Experimental energy evaluation of R516A and R513A as replacement of R134a in refrigeration and air conditioning modes

被引:7
作者
Mendez-Mendez, D. [1 ]
Perez-Garcia, V. [1 ]
Morales-Fuentes, A. [2 ]
机构
[1] Univ Guanajuato, Dept Mech Engn, DICIS, IRSE Res Grp, Km 3-5 1 8, Salamanca Valle De Santia 36885, Guanajuato, Mexico
[2] Univ Autonoma Nuevo Leon, Fac Ingn Mec an & Electr FIME, Ave Univ S-N, Cd Univ, San Nicolas De Los Garza 66445, Nuevo Leon, Mexico
关键词
R134a drop-in replacement; R516A; R513A; Low-GWP; COP; THERMOCOUPLE;
D O I
10.1016/j.ijrefrig.2023.06.003
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents the experimental energy behavior of R516A and R513A compared to R134a as baseline refrigerant in refrigeration and air conditioning temperatures. The comparative is made in an evaporating temperatures range of 261 K to 285 K with step 4 K increases, taking condensing temperatures of 308 K, 313 K, and 318 K. Results show that the best energy performance was reached by R134a while the worst were for R513A in all experimental tests, here R516A shows the smallest difference respect to R134a being just 5.4%. Also, R134a showed lower values in discharge pressure respect to its replacements, while R516A exhibited the lower discharge temperatures. R513A showed lower useful superheating for refrigeration applications, while R516A achieved the minor useful superheating for air conditioning temperatures only below R134a. Finally, R513A reached the higher value of volumetric refrigeration capacity for air conditioning temperatures at 308 K condensing temperature. All results were obtained considering the optimal refrigerant mass charge which were 682 g, 655 g, and 632 g for R134a, R513A and R516A, respectively.
引用
收藏
页码:73 / 83
页数:11
相关论文
共 27 条
  • [1] Comprehensive experimental evaluation of R1234yf-based low GWP working fluids for refrigeration and heat pumps
    Al-Sayyab, Ali Khalid Shaker
    Navarro-Esbri, Joaquin
    Barragan-Cervera, Angel
    Kim, Sarah
    Mota-Babiloni, Adrian
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2022, 258
  • [2] [Anonymous], 2023, NIST STANDARD REFERE, DOI 10.18434/T4D303
  • [3] ASHRAE, 2019, Standard 34,designation and safety classification of refrigerants
  • [4] The hunt for nonflammable refrigerant blends to replace R-134a
    Bell, Ian H.
    Domanski, Piotr A.
    McLinden, Mark O.
    Linteris, Gregory T.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 104 : 484 - 495
  • [5] Experimental evaluation of R513A as a low GWP refrigerant to replace R134a in a domestic refrigerator
    Belman-Flores, J. M.
    Heredia-Aricapa, Y.
    Pardo-Cely, D.
    Rodriguez-Valderrama, D. A.
    De Alba-Rosano, M.
    Silva-Romero, J. C.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2022, 142 : 148 - 155
  • [6] Chen X., 2022, Journal of Mechanical Engineering and Automation, V11, P19, DOI [10.5923/j.jmea.20221101.03, DOI 10.5923/J.JMEA.20221101.03]
  • [7] Conference of the Parties, 2022, 27 SESS SHARM EL SHE
  • [8] He QH, 2011, P IEEE SEMICOND THER, P280, DOI 10.1109/STHERM.2011.5767212
  • [9] Thermodynamic analysis of two evaporator vapor compression refrigeration system with low GWP refrigerants in automobiles
    Khatoon, Salma
    Karimi, Munawar Nawab
    [J]. INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2023, 31 (01)
  • [10] Thermocouple and Infrared Sensor-Based Measurement of Temperature Distribution in Metal Cutting
    Kus, Abdil
    Isik, Yahya
    Cakir, M. Cemal
    Coskun, Salih
    Ozdemir, Kadir
    [J]. SENSORS, 2015, 15 (01): : 1274 - 1291