Modeling and Simulation of Time Domain Reflectometry Signals on a Real Network for Use in Fault Classification and Location

被引:3
|
作者
Fornas, Javier Granado [1 ]
Jaraba, Elias Herrero [2 ]
Bludszuweit, Hans [1 ]
Garcia, David Cervero [1 ]
Estopinan, Andres Llombart [1 ]
机构
[1] CIRCE Fdn Parque Empresarial Dinamiza, Zaragoza 50018, Spain
[2] Univ Zaragoza, Dept Elect Engn & Commun, Zaragoza 50018, Spain
基金
欧盟地平线“2020”;
关键词
Distribution networks; Fault location; Load modeling; Databases; Couplers; PSCAD; Data models; Fault classification; fault location; transmission lines; time-domain pulse reflectometry; modelling networks; distribution networks; DISTRIBUTION-SYSTEMS; LINES;
D O I
10.1109/ACCESS.2023.3253772
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Today, the classification and location of faults in electrical networks remains a topic of great interest. Faults are a major issue, mainly due to the time spent to detect, locate, and repair the cause of the fault. To reduce time and associated costs, automatic fault classification and location is gaining great interest. State-of-the-art techniques to classify and locate faults are mainly based on line-impedance measurements or the detection of the traveling wave produced by the event caused by the fault itself. In contrast, this paper describes the methodology for creating a database and a model for a complex distribution network. Both objectives are covered under the paradigm of the time-domain pulse reflectometry (TDR) principle. By using this technique, large distances can be monitored on a line with a single device. Thus, in this way a database is shared and created from the results of simulations of a real and complex distribution network modeled in the PSCAD(TM) software, which have been validated with measurements from an experimental test setup. Experimental validations have shown that the combination of the TDR technique with the modeling of a real network (including the real injector and the network coupling filter from the prototype) provides high-quality signals that are very similar and reliable to the real ones. In this sense, it is intended firstly that this model and its corresponding data will serve as a basis for further processing by any of the existing state-of-the-art techniques. And secondly, to become a valid alternative to the already well-known Test Feeders but adapted to work groups not used to the electrical world but to the environment of pure data processing.
引用
收藏
页码:23596 / 23619
页数:24
相关论文
共 50 条
  • [21] Network Cable Fault Location Based on the Wide Pulse Time Domain Reflection
    Liu, Ke
    Tian, Shulin
    Xiao, Yindong
    Xie, Di
    IEEE CIRCUITS AND SYSTEMS INTERNATIONAL CONFERENCE ON TESTING AND DIAGNOSIS, 2009, : 5 - 7
  • [22] A Time-domain-reflectometry Cable Fault Location Method Using Wavelet Pulses and Cross-correlation
    Liang, Dong
    Xu, Bingyin
    Xie, Wei
    Liu, Yang
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2020, 40 (24): : 8050 - 8057
  • [23] A Time-Domain-Reflectometry Cable Fault Location Method Using Wavelet Pulses and Cross-correlation
    LIANG Dong
    XU Bingyin
    XIE Wei
    LIU Yang
    中国电机工程学报, 2020, (24) : 8241 - 8241
  • [24] FAULT LOCATION IN OPTICAL FIBERS USING OPTICAL FREQUENCY-DOMAIN REFLECTOMETRY
    GHAFOORISHIRAZ, H
    OKOSHI, T
    JOURNAL OF LIGHTWAVE TECHNOLOGY, 1986, 4 (03) : 316 - 322
  • [25] SIMULATION OF PIPELINE HOLIDAY DETECTION BY TIME DOMAIN REFLECTOMETRY
    PAL, ZM
    JOHNSTON, RH
    INDUSTRIAL APPLICATIONS SOCIETY : 36TH ANNUAL PETROLEUM AND CHEMICAL INDUSTRY CONFERENCE, 1989, : 103 - 108
  • [26] SIMULATION OF PIPELINE HOLIDAY DETECTION BY TIME DOMAIN REFLECTOMETRY
    PAL, ZM
    JOHNSTON, RH
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1990, 26 (05) : 961 - 966
  • [27] Differential processing of location signals in time domain
    Pogribny, W
    Rozhankiwsky, I
    Drzycimski, Z
    Milewski, A
    Lozynsky, V
    SENSORS, SYSTEMS, AND NEXT-GENERATION SATELLITES IV, 2000, 4169 : 337 - 347
  • [28] CNN-based fault classification considered fault location of vibration signals
    Lee, Jeong Jun
    Cheong, Deok Young
    Min, Tae Hong
    Park, Dong Hee
    Choi, Byeong Keun
    JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY, 2023, 37 (10) : 5021 - 5029
  • [29] Performance limits of PD location based on time-domain reflectometry
    Raychem Corp, Menlo Park, United States
    IEEE Trans Dielectr Electr Insul, 2 (182-188):
  • [30] Performance limits of PD location based on time-domain reflectometry
    Du, ZF
    Willett, PK
    Mashikian, MS
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1997, 4 (02) : 182 - 188