Experimental Investigation of the Frequency Response of an LC-Filter and Power Transformer for Grid Connection

被引:1
作者
Fjellstedt, Christoffer [1 ]
Forslund, Johan [1 ]
Thomas, Karin [1 ]
机构
[1] Uppsala Univ, Dept Elect Engn, Div Elect, S-75237 Uppsala, Sweden
关键词
LC-filter; LCL-filter; power transformer; grid connection; renewable energy; ACTIVE DAMPING TECHNIQUE; DESIGN;
D O I
10.3390/en16155784
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The power delivered by a voltage source inverter needs to be filtered to fulfill grid code requirements. A commonly used filter technology is the LCL-filter. An issue with the LCL-filter is the occurrence of a resonance peak, which can be mitigated with active or passive damping methods. The transfer function of the filter is often used to investigate the frequency response of the system and propose damping methods. The use of an LC-filter combined with a power transformer to form an LCL-filter has not been extensively investigated. Therefore, the study in this article introduces a model for an LC-filter and power transformer for the grid connection and a derived transfer function for the model. The transfer function for the system is validated with simulations and experimental investigations. The results from simulations and the results from a direct solution of the derived analytical function overlap almost perfectly. The magnitudes of the experimental results are approximately 1 dB lower than the simulation and analytical results before the resonance frequency. At the resonance frequency, the experimental results are approximately 13.4 dB lower. The resonance frequency, however, occurs at approximately the same frequency. It is also concluded that the system is significantly damped.
引用
收藏
页数:12
相关论文
共 29 条
  • [1] [Anonymous], 2021, Renewables 2021: Analysis and forecast to 2026, DOI DOI 10.1787/6DCD2-15-EN.2021
  • [2] A Back-to-Back 2L-3L Grid Integration of a Marine Current Energy Converter
    Apelfrojd, Senad
    Ekstrom, Rickard
    Thomas, Karin
    Leijon, Mats
    [J]. ENERGIES, 2015, 8 (02) : 808 - 820
  • [3] Beres R, 2014, APPL POWER ELECT CO, P2208, DOI 10.1109/APEC.2014.6803611
  • [4] Wind Energy Systems
    Blaabjerg, Frede
    Ma, Ke
    [J]. PROCEEDINGS OF THE IEEE, 2017, 105 (11) : 2116 - 2131
  • [5] Topologies, generalized designs, passive and active damping methods of switching ripple filters for voltage source inverter: A comprehensive review
    Buyuk, Mehmet
    Tan, Adnan
    Tumay, Mehmet
    Bayindir, K. Cagatay
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2016, 62 : 46 - 69
  • [6] Limitations of Voltage-Oriented PI Current Control of Grid-Connected PWM Rectifiers With LCL Filters
    Dannehl, Joerg
    Wessels, Christian
    Fuchs, Friedrich Wilhelm
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2009, 56 (02) : 380 - 388
  • [7] A sensorless Kalman filter-based active damping technique for grid-tied VSI with LCL filter
    Eldeeb, Hisham
    Massoud, Ahmed
    Abdel-Khalik, Ayman S.
    Ahmed, Shehab
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2017, 93 : 146 - 155
  • [8] Forslund J., 2018, P 4 AS WAV TID EN C
  • [9] Damping techniques for grid-connected voltage source converters based on LCL filter: An overview
    Gomes, Camilo C.
    Cupertino, Allan F.
    Pereira, Heverton A.
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2018, 81 : 116 - 135
  • [10] Optimal LCL-filter design method for grid-connected renewable energy sources
    Gurrola-Corral, Carlos
    Segundo, Juan
    Esparza, Miguel
    Cruz, Roel
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 120 (120)