Transient induced voltages on aboveground pipelines parallel to overhead transmission lines

被引:2
作者
Papadopoulos, T. A. [1 ]
Datsios, Z. G. [2 ,3 ]
Chrysochos, A. I. [4 ]
Martins-Britto, A. G. [5 ]
Papagiannis, G. K.
机构
[1] Democritus Univ Thrace, Dept Elect & Comp Engn, Power Syst Lab, Xanthi 67100, Greece
[2] Aristotle Univ Thessaloniki, Sch Elect & Comp Engn, Thessaloniki 54124, Greece
[3] Univ Western Macedonia, Dept Elect & Comp Engn, Kozani 50131, Greece
[4] Hellen Cables, Athens 15125, Greece
[5] Univ Brasilia, Dept Elect Engn, LAPSE, BR-70910900 Brasilia, Brazil
关键词
Earth conduction effects; Frequency-dependent soil models; Overhead lines; Pipelines; Transients; PROPAGATION; COMPUTATION;
D O I
10.1016/j.epsr.2023.109631
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Lightning strikes to conductors of overhead lines may cause high transient induced voltages at neighbouring pipelines. Thus, the computation of these voltages is important for the safe and reliable pipeline operation. This work investigates the effects of line parameters and soil modelling on the transient voltages induced at an aboveground pipeline due to lightning strikes to a phase conductor of a nearby overhead transmission line. Three different earth formulations are evaluated: the Carson, Wise, and the method of moments with surface operator combined with the extended transmission line approaches. Computations are performed using both frequency-and time-domain models, as well as constant and frequency-dependent soil electrical properties. CIGRE lightning current waveforms are employed in simulations derived on the basis of the statistical distributions of their parameters for negative first return-strokes. Transient induced voltage waveforms differ among the evaluated lightning currents, with higher peak values for shorter and steeper current wavefronts. Conservative results are obtained for the constant soil properties and Carson's earth formulations, which neglect, respectively, the dispersion of soil electrical properties and displacement current.
引用
收藏
页数:8
相关论文
共 31 条
[1]  
[Anonymous], 2022, EMTP-RV simulation software.
[2]  
[Anonymous], 1997, 12431997 IEEE, P1, DOI [DOI 10.1109/IEEESTD.1997.84660, 10.1109/IEEESTD.1997.84660]
[3]  
[Anonymous], 2019, Rep. no. CIGRE WG C4.33
[4]  
[Anonymous], 1995, CIGRE WG 36.02, P1
[5]  
Carson J. R., 1926, BELL SYST TECH J, V5, P539, DOI DOI 10.1002/J.1538-7305.1926.TB00122.X
[6]   Enhancing the frequency-domain calculation of transients in multiconductor power transmission lines [J].
Chrysochos, Andreas I. ;
Papadopoulos, Theofilos A. ;
Papagiannis, Grigoris K. .
ELECTRIC POWER SYSTEMS RESEARCH, 2015, 122 :56-64
[7]   Robust Calculation of Frequency-Dependent Transmission-Line Transformation Matrices Using the Levenberg-Marquardt Method [J].
Chrysochos, Andreas I. ;
Papadopoulos, Theofilos A. ;
Papagiannis, Grigoris K. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (04) :1621-1629
[8]  
Datsios Z.G., 2022, P 36 INT C LIGHTN PR
[9]   Closed-Form Expressions for the Estimation of the Minimum Backflashover Current of Overhead Transmission Lines [J].
Datsios, Zacharias G. ;
Mikropoulos, Pantelis N. ;
Tsovilis, Thomas E. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (02) :522-532
[10]   Effects of Lightning Channel Equivalent Impedance on Lightning Performance of Overhead Transmission Lines [J].
Datsios, Zacharias G. ;
Mikropoulos, Pantelis N. ;
Tsovilis, Thomas E. .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2019, 61 (03) :623-630