Accurate Voltage Phasor Measurement for Electric Power Transmission Line Protection Using Current Sensor

被引:1
|
作者
Mohanty, Rabindra [1 ]
Pradhan, Ashok Kumar [2 ]
Dutta, Pranab Kumar [2 ]
机构
[1] Indian Inst Technol Delhi, Dept Energy Sci & Engn, New Delhi 110016, India
[2] Indian Inst Technol Kharagpur, Dept Elect Engn, Kharagpur 721302, India
关键词
Sensor signal processing; capacitor voltage transformer (CVT); directional and distance protections; phasor estimation; transient response;
D O I
10.1109/LSENS.2023.3349322
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Accurate voltage phasor measurement is important for differ-ent applications in electric power systems including protection, control, and monitoring. At power transmission level, the transient response of the capacitor voltage transformer is a concern for the phasor based protection applications. This letter presents an accurate voltage phasor measurement technique at an electric bus during transient using the current through the capacitor voltage transformer. The numerical integration of current is multiplied with current transformer ratio and with the reciprocal of equivalent capacitance of the capacitor voltage transformer to obtain the accurate voltage during transient. The dependency of the obtained voltage accuracy on the current measurement error is also analyzed. The performance of the proposed technique for phasor estimation used in directional and distance protections during capacitor voltage transformer transient is demonstrated and found to be accurate. The performance of the proposed method is free from the capacitor voltage transformer topologies and operating conditions of electric power systems.
引用
收藏
页码:1 / 4
页数:4
相关论文
共 50 条
  • [1] Accurate phasor measurement for transmission line protection in the presence of shunt capacitor banks
    Nam, Soon-Ryul
    Kang, Sang-Hee
    Park, Jong-Keun
    ELECTRIC POWER SYSTEMS RESEARCH, 2007, 77 (12) : 1646 - 1653
  • [2] Three-terminal transmission line protection using synchronized voltage and current phasor measurements
    Chen, C.-S., 1600, IEEE Power Engineering Society, IEEE Japan (Institute of Electrical and Electronics Engineers Inc.):
  • [3] Three-terminal transmission line protection using synchronized voltage and current phasor measurements
    Chen, CS
    Liu, CW
    Jiang, JA
    IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXHIBITION 2002: ASIA PACIFIC, VOLS 1-3, CONFERENCE PROCEEDINGS: NEW WAVE OF T&D TECHNOLOGY FROM ASIA PACIFIC, 2002, : 1727 - 1732
  • [4] Analysis of Transmission Line Current Differential Protection Scheme Based on Synchronized Phasor Measurement
    Muddebihalkar, Sunita V.
    Jadhav, Ganesh N.
    2015 CONFERENCE ON POWER, CONTROL, COMMUNICATION AND COMPUTATIONAL TECHNOLOGIES FOR SUSTAINABLE GROWTH (PCCCTSG), 2015, : 21 - 25
  • [5] Phasor measurement unit based transmission line protection scheme design
    Zadeh, Hassan Khorashadi
    Li, Zuyi
    ELECTRIC POWER SYSTEMS RESEARCH, 2011, 81 (02) : 421 - 429
  • [6] Transmission Line Fault Detection and Identification in an Interconnected Power Network using Phasor Measurement Units
    Khan, Abdul Qayyum
    Ullah, Qudrat
    Sarwar, Muhammad
    Gul, Sufi Tabassum
    Iqbal, Naeem
    IFAC PAPERSONLINE, 2018, 51 (24): : 1356 - 1363
  • [7] Online Monitoring of the Electrical Power Transfer Stability and Voltage Profile Stability Margins in Electric Power Transmission Systems Using Phasor Measurement Units Data Sets
    Nguegan, Yves
    Claudi, Albert
    Strunge, Carsten
    2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 1668 - +
  • [8] Analysis of Fault Location Algorithm for Transmission Line Protection Based on Synchronized Phasor Measurement
    Muddebihalkar, Sunita V.
    Jadhav, Ganesh N.
    2015 INTERNATIONAL CONFERENCE ON ENERGY SYSTEMS AND APPLICATIONS, 2015, : 118 - 123
  • [9] Synchronized phasor measurement in protective relays for protection, control, and analysis of electric power systems
    Benmouyal, G
    Schweitzer, EO
    Guzmán, A
    2004 57TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS, 2004, : 419 - 450
  • [10] Synchronized phasor measurement in protective relays for protection, control, and analysis of electric power systems
    Benmouyal, G
    Schweitzer, EO
    Guzmán, A
    NETA: Annual Technical Conference 2003: POWER SYSTEMS MAINTENANCE, 2003, : 135 - +