Audible Noise Performance of High Voltage AC Conductor Bundles at an Altitude of 2261m

被引:13
|
作者
He, Wangling [1 ]
Wan, Baoquan [2 ]
Huang, Shilong [1 ]
Liu, Yunpeng [1 ]
Zhang, Jiangong [2 ]
Han, Xiao
机构
[1] North China Elect Power Univ, Baoding 071000, Peoples R China
[2] China Elect Power Res Inst, State Key Lab Power Grid Environm Protect, Wuhan 430074, Peoples R China
来源
CSEE JOURNAL OF POWER AND ENERGY SYSTEMS | 2023年 / 9卷 / 06期
基金
中国国家自然科学基金;
关键词
Conductors; Corona; Electric fields; Discharges (electric); Transmission line measurements; Rain; Temperature measurement; AC power lines; audible noise; corona discharge; high altitude; CORONA INCEPTION; LINE; IMPACT;
D O I
10.17775/CSEEJPES.2020.02970
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Extra or ultra-high voltage transmission lines can exhibit strong corona discharge and generate severe audible noise (AN) at high altitudes, which has become a critical limiting factor for power lines construction. However, the AN data of bundle conductors at high altitudes are very rare, which cannot adequately support the power utilities to make reasonable conductor selections. In this paper, a sound pressure level (SPL) of 14 types of bundle conductors is investigated by using an ultra-high-voltage (UHV) corona cage (8 m x 8 m x 35 m) at an altitude of 2216 m, where the bundle numbers between 4 and 12 and the conductor types are used in 500 kV, 750 kV or 1000 kV power transmission projects. Then a large number of valuable AN data are obtained; the influences of bundle numbers and sub-conductor diameters on an acoustic power density level (L-PWL) are analyzed; and an A-weighted L-PWL calculation method is proposed. In addition, by comparing the AN data obtained from the low-altitude area (altitude: 23 m), the AN altitude correction factor is concluded, and the influences of conductor parameters and the surface electric field strength on correction factors are discussed. The results obtained in this paper can provide important data for the construction of high-altitude AC power lines.
引用
收藏
页码:2447 / 2455
页数:9
相关论文
共 50 条
  • [1] Audible noise spectral characteristics of high-voltage ac bundled conductors at high altitude
    He, Wangling
    Wan, Baoquan
    Liu, Yunpeng
    Liu, Xingfa
    Huang, Shilong
    Zhang, Yinlu
    Zhang, Jiangong
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2021, 15 (08) : 1304 - 1313
  • [2] Environmental effect of high voltage AC transmission lines audible noise
    Al-Faraj, MA
    Shwehdi, MH
    Farag, AS
    IECEC-97 - PROCEEDINGS OF THE THIRTY-SECOND INTERSOCIETY ENERGY CONVERSION ENGINEERING CONFERENCE, VOLS 1-4: VOL.1: AEROSPACE POWER SYSTEMS AND TECHNOL; VOL 2: ELECTROCHEMICAL TECHNOL, CONVERSION TECHNOL, THERMAL MANAGEMENT; VOLS 3: ENERGY SYSTEMS, RENEWABLE ENERGY RESOURCES, ENVIRONMENTAL IMPACT, POLICY IMPACTS ON ENERGY; VOL 4: POST DEADLINE PAPERS, INDEX, 1997, : 2082 - 2087
  • [3] Effect of Altitude on the Audible Noise Level of AC Power lines
    He, Wangling
    Wan, Baoquan
    Lan, Lei
    Pei, Chunming
    Zhang, Jiangong
    Chen, Yuchao
    Chen, Xiaoyue
    Wen, Xishan
    ENERGIES, 2017, 10 (07):
  • [4] Audible Noise Performance of Conductor Bundles Based on Cage Test Results and Comparison with Long Term Data
    Wan, Baoquan
    He, Wangling
    Pei, Chunming
    Wu, Xiaorui
    Chen, Yuchao
    Zhang, Yemao
    Lan, Lei
    ENERGIES, 2017, 10 (07):
  • [5] AUDIBLE NOISE GENERATION OF INDIVIDUAL SUBCONDUCTORS OF TRANSMISSION-LINE CONDUCTOR BUNDLES
    COMBER, MG
    CORTINA, R
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1976, 95 (02): : 525 - 535
  • [6] Research on Audible Noise Performance of Triple IEC 315 Conductor Bundles for 400kV Transmission Line Applications
    Mathebula, Matimba
    Mahatho, Nishal
    Mathebula, Elvis
    2024 32ND SOUTHERN AFRICAN UNIVERSITIES POWER ENGINEERING CONFERENCE, SAUPEC, 2024, : 242 - 245
  • [7] Mechanism and theoretical model for corona audible noise from high voltage AC transmission lines
    Di, Zelong
    Wu, Jiuhui
    Hsi-An Chiao Tung Ta Hsueh/Journal of Xi'an Jiaotong University, 2012, 46 (08): : 128 - 132
  • [8] AUDIBLE NOISE PERFORMANCE OF REGULAR AND ASYMMETRIC BUNDLES AND EFFECT OF CONDUCTOR AGING ON PROJECT UHVS 3-PHASE TEST LINE
    COMBER, MG
    NIGBOR, RJ
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1979, 98 (02): : 561 - 572
  • [9] Radio Interference Performance of HVAC Conductor Bundles at High-Altitude Location: Measured Data Analysis and Altitude Correction
    He, Wangling
    Lan, Lei
    Wan, Baoquan
    Zhang, Jiangong
    Wen, Xishan
    Chen, Xiaoyue
    Wu, Xiaorui
    Li, Wei
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2018, 60 (05) : 1322 - 1329
  • [10] Audible Noise and High-Voltage Power Capacitors
    Bandalo, Felix Srecko
    Singh, Biswajit
    Sevigny, Richard
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (05) : 2437 - 2441