Low-voltage ride-through handling in wind farm with doubly fed induction generators based on variable-step model predictive control

被引:4
作者
Nie, Yonghui [1 ,5 ]
Zhang, Jie [2 ]
Liu, Tianyu [3 ]
Cui, Jiaxu [3 ]
Zhang, Lidong [4 ]
机构
[1] Northeast Elect Power Univ, Acad Adm Off, Jilin, Peoples R China
[2] Northeast Elect Power Univ, Dept Elect Engn, Jilin, Peoples R China
[3] State Grid Jilin Elect Power Co, Jilin Power Supply Co Ltd, Jilin, Peoples R China
[4] Northeast Elect Power Univ, Dept Energy & Power Engn, Jilin, Peoples R China
[5] Northeast Elect Power Univ, Acad Adm Off, Jilin 132012, Peoples R China
基金
中国国家自然科学基金;
关键词
doubly fed induction generator; low-voltage ride-through; rotor current; variable-step model predictive control; voltage sag protection; POWER; PERTURBATION; CAPABILITY; TURBINES; SYSTEMS;
D O I
10.1049/rpg2.12752
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
A severe voltage sag on the wind-farm grid side with doubly fed induction generators (DFIGs) can induce a peak inrush current in the rotors and damage converters, resulting in wind-turbine disconnection from the grid. To prevent this from happening, a variable-step model predictive control (VS-MPC) strategy is proposed for improving the wind turbines' ability to operate without disconnecting themselves from the grid when a fault occurs. First, the predictive-control state-space model of a doubly fed wind farm is established according to its working principle. Second, model predictive control (MPC) is applied on the rotor side of the DFIG to realize the rapid tracking of the rotor current to the reference value during low-voltage ride-through (LVRT) of the DFIG. Finally, a variable-step size algorithm is introduced into the MPC controller to change the step size continuously during the LVRT period. This increases the control accuracy, realizing rapid attenuation of each transient component, whereby the wind-farm LVRT capability is enhanced. The proposed control strategy was simulated and verified using MATLAB/Simulink. The simulation results indicated that VS-MPC can effectively handle LVRT, allowing the recovery of a wind farm that uses DFIGs and improving the performance of wind-farm.
引用
收藏
页码:2101 / 2112
页数:12
相关论文
共 35 条
[1]   Development and Application of Fuzzy Proportional-Integral Control Scheme in Pitch Angle Compensation Loop for Wind Turbines [J].
AlGhamdi, S. ;
Hamdan, I ;
Youssef, Marwa M. M. ;
Noureldeen, Omar .
MACHINES, 2021, 9 (07)
[2]  
[Anonymous], 2016, PROC 2016 INT S IND
[3]   Self-adapting variable step size strategies for active noise control systems with acoustic feedback [J].
Aslam, Muhammad Saeed ;
Shi, Peng ;
Lim, Cheng-Chew .
AUTOMATICA, 2021, 123
[4]   A Lyapunov-based model predictive control strategy in a permanent magnet synchronous generator wind turbine [J].
Babaghorbani, Behnaz ;
Beheshti, Mohammad Taghi ;
Ali Talebi, Heidar .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 130
[5]   Optimization of damping controller for PSS and SSSC to improve stability of interconnected system with DFIG based wind farm [J].
Bhukya, Jawaharlal ;
Mahajan, Vasundhara .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 108 :314-335
[6]  
Geng H., 2014, LOW VOLTAGE RIDE NEW
[7]  
Hamdan I., SVU-International Journal of Engineering Sciences and Applications, V2, P35, DOI [10.21608/svusrc.2021.80571.1010, DOI 10.21608/SVUSRC.2021.80571.1010]
[8]   Three-Phase Fault Direction Identification for Distribution Systems With DFIG-Based Wind DG [J].
Hooshyar, Ali ;
Azzouz, Maher Abdelkhalek ;
El-Saadany, Ehab F. .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2014, 5 (03) :747-756
[9]   Simultaneous STATCOM and Pitch Angle Control for Improved LVRT Capability of Fixed-Speed Wind Turbines [J].
Hossain, M. Jahangir ;
Pota, Hemanshu R. ;
Ugrinovskii, Valeri A. ;
Ramos, Rodrigo A. .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2010, 1 (03) :142-151
[10]   Bi-level decentralised active power control for large-scale wind farm cluster [J].
Huang, Sheng ;
Wu, Qiuwei ;
Guo, Yifei ;
Lin, Zhongwei .
IET RENEWABLE POWER GENERATION, 2018, 12 (13) :1486-1492