Failure Analysis of Heat Exchanger Using Eddy Current Testing (ECT)

被引:7
作者
Saffiudeen, Mohamed Fayas [1 ]
Syed, Abdullah [1 ]
Mohammed, Fasil T. [1 ]
机构
[1] Royal Commiss Jubail & Yanbu, Jubail Tech Inst, Dept Mech Skills, Jubail Ind City, Saudi Arabia
关键词
Heat exchanger; Tube inspection; Eddy current testing; Retubing; Maintenance; CORROSION; TUBE; INSPECTION; PERFORMANCE; EROSION; NDE;
D O I
10.1007/s11668-023-01746-0
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Shell and tube heat exchangers are widely used in the oil and gas, petrochemical and nuclear power sectors. The most important aspect of the turnaround is the routine testing and inspection of the in-service heat exchanger. Heat exchangers in use are the primary cause of tube flaws such as pitting, corrosion, erosion, fretting corrosion, crevice corrosion, stress corrosion cracking, wear, galvanic corrosion, fatigue cracking, microbiologically influenced corrosion, and so forth. For research, a seamless nickel-iron-chromium alloy-tubed SB 163 (UNS 8810) heat exchanger was taken. The total number of tubes that need to be inspected is 286 tubes with a specification of 19.05 mm OD x 2.11 mm thickness x 5000 mm length. From the different advanced NDT techniques, the eddy current testing (ECT) was chosen for inspection since it has become one of the most popular NDT methods for locating discontinuities in heat exchanger tubes. A standard calibration tube was used to calibrate the system's response and set the sensitivity. During the inspection, the ECT probe was inserted from the below side up to the other end and collected while pulling the probe from the tube. Inspection data were recorded for the length of each tube. All indications were assessed, and defects were categorized as different extents of wall thickness loss after inspection. The inspection report shows how many tubes were found defective and need to be plugged or removed (retubing). From the inspection data (the result of statistics), defects like corrosion, pitting, wall loss, wear, etc., that resulted in notable material loss were identified. Inspection data also summarized where the defects were located (like between the first baffle and the second baffle) and are helpful for further research. After analysis using ECT reports, the defective tubes were categorized according to their defect percentage and location, which helps to do retubing effectively by avoiding the 100% retubing concept.
引用
收藏
页码:1898 / 1906
页数:9
相关论文
共 79 条
[1]   Performance analysis of shell and tube heat exchanger: Parametric study [J].
Abd, Ammar Ali ;
Kareem, Mohammed Qasim ;
Naji, Samah Zaki .
CASE STUDIES IN THERMAL ENGINEERING, 2018, 12 :563-568
[2]   Challenges in improving the performance of eddy current testing: Review [J].
AbdAlla, Ahmed N. ;
Faraj, Moneer A. ;
Samsuri, Fahmi ;
Rifai, Damhuji ;
Ali, Kharudin ;
Al-Douri, Y. .
MEASUREMENT & CONTROL, 2019, 52 (1-2) :46-64
[3]  
Al-Qadeeb F.E., 2005, MENDT 3 MIDDL E NDT
[4]   Review of common failures in heat exchangers - Part I: Mechanical and elevated temperature failures [J].
Ali, Murad ;
Ul-Hamid, Anwar ;
Alhems, Luai M. ;
Saeed, Aamer .
ENGINEERING FAILURE ANALYSIS, 2020, 109
[5]   Evaluation of transient eddy current oscillations response for thickness measurement of stainless steel plate [J].
Angani, Chandra Sekhar ;
Ramos, Helena Geirinhas ;
Ribeiro, Artur Lopes ;
Rocha, Tiago Jorge .
MEASUREMENT, 2016, 90 :59-63
[6]  
Angelo J. D., 2016, Case Studies in Nondestructive Testing and Evaluation, V6, P89, DOI [10.1016/j.csndt.2016.11.003, 10.1016/j.csndt.2016.11.003]
[7]  
[Anonymous], 2023, NOND EX
[8]  
[Anonymous], 2020, PERSONNEL QUALIFICAT
[9]  
[Anonymous], 2023, MAT A, V2
[10]   Failure analysis of a heat-exchanger serpentine [J].
Azevedo, CRF ;
Alves, GS .
ENGINEERING FAILURE ANALYSIS, 2005, 12 (02) :193-200