Improving energy and water consumption of a data center via air free-cooling economization: The effect weather on its performance

被引:21
作者
Silva-Llanca, Luis [1 ,2 ]
Ponce, Carolina [2 ]
Bermudez, Elizabeth [2 ]
Martinez, Diego [2 ]
Diaz, Andres J. [3 ]
Aguirre, Fabian [1 ,2 ]
机构
[1] Univ La Serena, Inst Multidisciplinario Invest & Postgrad, Raul Bitran 1305, La Serena, Coquimbo, Chile
[2] Univ La Serena, Dept Ingn Mecan, Benavente 980, La Serena, Coquimbo, Chile
[3] Univ Diego Portales, Escuela Ingn Ind, Fac Ingn & Ciencias, Ctr Energia & Desarrollo Sustentable, Ave Ejercito 441, Santiago, Metropolitana, Chile
关键词
Air-free cooling; Data centers; Thermal management; SIDE ECONOMIZERS; SYSTEM; SIMULATION; EFFICIENCY; OPERATION;
D O I
10.1016/j.enconman.2023.117344
中图分类号
O414.1 [热力学];
学科分类号
摘要
In the past two decades, data centers have significantly grown in size and number around the globe, leading to substantial energy and water stress wherever they operate. Thermal management typically represents half of the total energy consumption in traditional data centers. This work studies the energy and water savings that air -side free-cooling yields under diverse weather conditions. We modeled a free-cooling system and a conventional data center using MATLAB. The hourly weather data was obtained from a publicly available online repository for the Chilean territory. Using air-side free-cooling for data center thermal management is feasible in various weather conditions. Locations with colder temperatures (< 20 degrees C) and higher humidity (> 60%) are more favorable as they require minimal use of the chiller and/or humidifier. These conditions are present in BSk'(s) Cold Semi-arid climate with dry summer and oceanic influence, as well as Csb' Mediterranean climate (warm summer) with oceanic influence. However, locations with drier air (< 50%) and warmer temperatures (> 20 degrees C), such as those found in ET(w) Tundra climate with dry winter, BWk(w) Cold Desert climate with dry winter, or BSk(s) Cold Semi-arid climate with dry summer, are less suitable for air free cooling. Even under suboptimal energy and water savings, the air-side economizer still performed considerably better than a conventional data center cooling method (using CRAH units).
引用
收藏
页数:19
相关论文
共 11 条
  • [1] Effect of climate conditions on the thermodynamic performance of a data center cooling system under water-side economization
    Diaz, Andres J.
    Caceres, Rodrigo
    Torres, Rodrigo
    Cardemil, Jose M.
    Silva-Llanca, Luis
    ENERGY AND BUILDINGS, 2020, 208 (208)
  • [2] Energy performance evaluation in a data center with water-side free cooling
    Mi, Ranran
    Bai, Xuelian
    Xu, Xin
    Ren, Fei
    ENERGY AND BUILDINGS, 2023, 295
  • [3] Evaluation of energy performance and ecological benefit of free-cooling system for data centers in worldwide climates
    Fan, Chengliang
    Zou, Binwei
    Liao, Yundan
    Zhou, Xiaoqing
    SUSTAINABLE CITIES AND SOCIETY, 2024, 108
  • [4] Comparative energy analysis of cooling energy performance between conventional and hybrid air source internet data center cooling system
    Lamptey, Nicholas Boafo
    Anka, Selorm Kwaku
    Cho, Yong
    Lee, Kwang Ho
    Choi, Jong Woong
    Choi, Jong Min
    ENERGY AND BUILDINGS, 2024, 302
  • [5] Thermal Management and Energy Consumption in Air, Liquid, and Free Cooling Systems for Data Centers: A Review
    Xu, Sijun
    Zhang, Hua
    Wang, Zilong
    ENERGIES, 2023, 16 (03)
  • [6] Energy differential-based optimal outdoor air ventilation strategy for high-tech cleanrooms concerning free cooling and its performance evaluation
    Zhao, Wenxuan
    Li, Hangxin
    Wang, Shengwei
    BUILDING AND ENVIRONMENT, 2023, 231
  • [7] Experimental and numerical investigation on thermal performance of data center via fan-wall free cooling technology
    Lan, Jiang
    Zhang, Zujing
    Liang, Xing
    Wu, Hongwei
    Wang, Gang
    Mao, Ruiyong
    APPLIED THERMAL ENGINEERING, 2023, 228
  • [8] Optimization air-conditioning system and thermal management of data center via fan-wall free cooling technology
    Zhang, Jun
    Mao, Ruiyong
    Li, Chao
    Lan, Jiang
    Yi, Xiaoyan
    Zhang, Zujing
    APPLIED THERMAL ENGINEERING, 2023, 234
  • [9] A novel data center free radiating system driven by waste heat and wind energy system (DCFRWWs) and its operation performance analysis
    Zou, Zetai
    Yang, Chao
    Hu, Licui
    Zhang, Qiang
    ENERGY AND BUILDINGS, 2024, 310
  • [10] Effect of air temperature non-uniformity on water-air heat exchanger thermal performance - Toward innovative control approach for energy consumption reduction
    Ramadan, M.
    Khaled, M.
    El Hage, H.
    Harambat, F.
    Peerhossaini, H.
    APPLIED ENERGY, 2016, 173 : 481 - 493