A new differential current circle diagram based technique for long transmission line protection

被引:0
|
作者
Gangolu, Suryanarayana [1 ]
Sarangi, Saumendra [2 ]
机构
[1] NIT Uttarakhand, Elect Engn, Pauri, India
[2] MNNIT Allahabad, Elect Engn, Allahabad, Uttar Pradesh, India
关键词
CT saturation; current differential protection; fault discrimination; line charging capacitive current; transmission lines; FAULT LOCATION; RELAY; ALGORITHM;
D O I
10.1515/ijeeps-2021-0300
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In view of sensitivity, selectivity, and operating speed of the relay, the current differential technique is an alternative against overcurrent and distance-based techniques for long transmission line protection. Moreover, this technique has limited performance due to Line Charging Capacitive Current (LCCC), Current Transformer (CT) saturation further, by using synchronized data, the effect of LCCC can be nullified. However, in case of synchronition is lost, the performance of the current differential is not reliable. Hence, in this paper, the Inverse of Difference of both end Current phasors (IDC) is applied to prevent maloperation due to channel delay and synchronization loss. The simulation experiments are conducted under various operating conditions on a 345 kV, 50 Hz, IEEE 39-bus network using PSCAD 4.5 and MATLAB (R2020a). Results reveal the enhanced security under CT saturation, LCCC and sensitivity under high resistance line to ground faults.
引用
收藏
页码:115 / 127
页数:13
相关论文
共 50 条
  • [1] A New Transmission Line Differential Protection based on Fault current DC Transients
    Latha, Adharapurapu Hema
    Bhimasingu, Ravikumar
    Katta, Sobhan Babu
    2018 IEEE 8TH POWER INDIA INTERNATIONAL CONFERENCE (PIICON), 2018,
  • [2] A Transmission Line Current Differential Protection Based on Virtual Restraint Current
    Wang, Xingguo
    Zhou, Zexin
    Liu, Huanzhang
    2015 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, 2015,
  • [3] Current Differential Protection of Transmission Line Using the Moving Window Averaging Technique
    Dambhare, Sanjay
    Soman, Shreevardhan
    Chandorkar, Mukul
    IEEE POWER AND ENERGY SOCIETY GENERAL MEETING 2010, 2010,
  • [4] Current Differential Protection of Transmission Line Using the Moving Window Averaging Technique
    Dambhare, Sanjay
    Soman, S. A.
    Chandorkar, M. C.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (02) : 610 - 620
  • [5] Novel HVDC Transmission Line Protection Scheme Based On Current Differential
    Muhammad, Mahmoud Gamal
    Hafez, Dina Mourad
    Abd-Elaziz, Abd-Elaziz Mahmoud
    2018 TWENTIETH INTERNATIONAL MIDDLE EAST POWER SYSTEMS CONFERENCE (MEPCON), 2018, : 361 - 366
  • [6] A New Approach to Current Transformer Saturation Compensation for Transmission Line Differential Protection
    Ebrahimian, Valiolah
    Namdari, Farhad
    Shakarami, Mahmoud-Reza
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2024,
  • [7] Novel Sensitive Current Differential Protection of Transmission Line
    Dambhare, Sanjay
    Soman, S. A.
    Chandorkar, M. C.
    2008 JOINT INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON) AND IEEE POWER INDIA CONFERENCE, VOLS 1 AND 2, 2008, : 1017 - 1022
  • [8] Study on a new differential protection for transmission line
    Yuan, Rongxiang
    Chen, Deshu
    Zhang, Zhe
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2000, 20 (04): : 9 - 13
  • [9] Fast Differential Protection for HVDC Transmission Line Based on Current Control Compensation
    Li H.
    Zhu X.
    Liang Y.
    Xu C.
    Deng C.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2021, 45 (11): : 111 - 119
  • [10] Adaptive Current Differential Protection Schemes for Transmission-Line Protection
    Dambhare, Sanjay
    Soman, Shreevardhan
    Chandorkar, Mukul
    IEEE POWER AND ENERGY SOCIETY GENERAL MEETING 2010, 2010,