Assessment of voltage harmonics' impact on the maximum load capacity of the power supply transformer for the LHCD system

被引:0
作者
Chen, Hui [1 ,2 ]
Wang, Junjia [1 ]
Hu, Hejun [1 ,2 ]
Huang, Yiyun [1 ]
机构
[1] Chinese Acad Sci, Hefei Inst Phys Sci, Inst Plasma Phys, Hefei 230031, Peoples R China
[2] Univ Sci & Technol China, Hefei 230026, Peoples R China
关键词
THDV; Transformers; LHCD; Winding losses; Maximum loading capability; DESIGN;
D O I
10.1038/s41598-024-56366-x
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
To study the influence of the voltage total harmonic distortion (THDV) and its spectrum on the harmonic loss factor (FHL) and the maximum allowable load capacity ratio (Imax (pu)) for the transformer of the LHCD system, we use MATLAB software to model the LHCD system and study the winding loss and maximum allowed load capacity of the LHCD system transformer when the supply voltage source is sinusoidal and non-sinusoidal, respectively. The calculation is carried out by the method of IEEE standard C57.110 and the method of considering the skin effect. The calculation results of both methods clearly show that the THDV value of the supply voltage has a significant effect on the harmonic dissipation factor (FHL) and the maximum allowable load capacity ratio (Imax (pu)) of the transformer. And the calculation method considering the skin effect increases the maximum allowable load capacity ratio of the LHCD system transformer by about 2%. The research results have important reference value for the future retrofit design of LHCD system transformers.
引用
收藏
页数:8
相关论文
共 24 条
[1]  
[Anonymous], 2008, Electr. Power Qual. Util. J
[2]  
[Anonymous], 1994, Underwriters Laboratories (UL) Standard 1561
[3]  
[Anonymous], 2018, IEEE Std C57.110&TRADE, P1
[4]  
Balci M. E., 2005, Sixth International Conference on Power Electronics and Drive Systems (IEEE Cat. No.05TH8824C), P1199
[5]  
Balci M. E., 2008, 43 UPEC, P1
[6]  
Dai Wan, 2019, 2019 IEEE 3rd Conference on Energy Internet and Energy System Integration (EI2), P2746, DOI 10.1109/EI247390.2019.9061866
[7]   Measurement of three-phase transformer derating and reactive power demand under nonlinear loading conditions [J].
Fuchs, EF ;
Lin, DS ;
Martynaitis, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (02) :665-672
[8]  
Funato H, 2010, INT POWER ELECT MOT
[9]  
Hao X., 2011, Appl. Mech. Mater, V135, P1027, DOI [10.4028/www.scientific.net/AMM.135-136.1027, DOI 10.4028/WWW.SCIENTIFIC.NET/AMM.135-136.1027]
[10]  
Hao X., 2012, Appl. Mech. Mater, V135-136, P1027