improving performance of underground MV distribution networks using distribution automation system: A case study [J].
Elkadeem, M. R. ;
Alaam, M. A. ;
Azmy, Ahmed M. .
AIN SHAMS ENGINEERING JOURNAL, 2018, 9 (04) :469-481
[10]   A survey of reliability assessment techniques for modern distribution networks [J].
Escalera, Alberto ;
Hayes, Barry ;
Prodanovic, Milan .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2018, 91 :344-357