Study on smoke blocking and thermal radiation attenuation by water curtain in tunnel fire

被引:4
作者
Chen, Yinuo [1 ,2 ]
Jia, Jinzhang [1 ,2 ]
Che, Guangbo [1 ,2 ,3 ]
Zhu, Zhiheng [1 ,2 ]
Shen, Zhiyuan [1 ,2 ]
Wu, Yumo [1 ,2 ]
机构
[1] Liaoning Tech Univ, Sch Safety Sci & Engn, Fuxin 123000, Liaoning, Peoples R China
[2] Minist Educ, Key Lab MineThermal Disaster & Prevent, Huludao 125000, Liaoning, Peoples R China
[3] Jilin Normal Univ, Minist Educ, Key Lab Preparat & Applicat Environm Friendly Mat, Changchun 130103, Peoples R China
基金
中国国家自然科学基金;
关键词
MIST; VELOCITY; SPRAY; TESTS;
D O I
10.1038/s41598-023-27437-2
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
A 1:10 scale model tunnel with a length, height and width of 9 m, 0.6 m and 0.8 m, respectively, was set up in this paper. A water curtain system was installed in the model to investigate the effect of water curtain systems on smoke flow and heat propagation. A reduced-scale experimental and theoretical study was carried out by varying the heat release rate of the fire source, the water curtain pressure, and the number of water curtain rows. A series of tests were carried out for various setups to quantify each mechanism of interaction between the water mist and hot smoke, to propose a method for qualitatively analysing water curtain systems blocking the propagation of heat radiation and the flow of smoke from combustion, and to propose a method for predicting heat fluxes. The study found that the pressure of the water curtain, the number of rows, and the heat release rate of the fire source all had an effect on the smoke blocking effect of the water curtain system. This effect decreased as the heat release rate of the fire source increased and increased significantly with the pressure of the water curtain and the number of rows. The smoke blocking effect was quantified using conservation of momentum by establishing a dimensionless parameter R to represent the ratio of water curtain momentum to smoke momentum, as well as the ratio of heat flux before and after the water curtain to represent the smoke blocking capacity delta of the water curtain. The smoke blockage rate delta ranges between 40 and 75%, and the smoke blockage rate increases as the momentum R increases. Finally, in tunnel fires, a predictive model for the attenuation of heat radiation by water curtains has been developed, providing theoretical support for the quantitative study of the smoke and thermal blockage effects of water curtains, which is beneficial to the protection of human life in confined spaces.
引用
收藏
页数:15
相关论文
共 38 条
[21]   Numerical analysis of a water mist spray: The importance of various numerical and physical parameters, including the drag force [J].
Liu, Yuanjun ;
Beji, Tarek ;
Thielens, Martin ;
Tang, Zhi ;
Fang, Zheng ;
Merci, Bart .
FIRE SAFETY JOURNAL, 2022, 127
[22]   Use of a water mist for smoke confinement and radiation shielding in case of fire during tunnel construction [J].
Mehaddi, R. ;
Collin, A. ;
Boulet, P. ;
Acem, Z. ;
Telassamou, J. ;
Becker, S. ;
Demeurie, F. ;
Morel, J-Y .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2020, 148
[23]   Predicting sprinkler spray dispersion in FireFOAM [J].
Myers, Taylor ;
Trouve, Arnaud ;
Marshall, Andre .
FIRE SAFETY JOURNAL, 2018, 100 :93-102
[24]   Experimental and numerical study on the interaction of a water mist spray with a turbulent buoyant flame [J].
Noda, Shogo ;
Merci, Bart ;
Tanaka, Futoshi ;
Beji, Tarek .
FIRE SAFETY JOURNAL, 2021, 120
[25]  
Purser D.A., 2016, SFPE Handbook of Fire Protection Engineering, Vfifth, P2308, DOI DOI 10.1007/978-1-4939-2565-0
[26]  
Sheppard D.T., 2002, SPRAY CHARACTERISTIC
[27]   Interpretation of flow fields induced by water spray systems in reduced-scale tunnel fire experiments by means of CFD simulations [J].
Sun, Jiayun ;
Fang, Zheng ;
Beji, Tarek ;
Merci, Bart .
TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2018, 81 :94-102
[28]   Experimental study of the effectiveness of a water system in blocking fire-induced smoke and heat in reduced-scale tunnel tests [J].
Sun, Jiayun ;
Fang, Zheng ;
Tang, Zhi ;
Beji, Tarek ;
Merci, Bart .
TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2016, 56 :34-44
[29]  
Svarovsky L., 2000, SOLID LIQUID SEPARAT, VFourth
[30]   Critical velocity and backlayering distance in tunnel fires with longitudinal ventilation taking thermal properties of wall materials into consideration [J].
Tanaka, Futoshi ;
Takezawa, Kohei ;
Hashimoto, Yuji ;
Moinuddin, Khalid A. M. .
TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2018, 75 :36-42