Performance Against Direct Lightning on 10-kV Overhead Distribution Lines With Counterpoise Wires

被引:3
|
作者
Cao, Jinxin [1 ]
Du, Yaping [2 ]
Ding, Yuxuan [2 ]
Li, Zhe [2 ]
Chen, Mingli [2 ]
Qi, Ruihan [3 ]
机构
[1] Wuhan Univ, Dept Elect Engn & Automat, Wuhan 430072, Peoples R China
[2] Hong Kong Polytech Univ, Dept Bldg Environm & Energy Engn, Hong Kong, Peoples R China
[3] China Southern Power Grid, Power Res Inst, Guangzhou 510760, Peoples R China
关键词
Counterpoise wire; lightning protection; Monte Carlo method; partial element equivalent circuit (PEEC); shield wire (SW); surge arrester (SA); ELECTROMAGNETIC-FIELD ANALYSIS; INDUCED VOLTAGES; SURGE ARRESTERS; MODEL; TOWER; BEHAVIOR;
D O I
10.1109/TEMC.2023.3243734
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This article investigates the lightning performance of a 10-kV overhead distribution line equipped with grounding counterpoise wires under extremely low soil conductivity conditions. A partial element equivalent circuit model with the lossy ground being considered is adopted for lightning surge investigation. The Monte Carlo method considering natural lightning randomness is used for the flashover rate evaluation. It is found that under extremely low soil conductivity conditions, the simple vertical grounding rod is not effective in lightning protection, while the performance is significantly improved with extended counterpoise wires. The single-row counterpoise wire with a length of line span performs best. The single-row counterpoise wire with a half-length of line span is a competitive one, due to a half-cost reduction and a competitive performance. If a higher performance of lightning protection is expected, further extending the length of counterpoise wires would be ineffective. Increasing the CFO level or installing surge arresters on all poles would be the possible solution.
引用
收藏
页码:1108 / 1116
页数:9
相关论文
共 50 条
  • [41] LIGHTNING PERFORMANCE OF OVERHEAD LINES.
    Chisholm, W.A.
    Buchan, P.G.
    Research Review - Ontario Hydro, 1981, (03): : 19 - 24
  • [42] Statistical Safety Factor in Lightning Performance Analysis of Overhead Distribution Lines
    Sarajcev, Petar
    Lovric, Dino
    Garma, Tonko
    ENERGIES, 2022, 15 (21)
  • [43] Lightning Induced Over-voltage Model and Application in Distribution Lines With Overhead Ground Wires
    Qi R.
    Cai H.
    Liao M.
    Jia L.
    Liu G.
    Liu Y.
    Dianwang Jishu/Power System Technology, 2021, 45 (06): : 2413 - 2419
  • [44] The Lightning Protection Performance of the Composite Material Cross-Arm in 10 kV Distribution Lines
    Cai, Wei
    Deng, Heming
    Zhang, Rui
    Zhang, Zichao
    Zeng, Qiang
    2014 INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2014, : 242 - 245
  • [45] Lightning protection of overhead power distribution lines
    Yokoyama, Shigeru
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2007, 2 (05) : 491 - 496
  • [46] LIGHTNING - INDUCED OVERVOLTAGES ON OVERHEAD DISTRIBUTION LINES
    ERIKSSON, AJ
    STRINGFELLOW, MF
    MEAL, DV
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (04): : 960 - 968
  • [47] Evaluation of a Direct Lightning Strike to the 24 kV Distribution Lines in Thailand
    Sestasombut, Pornchai
    Ngaopitakkul, Atthapol
    ENERGIES, 2019, 12 (16)
  • [48] Calculation of Lightning Trip-out Rates for 10 kV Overhead Distribution Line
    Lu Zejun
    Gu Shanqiang
    Zhao Chun
    2014 INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2014, : 667 - 670
  • [49] An accurate approach for the evaluation of the performance of overhead distribution lines due to indirect lightning
    Andreotti, Amedeo
    Araneo, Rodolfo
    Mahmood, Farhan
    Pierno, Antonio
    ELECTRIC POWER SYSTEMS RESEARCH, 2020, 186
  • [50] Lightning performance of grounding systems of overhead lines
    Visacro, Silverio
    Silveira, Fernando Henrique
    2014 INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2014, : 1386 - 1389