Adaptive Fault Locator for High-Voltage Transmission Lines Based on the Estimation of Power System Model Parameters

被引:0
作者
Zalitis, I. [1 ]
Dolgicers, A. [1 ]
Kozadajevs, J. [1 ]
Berkolds, J. [1 ]
机构
[1] Riga Tech Univ, Inst Power Engn, 12-K1 Azenes Str, LV-1010 Riga, Latvia
关键词
Fault location; modelling; optimisation; transmission lines; ALGORITHM;
D O I
10.2478/lpts-2023-0021
中图分类号
O59 [应用物理学];
学科分类号
摘要
This paper presents an adaptive transmission line fault location method, which incorporates fault location devices at both line ends and utilises data import from a supervisory control and data acquisition system without strictly requiring data synchronisation. The developed method aims at achieving a higher degree of robustness, adaptiveness and accuracy. The adaptiveness is achieved by dynamic updating of mathematical models used on the basis of network-wide information, such as data on the state of circuit-breakers and apparent power at load and generation nodes. The robustness and accuracy are enhanced by incorporating two stages of identification of model parameters with the goal of reducing the decision variable space for the stage identifying fault parameters. Furthermore, in addition to utilisation of all measurements available at a particular substation, the developed method partially employs the measurements from the other end of the line by means of result cross-checks, but does not require a full data set, unlike deterministic-model-based methods. An optimisation-based approach, redundancy on the basis of extended measurement set, and cross-checks reduce the risk of fault location errors due to measurement errors or "voids" in the data available. Testing of the developed method demonstrates its accuracy and robustness in a wide range of pre-fault and fault regime scenarios, even when considering various pre-fault contingencies.
引用
收藏
页码:3 / 20
页数:18
相关论文
共 25 条
  • [1] Abedini M, 2013, IRAN CONF ELECTR ENG
  • [2] Ahmed AS, 2017, PROC INT MID EAST P, P631, DOI 10.1109/MEPCON.2017.8301247
  • [3] Altayeva Aigerim, 2017, 2017 17th International Conference on Control, Automation and Systems (ICCAS). Proceedings, P1, DOI 10.23919/ICCAS.2017.8204281
  • [4] Ayyagari S.B., 2011, Artificial neural network based fault location for transmission lines
  • [5] Birjadar A., 2017, 2016 IEEE 1 INT C PO, P1, DOI [10.1109/ICPEICES.2016.7853231, DOI 10.1109/ICPEICES.2016.7853231]
  • [6] Blackburn J.L., 2006, Protective Relaying: Principles and Applications
  • [7] Enhancing fault location performance on power transmission lines
    Bockarjova, Marija
    Dolgicers, Aleksandrs
    Sauhats, Antans
    [J]. 2007 IEEE LAUSANNE POWERTECH, VOLS 1-5, 2007, : 1123 - +
  • [8] Application of combined adaptive fourier filtering technique and fault detector to fast distance protection
    Chen, CS
    Liu, CW
    Jiang, JA
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (02) : 619 - 626
  • [9] Cruz H.O., 2018, 2017 IEEE POW EN SOC, P1, DOI [10.1109/PESGM.2017.8273897, DOI 10.1109/PESGM.2017.8273897]
  • [10] Davoudi Masoud Ghiafeh, 2012, 2012 11th International Conference on Environment and Electrical Engineering, P1087, DOI 10.1109/EEEIC.2012.6221542