Probabilistic Evaluation Method of Transformer Neutral Direct Current Distribution in Urban Power Grid Caused by DC Metro Stray Current

被引:9
作者
Wang, Aimin [1 ]
Lin, Sheng [2 ]
He, Zhengyou [2 ]
Jingzhuo, Zhang [3 ]
Wu, Guoxing [3 ]
机构
[1] Xihua Univ, Sch Elect Engn & Elect Informat, Chengdu 610039, Peoples R China
[2] Southwest Jiaotong Univ, Sch Elect Engn, Chengdu 610031, Peoples R China
[3] Shenzhen power supplybureau co LTD, China Southern Power Grid, Shenzhen 518000, Peoples R China
基金
中国国家自然科学基金;
关键词
Transformers; Grounding; Power grids; Resistance; Rails; Substations; HVDC transmission; DC metro; probability evaluation method; stray current; transformer neutral direct current; urban power grid; GEOMAGNETICALLY INDUCED CURRENT; OPTIMIZATION; SYSTEMS;
D O I
10.1109/TPWRD.2022.3200953
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
With the coupling of the DC metro network and urban power grid, the DC metro stray currents flowing into transformers have caused serious DC bias. There is, therefore, a need to evaluate transformer neutral direct currents caused by the DC metro stray current. To achieve this, an evaluation model considering the coupling of DC metro network and urban power grid is proposed. In the modeling principle, metro lines are coupled with grounding grids of transfer stations. The DC metro system and the urban power grid are coupled with the soil and grounding systems. The train operations on DC metro lines are simulated using the Monte Carlo method. And, considering the conditions of one-way conduction devices (OWCDs) and over-voltage protection devices (OVPDs), transformer neutral direct currents are calculated. Moreover, two probability indexes are proposed to evaluate distributions of transformer neutral direct currents. The applicability of the proposed model is verified by comparing the calculation results with test data of the transformer neutral direct current. Using the evaluation model, transformer neutral direct currents are evaluated. The result indicates that substation supplying power to the DC metro network has a large probability of a high-level neutral direct current.
引用
收藏
页码:541 / 552
页数:12
相关论文
共 19 条
  • [11] Influence of horizontal multi-layer soil on DC current distribution in AC power grid
    Pan, Zhuohong
    Zhang, Lu
    Lin, Jindi
    Wen, Xishan
    Gaodianya Jishu/High Voltage Engineering, 2012, 38 (04): : 855 - 862
  • [12] A novel method of restoration path optimization for the alternating current-direct current bulk power grid after a major blackout
    Yang, Chao
    Liang, Gaoshen
    Cheng, Tianle
    Li, Yang
    Li, Shaoyan
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2023, 17 (23) : 5240 - 5251
  • [13] Reliability evaluation method for AC/DC hybrid distribution power network considering cascaded multiport power electronic transformer
    Liu, Yi
    Li, Haibo
    Yu, Zhanqing
    Zeng, Rong
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2019, 13 (23) : 5357 - 5364
  • [14] A Novel DC Current Injection Suppression Method for Three-Phase Grid-Connected Inverter Without the Isolation Transformer
    Chen, Min
    Xu, Dehong
    Zhang, Tao
    Shi, Keyan
    He, Guofeng
    Rajashekara, Kaushik
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2018, 65 (11) : 8656 - 8666
  • [15] Evaluation of the impact of urban rail system on the distribution of DC currents in the power grid considering multi-train density
    Tang, Mingwei
    Guo, Yujun
    Xiao, Song
    Zeng, Jiani
    Zhong, Hemin
    Ruan, Ling
    Tang, Zeyang
    Wu, Guangning
    ELECTRIC POWER SYSTEMS RESEARCH, 2024, 236
  • [16] Study of DC-Bias Current Distribution in AC Power System Based on Direct Field-Circuit Coupled Model
    Xu, Wenjie
    Ruan, Jiangjun
    Wu, Yongcong
    Sun, Xiang
    Zou, Guoping
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [17] Study of DC-bias Current Distribution in AC Power System Based on Direct Field-circuit Coupled Model
    Ruan J.
    Xu W.
    Ding Z.
    Wu Y.
    Sun X.
    Zou G.
    Xu, Wenjie (1789965541@qq.com), 1600, Science Press (43): : 1333 - 1340
  • [18] Harmonic Analysis of the Power Distribution Neutral-to-Earth Voltage (NEV) Test Case using Four-Wire Three-Phase Harmonic Current Injection Method
    Variz, A. M.
    Pereira, J. L. R.
    Carneiro, S., Jr.
    Barbosa, P. G.
    2009 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, VOLS 1-8, 2009, : 14 - +
  • [19] Integration of power decoupling buffer and grid-tied photovoltaic inverter with single-inductor dual-buck topology and single-loop direct input current ripple control method
    Liu, Bin
    Zhang, Zhigang
    Li, Guojin
    He, Deqiang
    Chen, Yanming
    Zhang, Zhenrong
    Li, Gang
    Song, Shaojian
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 125