Analysis of Voltage Dip Impact on Doubly Fed Induction Generator under Dynamic Conditions

被引:1
作者
Zergaw, Kidist Berhane [1 ]
Tuka, Milkias Berhanu [1 ]
机构
[1] Adama Sci & Technol Univ, Elect Power & Control Engn Dept, Adama, Ethiopia
来源
JORDAN JOURNAL OF ELECTRICAL ENGINEERING | 2023年 / 9卷 / 03期
关键词
Voltage dip; Adaptive neuro-fuzzy inference system; Crowbar; Doubly fed induction generator; Low voltage ride through; CAPABILITY ENHANCEMENT; WIND; DEVICES; RIDE;
D O I
10.5455/jjee.204-1669034454
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Doubly Fed Induction Generator (DFIG) is the most widely employed generator in the Wind Energy Conversion Systems (WECS) for the production of electricity. However, despite all of its various advantages, it is extremely vulnerable to grid faults such as voltage dip since its stator is directly coupled to the grid. A voltage dip problem is one the main issues among the power quality concerns. This fault causes the flow of excessive current across both the stator and the rotor terminals, which may lead to serious damage to the generator, power converters, and DC Link capacitor. On the other hand, the current Grid Codes (GC) requires the system to stay connected to the grid during this fault condition and support it in healing its nominal voltage. This capacity of the system is known as the Low Voltage Ride Through (LVRT) capacity. For the system to achieve such capacity, appropriate protection mechanisms or controlling strategies must be utilized. Therefore, in this paper, the crowbar protection technique, PI controller, and the Adaptive Neuro-Fuzzy Inference System (ANFIS) controller are employed. Furthermore, the performance of the system employing PI, crowbar, and ANFIS is analyzed and compared under grid fault conditions, i.e., a voltage dip with a magnitude of 0.1 pu (worst case) using MATLAB/Simulink software and based on actual data obtained from Adama II wind farm. The obtained results unveil that the settling time of ANFIS for controlling the rotor currents in d and q axes (idr and iqr) and DC link voltage is 3.6 s, 3.57 s, and 3.4 s, respectively. On the other hand, the settling times of the PI controller for controlling the rotor currents in d and q axes and the DC link voltage are found to be 4 s, 3.91 s, and 45.2 s, respectively, while the crowbar protection technique's settling times are found to be 4 s, 6 s, and 4.9 s, respectively. It is evident from the aforesaid results that the ANFIS controller provides the best performance of the three strategies since it allows both the rotor currents and the DC link voltage to return to their steady state values faster than the other two techniques, employed in this investigation.
引用
收藏
页码:338 / 356
页数:19
相关论文
共 50 条
[31]   Reactive Power Control of Doubly Fed Induction Generator during Grid Voltage Dips [J].
Zhang, Lu ;
Jin, Xinmin ;
Zhan, Liangyu .
2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
[32]   Transient analysis and crowbar design of doubly-fed induction generator with crowbar protection under grid voltage dips [J].
Xiong, Wei ;
Zou, Xudong ;
Huang, Qingjun ;
Liang, Zongze ;
Chen, Jianqing ;
Kang, Yong .
Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2015, 39 (11) :117-125
[33]   Dynamic Analysis of Current Loops in a Wind Turbine based on Doubly fed Induction Generator [J].
Garkki, B. ;
Revathi, S. .
2022 IEEE INTERNATIONAL CONFERENCE ON POWER ELECTRONICS, DRIVES AND ENERGY SYSTEMS, PEDES, 2022,
[34]   Dynamic Simulation of a Wind Turbine Driven Doubly Fed Induction Generator under Wind Fluctuation [J].
Chen, Hung-Cheng ;
Kuo, Cheng-Chien .
COMPUTATIONAL MATERIALS SCIENCE, PTS 1-3, 2011, 268-270 :61-+
[35]   Phase Angle Compensation Control Strategy for Low Voltage Ride Through of Doubly-Fed Induction Generator [J].
Wang, W. ;
Chen, N. ;
Zhu, L. Z. ;
Xu, D. G. .
2009 INTERNATIONAL CONFERENCE ON SUSTAINABLE POWER GENERATION AND SUPPLY, VOLS 1-4, 2009, :991-+
[36]   Providing Ride-Through Capability to a Doubly Fed Induction Generator Under Unbalanced Voltage Dips [J].
Santos-Martin, David ;
Luis Rodriguez-Amenedo, Jose ;
Arnaltes, Santiago .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2009, 24 (07) :1747-1757
[37]   Short-circuit current of doubly fed induction generator under partial and asymmetrical voltage drop [J].
Ouyang, Jinxin ;
Zheng, Di ;
Xiong, Xiaofu ;
Xiao, Chao ;
Yu, Rui .
RENEWABLE ENERGY, 2016, 88 :1-11
[38]   Analysis of Doubly Fed Induction Generator Interconnected with Grid under Normal and Abnormal Condition [J].
Junghare, Gunwanta ;
Debre, Prashant ;
Kadu, Akshay .
PROCEEDINGS OF THE FIRST IEEE INTERNATIONAL CONFERENCE ON POWER ELECTRONICS, INTELLIGENT CONTROL AND ENERGY SYSTEMS (ICPEICES 2016), 2016,
[39]   Investigation of Voltage Dip Problems during Faults on a Grid-Tied Doubly Fed Induction Generator in a Wind Energy System [J].
Tuka, Milkias Berhanu .
JORDAN JOURNAL OF ELECTRICAL ENGINEERING, 2023, 9 (02) :209-227
[40]   A New Direct Torque Control of Doubly-Fed Induction Generator Under Unbalanced Grid Voltage [J].
Pimple, B. B. ;
Vekhande, V. Y. ;
Fernandes, B. G. .
2011 TWENTY-SIXTH ANNUAL IEEE APPLIED POWER ELECTRONICS CONFERENCE AND EXPOSITION (APEC), 2011, :1576-1581