Global sensitivity analysis and optimal design of heat recovery ventilation for zero emission buildings

被引:14
|
作者
Liu, Peng [1 ]
Alonso, Maria Justo [1 ]
Mathisen, Hans Martin [2 ]
机构
[1] SINTEF Community, Dept Architecture Mat & Struct, Trondheim, Norway
[2] Norwegian Univ Sci & Technol, Dept Energy & Proc Engn, Trondheim, Norway
关键词
Energy -efficient ventilation; Rotary heat exchanger; Global sensitivity analysis; Optimal design; ENERGY; AIR;
D O I
10.1016/j.apenergy.2022.120237
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Energy-efficient building services are necessary to realise zero-emission buildings while maintaining adequate indoor environmental quality. As the share of ventilation heating needs grow in well-insulated and airtight buildings, heat recovery in mechanical ventilation systems is increasingly common. Ventilation heat recovery is one of the most efficient and viable means to reduce ventilation heat losses and save energy. Highly efficient heat exchangers are being developed or applied to maximise the energy-saving potential of heat recovery ventilation. Nevertheless, the effects of practical operating conditions and the constraints of heat recovery - such as variations in ventilation rates, frost protection, and the prevention of an overheated air supply over a long-term period, which may significantly influence realistic recovery rates - have been less considered in efforts to maximise the energy savings. It is unclear which design parameters for heat recovery devices have the greatest effect on the annual energy savings from ventilation. This study proposes annual efficiency and annual net energy saving models for heat recovery ventilation that consider ventilation rate variations, the longitudinal heat conduction effect and operating controls. We use a global sensitivity analysis to quantify the contributions of various design input parameters to the variation in annual recovery efficiency and annual net energy savings. We identify the most influential parameters and their significant interaction effects for the annual energy performance of heat recovery ventilation. More attention should be paid to these most influential parameters during the design process. Furthermore, the optimal designs for rotary heat exchangers (as identified by a pattern-search optimisation algorithm) can improve annual net energy savings in demand-controlled ventilation by 33-48%, depending on the building areas. In combination with the reference year analysis presented in this study, heat recovery and demand-controlled ventilation can help to meet the need for highly efficient ventilation systems and zero-emission buildings.
引用
收藏
页数:13
相关论文
共 50 条
  • [31] Heat recovery ventilation design limitations due to LHC for different ventilation strategies in ZEB
    Liu, Peng
    Alonso, Maria Justo
    Mathisen, Hans Martin
    BUILDING AND ENVIRONMENT, 2022, 224
  • [32] Sensitivity analysis techniques for the optimal system design of forward osmosis in organic acid recovery
    Ruprakobkit, Tam
    Ruprakobkit, Lert
    Ratanatamskul, Chavalit
    COMPUTERS & CHEMICAL ENGINEERING, 2019, 123 : 34 - 48
  • [33] Night Ventilation Research of Office Buildings: Part 1. Sensitivity Analysis of Ventilation Parameters
    Zhu, Xinrong
    Liu, Wei
    Yang, Liu
    Liu, Jiaping
    ADVANCED BUILDING MATERIALS, PTS 1-4, 2011, 250-253 (1-4): : 3002 - 3007
  • [34] Towards zero energy infrastructure buildings: optimal design of envelope and cooling system
    Barone, Giovanni
    Buonomano, Annamaria
    Giuzio, Giovanni Francesco
    Palombo, Adolfo
    ENERGY, 2023, 279
  • [35] Optimal design of renewable energy solution sets for net zero energy buildings
    Harkouss, Fatima
    Fardoun, Farouk
    Biwole, Pascal Henry
    ENERGY, 2019, 179 : 1155 - 1175
  • [36] Net zero proximity index and techno-economic analysis of BIPV for zero energy and zero emission buildings
    Nam, Kyungmin
    Ahn, Hyeon Woo
    Lee, Sung Gue
    Kim, Juhee
    Jeong, Su-Gwang
    JOURNAL OF BUILDING ENGINEERING, 2025, 103
  • [37] DESIGN OF NEAR-ZERO SENSITIVITY OPTIMAL CONTROL-SYSTEMS
    ELMETWALLY, MM
    RAO, ND
    INTERNATIONAL JOURNAL OF CONTROL, 1973, 18 (02) : 353 - 357
  • [38] Adequacy of air-to-air heat recovery ventilation system applied in low energy buildings
    El Fouih, Younness
    Stabat, Pascal
    Riviere, Philippe
    Phuong Hoang
    Archambault, Valerie
    ENERGY AND BUILDINGS, 2012, 54 : 29 - 39
  • [39] 19th-century thermosiphon ventilation and its potential for heat recovery in buildings today
    Halepaska, Anna
    Adams, Annmarie
    Craig, Salmaan
    ISCIENCE, 2024, 27 (01)
  • [40] Hybrid Ventilation with Innovative Heat Recovery-A System Analysis
    Davidsson, Henrik
    Bernardo, Ricardo
    Hellstrom, Bengt
    BUILDINGS, 2013, 3 (01): : 245 - 257