The Effect of Conducted Emissions of Grid-Tied Three-Phase Adjustable Drives

被引:0
作者
Genc, Secil [1 ]
Muneeswaran, Venkatkumar [2 ]
Thomas, David [2 ]
Greedy, Steve [2 ]
Gundogdu, Burcu [3 ]
Sarma, Nur [4 ,5 ]
Ozgonenel, Okan [1 ]
机构
[1] Ondokuz Mayis Univ, Elect Elect Engn Dept, Samsun, Turkiye
[2] Univ Nottingham, Elect Elect Engn Dept, Nottingham, England
[3] Hakkari Univ Colemerik, VHS, Comp Technol, Hakkari, Turkiye
[4] Duzce Univ, Elect Elect Engn Dept, Duzce, Turkiye
[5] Univ Durham, Dept Engn, Durham, England
来源
ENGINEERING SCIENCE AND TECHNOLOGY-AN INTERNATIONAL JOURNAL-JESTECH | 2023年 / 46卷
关键词
Conducted emission (CE); Electromagnetic compatibility (EMC); Electromagnetic interference (EMI); Adjustable motor drive inverters; EMI FILTER;
D O I
10.1016/j.jestch.2023.101505
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Electromagnetic Interference (EMI) is generated and mitigated in power converters. EMI problems are related to high-speed power converters. This article focuses on conducted electromagnetic interference in adjustable-speed drive (ASD) systems. The electromagnetic compatibility of three-phase/level grid-connected drive inverters is investigated. The test setup is built per the CISPR16-1-2 standard, and the interferences produced from the inverter to the grid are measured. The main dependencies of conducted emissions of a power inverter, changes in the length/shape of main cables, and motor speed have been investigated under load and no load conditions. Factors affecting EMI performance and filter design issues will be addressed. A statistical approach to quantifying the frequency domain impact of conducted emission noise created on the three-phase system by operating various emission sources. Fast Fourier Transform (FFT) was applied for time-frequency domain conversion, and to evaluate with a statistical approach Minitab software was used. Then, a filter design is created to prevent these interferences from being conducted to the grid. Also, the noise attenuation of the EMI filter has been validated in the simulation. Briefly, this study fills in the blanks of uncertainties involved in measuring three-phase emissions, which helps the engineers at the design stage of three-phase converters.
引用
收藏
页数:12
相关论文
共 36 条
  • [1] The influence of positioning tables on the results of radiated EMC measurements
    Beeckman, PA
    [J]. 2001 IEEE EMC INTERNATIONAL SYMPOSIUM, VOLS 1 AND 2, 2001, : 280 - 285
  • [2] Benazza B., 2020, Modeling, Measurement and Control A, V93, P26, DOI [10.18280/mmc_a.931-404, DOI 10.18280/MMC_A.931-404]
  • [3] Evaluation of the measurement uncertainties in the conducted emissions from adjustable speed electrical power drive systems
    Betta, G
    Capriglione, D
    Tomasso, G
    [J]. IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2004, 53 (04) : 963 - 968
  • [4] Cenelec, 2013, Study Report on Electromagnetic Interference Between Electrical Equipment/Systems in the Frequency Range below 150 kHz
  • [5] CTC AppNotes, 2022, Cable Length Calculation for Hazardous Locations
  • [6] Cable Parameter Calculation for Typical Industrial Installation Methods and High-Frequency Studies
    de Souza, Warley Leal
    de Paula, Helder
    De Conti, Alberto
    Mesquita, Renato C.
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2018, 54 (04) : 3919 - 3927
  • [7] Electromagnetic Compatibility, 1997, IEC Standard 61000-4-7
  • [8] Ensini L, 2018, IEEE INT SYMP ELEC, P214, DOI 10.1109/EMCEurope.2018.8485174
  • [9] Gallo D., 2005, 10 IMEKO TC4 INT WOR
  • [10] Novel Three-Phase CM/DM Conducted Emission Separator
    Heldwein, Marcelo Lobo
    Biela, Juergen
    Ertl, Hans
    Nussbaumer, Thomas
    Kolar, Johann W.
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2009, 56 (09) : 3693 - 3703