A new differential current circle diagram based technique for long transmission line protection

被引:0
|
作者
Gangolu, Suryanarayana [1 ]
Sarangi, Saumendra [2 ]
机构
[1] NIT Uttarakhand, Elect Engn, Pauri, India
[2] MNNIT Allahabad, Elect Engn, Allahabad, Uttar Pradesh, India
关键词
CT saturation; current differential protection; fault discrimination; line charging capacitive current; transmission lines; FAULT LOCATION; RELAY; ALGORITHM;
D O I
10.1515/ijeeps-2021-0300
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In view of sensitivity, selectivity, and operating speed of the relay, the current differential technique is an alternative against overcurrent and distance-based techniques for long transmission line protection. Moreover, this technique has limited performance due to Line Charging Capacitive Current (LCCC), Current Transformer (CT) saturation further, by using synchronized data, the effect of LCCC can be nullified. However, in case of synchronition is lost, the performance of the current differential is not reliable. Hence, in this paper, the Inverse of Difference of both end Current phasors (IDC) is applied to prevent maloperation due to channel delay and synchronization loss. The simulation experiments are conducted under various operating conditions on a 345 kV, 50 Hz, IEEE 39-bus network using PSCAD 4.5 and MATLAB (R2020a). Results reveal the enhanced security under CT saturation, LCCC and sensitivity under high resistance line to ground faults.
引用
收藏
页码:115 / 127
页数:13
相关论文
共 50 条
  • [21] Wavelet Based Transmission Line Differential Protection Scheme
    Pahade, Nilesh
    Patil, P. S.
    Badar, Altaf
    2017 INTERNATIONAL CONFERENCE ON POWER AND EMBEDDED DRIVE CONTROL (ICPEDC), 2017, : 522 - 526
  • [22] New differential protection of transmission line with strong immunity from noise in current transient component
    Yuan, Rongxiang
    Chen, Deshu
    Zhang, Zhe
    2000, Autom Electr Power Syst Press, Nanjing, China (24):
  • [23] Long transmission line current differential protection by using instantaneous value after equal transfer processes
    Electric Power Security and High Efficiency Lab., Huazhong Univ. of Sci. and Technol., Wuhan 430074, China
    Zhongguo Dianji Gongcheng Xuebao, 2007, 28 (59-65):
  • [24] Self-Synchronized Current Differential Protection Scheme for Transmission Line
    Huang J.
    Gao H.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2019, 34 (09): : 1944 - 1951
  • [25] Modal current differential protection method based on distributed parameter model of an HVDC transmission line
    Shao, Qingzhu
    Zhao, Xiaodong
    Zhao, Chuangye
    Ping, Xia
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2021, 49 (22): : 171 - 179
  • [26] NEW APPLICATION OF LONG LINES CIRCLE DIAGRAM (WOLPERT DIAGRAM)
    CHERNYY, FB
    TELECOMMUNICATIONS AND RADIO ENGINEER-USSR, 1972, (01): : 32 - &
  • [27] Improved Differential Protection Scheme for Long Distance UHVDC Transmission Line
    Zheng, Xiaodong
    Tai, Nengling
    Thorp, James S.
    Yang, Xia
    2014 IEEE PES GENERAL MEETING - CONFERENCE & EXPOSITION, 2014,
  • [28] A new current differential protection principle for HVDC transmission lines
    Gao, Shuping
    Suonan, Jiale
    Song, Guobing
    Zhang, Jiankang
    Hou, Zhuo
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2010, 34 (17): : 45 - 49
  • [29] A new current differential protection scheme for teed transmission lines
    Gao, Houlei
    Crossley, Peter A.
    2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, : 2684 - +
  • [30] Influence of capacitive current on distance protection of UHV long transmission line
    School of Electrical and Automation Engineering, Tianjin University, Tianjin 300072, China
    Tianjin Daxue Xuebao (Ziran Kexue yu Gongcheng Jishu Ban), 2006, SUPPL. (83-87):